                        www.hampton-fi re.com
Owners & 
H25 Direct Vent Gas Fireplace
Installation Manual
MODELS:      H25-NG1 Natural Gas       H25-LP1 Propane   
WARNING:  FOR YOUR SAFETY This appliance may only be 
If the information in these instructions are not installed in an aftermarket 
followed exactly, a fi re or explosion may result What to do if you smell gas: permanently located, manu-
causing property damage, personal injury or loss  Do not try to light any appliance factured (USA only) or mobile 
of life. 
                    
                    Inhaltszusammenfassung zur Seite Nr. 2 
                    
                        ® HAMPTON Direct Vent Freestanding Gas Stove To the New Owner: Congratulations!  ® You are the owner of a state-of-the-art Hampton Gas Stove by  FPI FIREPLACE PRODUCTS INTERNATIONAL  LTD. The H25 is a hand crafted appliance and has been designed to provide you with all  the warmth and charm of  a wood fi replace at the fl ick of a switch.  The model H25 has been approved by Warnock Hersey for both safety and  effi ciency.  As it also bears our own mark, it promises to provide you with economy, comf
                    
                    Inhaltszusammenfassung zur Seite Nr. 3 
                    
                        TABLE OF CONTENTS Gas Pipe  .....................................................................27 Unit Dimensions ............................................................2 Pressure Testing ..........................................................27 Conversion Kit #434-969 from NG to LP .....................28 SAFETY LABEL Log Set Installation ......................................................31 Decorative Door Grill Installation .................................33 Copy of Safety Label
                    
                    Inhaltszusammenfassung zur Seite Nr. 4 
                    
                        SAFETY LABEL ® This is a copy of the label that accompanies  NOTE: Hampton units are constantly being  each  Direct Vent Freestanding Gas Stove.  improved. Check the label on the unit and if  We have printed a copy of the contents here  there is a difference, the label on the unit is  for your review.  the correct one. COPY OF SAFETY LABEL FOR H25-NG1 & H25-LP1 For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the  Commonwealth of Massachu
                    
                    Inhaltszusammenfassung zur Seite Nr. 5 
                    
                        REQUIREMENTS  MA Code - CO Detector (for the State of Massachusetts only) 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements:  (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for  residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than  seven (7) feet above finished gr
                    
                    Inhaltszusammenfassung zur Seite Nr. 6 
                    
                        INSTALLATION This appliance installation must comply with the  IMPORTANT MESSAGE  DUE TO HIGH TEMPERATURES,  manufacturer's installation instructions and local  THE APPLIANCE SHOULD BE  codes, if any. In the absence of local codes fol- SAVE THESE  low the current National Fuel Gas Code, ANSI LOCATED OUT OF TRAFFIC AND  INSTRUCTIONS Z223.1 and the current National Electrical Code  AWAY FROM FURNITURE AND  ANSI/NFPA 70 in the U.S.A., and the current  DRAPERIES. The  Direct Vent Freestanding Gas St
                    
                    Inhaltszusammenfassung zur Seite Nr. 7 
                    
                        INSTALLATION Thermostat. Some areas may have further  2) If required, adjusting the primary air to ensure  Emissions from burning  wood or gas could  requirements, check local codes before  that the fl ame does not carbon. First allow  contain chemicals known to the State of Cali- installation. the unit to burn for 15-20 min. to stabilize. fornia to  cause cancer, birth defects or other  reproductive harm. 5) This appliance is Listed for Alcove installa- CAUTION: Any alteration to the product tha
                    
                    Inhaltszusammenfassung zur Seite Nr. 8 
                    
                        INSTALLATION 4) Remove the nylon hole plug from the control  OPTIONAL FAN  LOCATING YOUR  panel. GAS STOVE INSTALLATION 5) Install the fan speed controller onto the    control panel and secure with nut and  Fan Kit Contains: When selecting a location for your stove, ensure  washer. Connect the red and black wires  that the clearances listed above are met as well  from the wire harness to speed controller.  as ensuring that there is adequate accessibility Qty. Description NOTE: Speed control wire
                    
                    Inhaltszusammenfassung zur Seite Nr. 9 
                    
                        INSTALLATION 9) Place the blower close to the base of the unit and feed the long red 12) Before re-attaching the rear access panel, the valve wires and the  fan wires need to be connected. and black wires through the opening of the base of the unit and  connect them to the thermodisc.  Re-connect the red and grey valve wires.  Connect the fan wires. 10) Feed the short red and black wires through the small hole at the base  of the unit. 13) Slide the Rear Access Panel back into position and secur
                    
                    Inhaltszusammenfassung zur Seite Nr. 10 
                    
                        INSTALLATION VENTING INSTALLATION  SAFETY PRECAUTIONS  INTRODUCTION PRECAUTIONS FOR THE INSTALLER The Horizontal Termination Kit and the Simpson These venting systems are engineered products  1) Wear gloves and safety glasses for protec- Dura-Vent Direct Vent System Model DV-GS that have been designed and tested for use tion. venting systems, in combination with the  Direct with the H25-NG1, and H25-LP1. The warranty  Vent Freestanding Gas Stoves, H25-NG1, and will be voided and serious fi re, he
                    
                    Inhaltszusammenfassung zur Seite Nr. 11 
                    
                        INSTALLATION EXTERIOR VENT TERMINAL LOCATIONS ® Hampton H25-1 Direct Vent Freestanding Gas Stove 11 A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) J= Clearance to service regulator vent outlet *(min. 36"/90cm) B= Clearance to window or door that may be opened *(12"/30cm) K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to  C= Clearance to permanently closed window *(min. 12"/30cm) any other appliance *(12"/30cm) D= Vertical clea
                    
