Resumen del contenido incluido en la página 3
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions p UCT odr f ea TUres Standard Features • R-410A chlorine-free refrigerant • TuffTube™ tubular heat exchanger • High-efficiency scroll compressor • Copper tube / aluminum fin coils • High- and low-pressure switches • High-capacity, steel-cased filter dryer • Built-in filter rack with standard 2” filters (convertible to 4” filters) • 24-volt terminal strip • Contactor with lugs • Easy to service • Bottom utility entry • Com
Resumen del contenido incluido en la página 4
p odUCT r s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions — 15 Tons CPG180350 CPG180350 CPG180*** 3B*** 4B*** 7B*** Cooling Capacity Total, BTU/h 180,000 180,000 180,000 Sensible BTU/h 127,500 127,500 127,500 EER / IEER 10.8 / 11 10.8 / 11 10.8 / 11 Decibels 88 88 88 ARI Reference #s 3965698 3965698 3965698 Heating Capacity Max. Input: High / Low KBTU/h 350 / 262 350 / 262 350 / 262 Output: High / Low KBTU/h 280 / 210 280 / 210 280 / 210 Steady State Efficie
Resumen del contenido incluido en la página 5
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions — 20 Tons CPG240 CPG240 CPG240 4003B*** 4004B*** 4007B*** Cooling Capacity Total, BTU/h 240,000 240,000 240,000 Sensible BTU/h 170,000 170,000 170,000 EER / IEER 9.8 / 10.0 9.8 / 10.0 9.8 / 10.0 Decibels 88.3 88.3 88.3 AHRI Reference #s 3897346 3897346 3897346 Heating Capacity Max. Input High / Low (KBTU/h) 400 / 300 400 / 300 400 / 300 Output BTU/h 320 / 240 320 / 240 320 / 240 Steady State Efficiency (
Resumen del contenido incluido en la página 6
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions a woirfl d a Ta — 15 Tons Standard Belt Drive ― Down Shot Turns Open ESP 0 1 2 3 4 5 6 (" H₂O) CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0.2 0.00 6827 2.67 6394 2.28 5982 1.94 0.4 7079 3.20 6623 2.76 6161 2.34 5706 1.98 5271 1.66 0.6 6903 3.32 6405 2.83 5923 2.41 5434 2.02 4949 1.68 0.8 6717 3.42 6198 2.92 5668 2.45 5152 2.05 1.0 5975 2.99 5418 2.51 1.2 5147 2.55 High-Static Belt Drive ― Down Shot Turns Open ESP 0 1
Resumen del contenido incluido en la página 7
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions a woirfl d a Ta — 20 Tons Standard Belt Drive ― Down Shot Turns Open ESP 0 1 2 3 4 5 6 (" H₂O) CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0.2 9359 4.92 8991 3.79 8621 3.54 8188 3.27 7826 3.04 0.4 9018 3.18 8632 4.39 8251 3.39 7867 3.15 7363 2.85 6992 2.63 0.6 8279 2.96 7879 3.86 7484 2.99 7085 2.75 0.8 7957 4.82 7513 2.73 7097 3.35 1.0 7179 4.23 6716 2.49 1.2 6368 3.66 High-Static Belt Drive ― Down Shot Turns Open ESP
Resumen del contenido incluido en la página 8
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions e andedxp Cooling d a Ta — 15 Tons 8 www.goodmanmfg.com SS-CPG180-240 Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 MBh 176.4 182.8 200.3 - 172.3 178.6 195.6 - 168.2 174.3 191.0 - 164.1 170.1 186.3 - 155.9 161.6 177.0 - 144.4 149.7 164.0 - S/T 0.71 0.59 0.41 - 0.74 0.62 0.43 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.8
Resumen del contenido incluido en la página 9
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions e andedxp Cooling d a Ta — 15 Tons (CT on .) SS-CPG180-240 www.goodmanmfg.com 9 Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 MBh 182.6 186.5 199.3 213.1 178.3 182.2 194.7 208.1 174.1 177.9 190.0 203.1 169.8 173.5 185.4 198.2 161.3 164.9 176.1 188.3 149.4 152.7 163.2 174.4 S/T 0.89 0.83 0.68 0.51 0.92 0.86 0.70 0
Resumen del contenido incluido en la página 10
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions e andedxp Cooling d a Ta — 20 Tons 10 www.goodmanmfg.com SS-CPG180-240 Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 MBh 235.2 243.8 267.1 - 229.7 238.1 260.9 - 224.2 232.4 254.6 - 218.8 226.8 248.4 - 207.8 215.4 236.0 - 192.5 199.5 218.6 - S/T 0.71 0.59 0.41 - 0.74 0.62 0.43 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.
