Resumen del contenido incluido en la página 1 
                    
                         
 
Owner’s Manual 
 
 
 
Extended-Run 3-Phase Battery Cabinet 
 
C US 
 
Not suitable for mobile applications. 
 
 
 
p. 2 
 1 – Introduction 
 
 
 2 – Important Safety Instructions p. 3 
  
 3 – Battery Cabinet Installation p. 5 
  
p. 5 
 3-1 Preparation 
  
  
p. 5 
 3-2 Transportation 
 
 
p. 5 
 3-3 Mechanical Check 
 
 
 3-4 Internal Wiring (Typical) p. 6 
  
 3-5 Preliminary Electrical Check p. 6 
  
p. 6 
 3-6 Battery Cabinet Placement 
 
 
p. 7 
 3-7 Electrical Connection 
 
 
p. 7 
 3
                    
                    Resumen del contenido incluido en la página 2 
                    
                             1 – Introduction      Tripp Lite’s Extended-Run 3-Phase Battery Cabinets connect to SmartOnline 3-Phase UPS Systems to provide long-lasting battery  backup for data centers, telecommunications, networks, industrial facilities, security, emergency systems and other mission-critical  applications that require high capacity, high availability and extended runtime.    Features     Battery cabinets are available in voltages from 240 VDC through 480 VDC and capacities from 33 to 720 ampere-hours 
                    
                    Resumen del contenido incluido en la página 3 
                    
                             2 – Important Safety Instructions      SAVE THESE INSTRUCTIONS   All sections of this manual contain instructions and warnings that must be followed during the installation and operation of the  battery cabinet described in this manual. Read ALL instructions thoroughly before attempting to move, install or connect your  battery cabinet. Failure to comply may invalidate the warranty and cause serious property damage and/or personal injury.        DANGER! LETHAL HIGH VOLTAGE HAZARD!    All wi
                    
                    Resumen del contenido incluido en la página 4 
                    
                               2 – Important Safety Instructions (continued)      Battery Warnings    • The battery cabinet does not require routine maintenance by the user. There are no user-serviceable parts inside. Only  qualified, knowledgeable service personnel familiar with all required precautions should open the access panels for any  reason. Keep unauthorized personnel away from batteries.  • The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries. Do not attempt to add water to the
                    
                    Resumen del contenido incluido en la página 5 
                    
                             3 – Battery Cabinet Installation      Read Section 2 – Important Safety Instructions Before Installation          3-1 Preparation     • At your site, prepare to off-load the battery cabinet from the delivery truck and transport it to the final installation location.  Consider both the packaged weight and dimensions.  • Assure that the floor can bear the load of the specific battery cabinet being installed. The battery cabinet must be installed in a  structurally sound area with a level floo
                    
                    Resumen del contenido incluido en la página 6 
                    
                             3 – Battery Cabinet Installation (continued)       3-4 Internal Wiring (Typical)    • Battery cabinets use multiple 6 VDC or 12 VDC batteries connected in series to provide nominal DC voltages ranging from  240 VDC to 480 VDC.  • Internal cabling is sized for specific application load currents. The insulated cables can be 2 AWG, 4 AWG, 2/0 AWG, 4/0  AWG or dual 2/0 AWG.  • Each battery cabinet includes a specific wiring diagram. Some battery cabinets may contain series-parallel battery stri
                    
                    Resumen del contenido incluido en la página 7 
                    
                             3 – Battery Cabinet Installation (continued)       3-7 Electrical Connection      DANGER! LETHAL HIGH VOLTAGE HAZARD!    All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual    and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and    property damage.      • The battery cabinet should be connected to the load through a DC disconnect switch or a DC circuit breaker. This allows the  battery to
                    
                    Resumen del contenido incluido en la página 8 
                    
                             4 – Operation and Charging       4-1 Determine Charging Voltages    To determine the appropriate equalization (freshening) charge voltage and float charge voltage, multiply the number of batteries  connected in series in the battery cabinet by the recommended charging voltage per unit.    For example:    A +/- 240 VDC cabinet containing 40 each of the UPS12-400MR batteries in series would use the following charging voltages:    Freshening/Equalization Charge Voltage = 20 x 14.4 VDC/unit ave
                    
                    Resumen del contenido incluido en la página 9 
                    
                             5 – Maintenance      The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries, which are maintenance-free relative to the  electrolyte. You cannot add water to these batteries or sample the electrolyte specific gravity. It is necessary, however, to periodically  check the charging voltage, temperature and connections of the individual battery units.     5-1 Maintenance Schedule    Quarterly Check    1. Measure individual battery unit temperature. (Measure with a d
                    
