Résumé du contenu de la page N° 1
UNI-TRAN PREMIUM PLUS
TOXIC GAS DETECTOR
USER MANUAL
UT-P+-STXXXX
(Picture of ST1200 Premium Plus Toxic Gas Detector)
Part Number: MAN-0005-00 Rev. 3
Résumé du contenu de la page N° 2
Résumé du contenu de la page N° 3
Copyright © 2003 Net Safety Monitoring Inc. Printed in Canada This manual is provided for informational purposes only. Although the information contained in this manual is believed to be accurate, it could include technical inaccuracies or typographical errors. Changes are, therefore, periodically made to the information within this document and incorporated without notice into subsequent revisions of the manual. Net Safety Monitoring Inc. assumes no responsibility for any errors that may be co
Résumé du contenu de la page N° 4
Résumé du contenu de la page N° 5
Table of Contents Chapter 1 Introduction ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1 Introduction ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1 Features ........................................................................... 1 Chapter 2 Installation and Start Up ... ... ... ... ... ... ... ... ... ... ... ... . 2 W hat’s in the package ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .
Résumé du contenu de la page N° 6
Figure 17 - Magnetic Reed Switch Activation ... ... ... ... ... ... ... ... ... ... ... ... ... 25 Calibration Procedure for UNI-TRAN Premium Plus ST1400 O sensor . . . . . . . . . . . . . . . . . . 26 2 Relay Settings ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 26 Review Settings ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 27 Start Delay ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
Résumé du contenu de la page N° 7
Chapter 1 Introduction Introduction The Uni-Tran micro-controller based toxic gas detector provides fast, accurate, continuous and cost effective monitoring of toxic gases in harsh industrial environments. Net Safety selects the very best electrochemical sensors from the world's leading manufacturers for use in its broad line of toxic gas detectors. High performance, proprietary circuits and micro-controller based firmware ensure accurate and repeatable response in the most severe environments
Résumé du contenu de la page N° 8
Chapter 2 Installation and Start Up What’s in the package Carefully remove all the components from the packing box(s). Check components against the packing list. Inspect all components for obvious damage and broken/loose parts. Notify the carrier and distributor immediately if damage is found or parts are missing. Location of Sensor(s) There are no absolute rules for determining the quantity and location of gas detection instruments within a particular facility. Care should be taken to locate
Résumé du contenu de la page N° 9
Figure 1 Toxic Detector Layout Mounting The housing should be oriented so that the sensor is on the underside of the housing. Water will damage electronic devices. Seal conduit near housing entries to prevent water damage in the enclosure (refer to figure 2, 3, 4 and 5). 3
Résumé du contenu de la page N° 10
Dimensional Drawings Figure 2 Uni-Tran Premium plus dimensional drawing for the ST1200 ST1300 ST1400 ST1500 ST1600 toxic sensors. 4
Résumé du contenu de la page N° 11
Figure 3 Uni-Tran Premium dimensional drawing for the ST1200 ST1300 ST1400 ST1600 toxic sensors using sensor separation. 5
Résumé du contenu de la page N° 12
Figure 4 Uni-Tran Premium plus dimensional drawing for the ST1210 toxic sensor. 6
Résumé du contenu de la page N° 13
Figure 5 Uni-Tran Premium plus dimensional drawing for the ST1210 toxic sensor using sensor separation. 7
Résumé du contenu de la page N° 14
Wiring (refer to figure 7, 8, 9, 10, 11 and 12) NOTE: The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Confirm that all wiring complies with applicable regulations that relate to the installation of electrical equipment in a hazardous area. If in doubt, consult a qualified official before wiring th
Résumé du contenu de la page N° 15
non-hazardous area. Conform to local wiring codes. When pouring a seal, use a fibre dam to assure proper formation of the seal. Seals should never be poured at temperatures below freezing. The jacket and shielding of the cable should be stripped back to permit the seal to form around the individual wires. This will prevent air, gas and water leakage through the inside of the shield and into the enclosure. It is recommended that explosion-proof drains and conduit breathers be used. In some appl
Résumé du contenu de la page N° 16
The ST1210 sensors can be installed and wired directly to the UNI-TRAN Premium Plus housing and terminal board as per the wiring diagram (see Figure 10 ) or they may be remotely mounted using a sensor separation kit (JB2-3-ASSY) which is composed of a junction box and terminal strip (see Figure 11). The sensor and kit are then connected to the UNI-TRAN Premium Plus. When sensor separation is required for units using the ST1210 Hydrogen Sulfide sensor use a minimum of 18AWG shielded copper ins
Résumé du contenu de la page N° 17
Wiring Diagrams Figure 7 Uni-Tran Premium Plus wiring drawing for the ST1400 toxic sensor 11
Résumé du contenu de la page N° 18
Figure 8 Uni-Tran Premium Plus wiring drawing for the St1400 toxic sensor using sensor separation 12
Résumé du contenu de la page N° 19
Figure 9 Uni-Tran Premium Plus wiring diagram for the ST1200, ST1300, ST1500 and ST1600 Toxic Sensors 13
Résumé du contenu de la page N° 20
Figure 10 Uni-Tran Premium Plus wiring drawing for the ST1200, ST1300 , ST1500 and ST1600 toxic sensor using sensor separation 14