Resumen del contenido incluido en la página 11
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions e andedxp Cooling d a Ta — 20 Tons (CT on .) SS-CPG180-240 www.goodmanmfg.com 11 Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 MBh 243.4 248.7 265.7 284.1 237.8 242.9 259.6 277.5 232.1 237.2 253.4 270.9 226.4 231.4 247.2 264.3 215.1 219.8 234.8 251.0 199.3 203.6 217.5 232.5 S/T 0.89 0.83 0.68 0.51 0.92 0.86 0.70
Resumen del contenido incluido en la página 12
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions d imensions 88⁷/₃₂” 133½” 50⁹/₃₂” 5⁵/₃₂” Vertical Discharge (Top of Unit) Gas Inlet Location (¾” NPT) 9⅔” 46¹/₁₀” Flue Vent 12 www.goodmanmfg.com SS-CPG180-240 2 x 21” 2 x 60” 7” 22” Return 48” 22” Supply
Resumen del contenido incluido en la página 13
p UCT odr s C pe ifiCa Tions p UCT odr s C pe C ifi a Tions UniT CC learan es Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compres- sor removal or service access, and to ensure proper ventilation and condenser airflo
Resumen del contenido incluido en la página 14
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions r oof CUB r i T ns alla Tion — r igging Provisions for forks have been included in the unit base frame. No other fork locations are approved. • Unit must be lifted by the four lifting holes located at the base frame corners. • Lifting cables should be attached to the unit with shackles. • The distance between the crane hook and the top of the unit must not be less than 60”. • Two spreader bars must span over the unit to prevent
Resumen del contenido incluido en la página 15
p UCT odr s C pe ifiCa Tions p UCT odr s C pe C ifi a Tions r oof CUB r i T ns alla Tion Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors Association. Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb. Full perimeter roof curbs are available from the factory and are shipped unasse
Resumen del contenido incluido en la página 16
p UCT odr s peCC ifi a Tions p UCT odr s C pe C ifi a Tions w iring d gramia — C1 pg 80/240***3B*** T hree -p hase 208-230 Bel T d rive 16 www.goodmanmfg.com SS-CPG180-240 Wiring is subject to change. Always High Voltage: Disconnect all power before servicing or installing this unit. Multiple power refer to the wiring diagram or the ⚠ WARNING ⚡ sources may be present. Failure to do so may cause property damage, personal injury, or death. unit for the most up-to-date wiring.
Resumen del contenido incluido en la página 17
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions w iring d gramia — C1 pg 80/240***3B*** T hree -p hase 208-230 Bel T d rive SS-CPG180-240 www.goodmanmfg.com 17 Wiring is subject to change. Always High Voltage: Disconnect all power before servicing or installing this unit. Multiple power refer to the wiring diagram or the ⚠ WARNING ⚡ sources may be present. Failure to do so may cause property damage, personal injury, or death. unit for the most up-to-date wiring.
Resumen del contenido incluido en la página 18
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions w iring d gramia — C1 pg 80/240***4B***/7B* T hree -p hase 460/575 Bel T d rive 18 www.goodmanmfg.com SS-CPG180-240 Wiring is subject to change. Always High Voltage: Disconnect all power before servicing or installing this unit. Multiple power refer to the wiring diagram or the ⚠ WARNING ⚡ sources may be present. Failure to do so may cause property damage, personal injury, or death. unit for the most up-to-date wiring.
Resumen del contenido incluido en la página 19
p UCT odr s C pe C ifi a Tions p odUCT r s C pe C ifi a Tions w iring d gramia — C1 pg 80/240***4B/7B*** T hree -p hase 460/575 Bel T d rive SS-CPG180-240 www.goodmanmfg.com 19 Wiring is subject to change. Always High Voltage: Disconnect all power before servicing or installing this unit. Multiple power refer to the wiring diagram or the ⚠ WARNING ⚡ sources may be present. Failure to do so may cause property damage, personal injury, or death. unit for the most up-to-date wiring.
Resumen del contenido incluido en la página 20
p UCT odr s C pe C ifi a Tions p UCT odr s C pe C ifi a Tions a CCessories Fits Item # Description Model Sizes 14CURB180240 Roof Curb 14" Tall 15-20 tons 25FD180240 25% Manual Fresh Air Damper 15-20 tons 25MFD180240 25% Motorized Fresh Air Damper 15-20 tons CDK180 Concentric Duct Kit 15 tons CDK240 Concentric Duct Kit 20 tons DNECONGS180240 Downflow Economizer 15-20 tons GHRC-1 Hurricane Restraint Clip All Models HAKT36300 High Altitude Kit All Models LPKT180240 LP Conversion Kit HSKT180 High St