                    Resumen del contenido incluido en la página 10 
                    
                             6 – Diagrams       6-1 Battery Cabinet Diagram (4 Shelves)    4.38  Breaker Mounting Plate 8.25  24.75  6 22  16  79  16  16  4.5  4  2.25  4.5 11.75 5.5  15.75  Side View Front View Side View  40.25  30.25  6  Top View  6  Front of Cabinet  Conduit Knockouts  Front of Cabinet  Conduit Knockouts  17.25  34.5  Side View Bottom View Side View    Note: All dimensions are in inches.    [10]                                                                                                          
                    
                    Resumen del contenido incluido en la página 11 
                    
                             6 – Diagrams (continued)       6-2 Battery Cabinet Diagram (3 Shelves)    3.25  30  6  58  32  Top View  Breaker  8.25  Mounting  Plate  24  16 11  2.25  15.75  4.5 4.5  Side View Side View  14  16  4  4 10.25  Front View  Conduit  Conduit  Knockouts  Knockouts  Front of Cabinet Front of Cabinet  14.5  29  Side View Side View  Bottom View    Note: All dimensions are inches.          [11]                                                                                                         
                    
                    Resumen del contenido incluido en la página 12 
                    
                             6 – Diagrams (continued)       6-3 Battery and Breaker Diagrams (240 VDC)    Shelf 2  Battery  Positive  To UPS  Positive  To UPS  Shelf 3 Negative  Battery  Negative  UL-Listed  Breaker  Shelf 1 (Bottom)  To Fuse or Breaker  Termination    Notes:    • All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.  • Terminal block is UL-recognized and rated for 600 VDC.  • Breaker is UL-listed and rated for 150 A, 600 VDC, 25  KAIC.  • Cabinets with breakers are shipped with the breaker in the
                    
                    Resumen del contenido incluido en la página 13 
                    
                             6 – Diagrams (continued)       6-4 Battery and Breaker Diagrams (+/- 240 VDC)    Shelf 4 (Top)  Battery  Positive  Shelf 3  To UPS  Positive  To UPS  Negative  Battery  Negative  UL-Listed Breaker  To UPS From Battery  Center Tap Center Tap  Shelf 2  Shelf 1 (Bottom)  To Fuse or Breaker To Center Tap  Termination Termination    Notes:    • All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.  • Terminal block is UL-recognized and rated for 600 VDC.  • Breaker is UL-listed and rated fo
                    
                    Resumen del contenido incluido en la página 14 
                    
                             6 – Diagrams (continued)       6-5 Integrated Battery Charger (Select Models)    6.25  MAX  0.5  13.5 12.5  Terminal Block Detail  Input Voltage Selection AC L       N -        +   Input    For 120 VAC Jumper: 120 Output  2 & 3, 3 & 4, 5 & 6 VAC    Output  For 208 VAC Jumper:  1 & 2, 4 & 5    For 240 VAC Jumper:  2 & 3, 4 & 5  Warning: Do not connect the battery charger  AC input to the UPS system output. The battery  charger requires a separate AC supply circuit.      Notes:    • All dimen
                    
                    Resumen del contenido incluido en la página 15 
                    
                             7 – Specifications       7-1 Dimensions and Floor Loading    Dimensions  Battery Cabinet Model Shelves (Width x Depth x Height) Weight Floor Loading  2  32 x 30 x 58 inches 1760 lb 264 lb/ft BP240V99 3 2 (81.3 x 76.2 x 147.3 cm) (800 kg) (1292 kg/m )  2  32 x 30 x 58 inches 1920 lb 288 lb/ft BP240V120 3  2 (81.3 x 76.2 x 147.3 cm) (873 kg) (1410 kg/m )  2  32 x 30 x 58 inches 1983 lb 297 lb/ft BP240V1207C 3  2 (81.3 x 76.2 x 147.3 cm) (901 kg) (1452 kg/m )  2  32 x 30 x 58 inches 2400 lb 36
                    
                    Resumen del contenido incluido en la página 16 
                    
                             8 – Storage and Service      Storage  The battery cabinet must be stored in a clean, secure environment with a temperature less than 40° C (104° F) and a relative humidity  less than 90% (non-condensing). Store the battery cabinet in its original shipping container if possible. Charge the batteries for at least  24 hours prior to use. Do not rely on the battery cabinet to provide backup power to connected equipment until the batteries are fully  charged. Note: If the UPS system remains off