                    Inhaltszusammenfassung zur Seite Nr. 12 
                    
                        INSTALLATION RIGID PIPE VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from FPI. ® Description     Simpson Dura-Vent     Selkirk            Amerivent               Security ® TM ®            Direct VentGS Direct-Temp          Direct Vent          Secure Vent 6" Pipe Length, Galvanized   908             4DT-6  N/A  SV4L6 6" Pipe Length, Black    908B             4DT-6B  N/A SV4LB6 7" Pipe Length, Galvanized   N/A             N/A   4D7 #N/A 7" Pipe Length, Black   
                    
                    Inhaltszusammenfassung zur Seite Nr. 13 
                    
                        INSTALLATION RIGID PIPE VENTING SYSTEMS Horizontal or Vertical Terminations Vertical Alternate  Termination Horizontal  Cap Termination  Caps Storm Collar Vinyl Siding Standoff (Optional) Flashing Horizontal Termination Ceiling Firestop Cap Wall Thimble Pipe Length Adj.Pipe Length 11" - 14-5/8" o 90 Elbow WARNING: Do not combine venting components from  24" Pipe different venting systems. Length TM However use of the the AstroCap and FPI  Riser is acceptable with all systems. This product has be
                    
                    Inhaltszusammenfassung zur Seite Nr. 14 
                    
                        INSTALLATION VENTING ARRANGEMENTS Horizontal Terminations for Vertical Terminations Systems for  All Venting Systems Residential Manufactured and Mobile Homes The shaded areas in the diagram below show all The shaded area in the diagram below shows all allowable combinations of straight  o vertical and offset to vertical runs with vertical terminations. Maximum two 45  allowable combinations of vertical runs with hori- O zontal terminations.  Maximum one 90 elbow (two  elbows. o o 45 elbows equa
                    
                    Inhaltszusammenfassung zur Seite Nr. 15 
                    
                        INSTALLATION o Horizontal Venting with Two (2) 90 Elbows o o One 90 elbow = Two 45 elbows. With these options, maxi-  Option     V          H + H1 mum total pipe length is 30       A) 2'  Min.      4' Max. feet with minimum of 6 feet       B) 3'  Min.      5' Max. total vertical and maximum       C) 4'  Min.      6' Max. 8 feet total horizontal. Please note minimum 1       D) 5'  Min.      7' Max. o foot between 90 elbows       E) 6'  Min.      8' Max.  is required. H1 Lengths do not include elb
                    
                    Inhaltszusammenfassung zur Seite Nr. 16 
                    
                        INSTALLATION o Vertical Venting with Two (2) 90 Elbows o o One 90 elbow = Two 45 elbows.  Option V     H V + V1 With these options, max. total  pipe length is 30 feet with min.        A) 1' Min. 4' Max. 2' Min.  of 6 feet total vertical and max.        B) 2' Min. 5' Max. 3' Min.  8 feet total horizontal.       C) 3' Min. 6' Max. 4' Min.  Please note min. 1 foot  o       D) 4' Min. 7' Max. 5' Min. between 90 elbows is re- quired.       E) 5' Min. 8' Max. 6' Min.  V1 Lengths do not include elbow i
                    
                    Inhaltszusammenfassung zur Seite Nr. 17 
                    
                        INSTALLATION VERTICAL TERMINATION WITH CO-LINEAR FLEX SYSTEM Masonry chimneys may take various contours which the fl exible liner will accommodate. However,  THE APPLIANCE MUST NOT BE  CONNECTED TO A CHIMNEY FLUE keep the fl exible liner as straight as possible, avoid unnecessary bending. SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE. The Air Intake pipe must  be attached to the inlet air collar of the termination cap. This appliance is designed to be attached to  Alternate Approved Caps Require
                    
                    Inhaltszusammenfassung zur Seite Nr. 18 
                    
                        INSTALLATION DV STOVE HORIZONTAL VENT KIT DV 2 ft.  Stove Vent Kit (Part # 946-116)  and DV 4 ft. Stove Vent Kit (946-216) includes all the parts needed  to install the H25 Direct Vent unit with minimum horizontal and vertical vent dimensions. For installations  that require longer vertical and/or horizontal vents use the Dura-Vent system as shown in the "Dura-Vent  Termination Kit" and "Dura-Vent Venting Components" sections.     Qty. Description 1) 1  Rigid Pipe Section (Kit # 946-116: 2 ft. (
                    
                    Inhaltszusammenfassung zur Seite Nr. 19 
                    
                        INSTALLATION 13) Secure the 4" dia. fl ex liner with adapter  onto the stove collar. Put a bead of Mill-Pac  around the appliance adapter and secure  with 3 screws (#8 x 1/2, stainless steel). o 14) Attach the 45 elbow onto the starter col- lar by sealing with Mill-Pac and/or high  temperature silicone and securing with 3  of the #8 x 1/2" (black) screws.  o 15) Attach the pipe section to the 45 elbow by  sealing with Mill-Pac and/or high tempera- ture silicone and securing with 3 of the #8  x 1/
                    
                    Inhaltszusammenfassung zur Seite Nr. 20 
                    
                        INSTALLATION RESIDENTIAL AND MANUFACTURED HOMES / MOBILE HOMES  MINIMUM HORIZONTAL TERMINATION INSTALLATIONS Planning Your venting Installation ® You will require the following components with your new Hampton Rear Vent Direct Vent Free- standing Gas Stove. Please review your product to make sure you have everything you need. In  See the "Exterior Vent Terminatal Locations"  the event that you are missing any part, contact your dealer. Decorative brass  section for requirements. The H25 is appro