Résumé du contenu de la page N° 1 
                    
                         
        
FILE NO : A09-01P
 
 
 
Quick reference
 
 
 
 
 
 
 
 
AIR TO WATER HEAT PUMP 
 
 
 
 
 
 
 
 
 
 
  
 
 
 
 
 
 
 
                                                                                                                                                                                                                                                                                                                                                                                    
                    
                    Résumé du contenu de la page N° 2 
                    
                        Quick Reference Guide  -  Page 2  Estia System                    Domestic Hot Water Space Conditioning            Radiator                Fan coil unit    (Heating or Cooling)        Outdoor unit    Under floor heating  Hot water    Hydro unit  (Zone Control)  cylinder        Estia Outdoor Unit  HWS-802H-E  8.0kW Inverter (use Hydro Unit: HWS-802XWH**-E)  HWS-1102H-E 11.2kW Inverter (use Hydro Unit: HWS-1402XWH**-E)  HWS-1402H-E 14.0kW Inverter (use Hydro Unit: HWS-1402XWH**-E)    Estia Hydro U
                    
                    Résumé du contenu de la page N° 3 
                    
                        Quick Reference Guide  -  Page 3  Notes on System Design    • The input water temperature to the Hydro Unit must be 55°C or less.  Especially, be careful when there is an external heating source such as a boiler.  When hot water over 55°C returns, it may result in a failure of the unit or water leakage.  • The flow rate of the circulating water must meet the following range:-  11 and 14 kW  17.5 L/minute or more  8 kW    13 L/minute or more  If the flow rate becomes less than the minimum, the pr
                    
                    Résumé du contenu de la page N° 4 
                    
                        Quick Reference Guide  -  Page 4  Installation Examples  Space Cooling and Space Heating with Domestic Hot Water  When both cooling and heating are used, install a 2-way valve (for cooling) to the pipe to the room  for heating only.                                                                                                                                                                                                                                                                            
                    
                    Résumé du contenu de la page N° 5 
                    
                        Quick Reference Guide  -  Page 5  Installation Examples (cont.)  2-Zone Space Heating with Domestic Hot Water  The following shows an example of the 2-zone temperature control.  A buffer tank and a water pump are required for the 2-zone temperature control. This example is  Heating only, if the Fan Coils are to be used for Cooling then a 2-Way valve must be fitted.                                                                                                                                     
                    
                    Résumé du contenu de la page N° 6 
                    
                        Quick Reference Guide  -  Page 6  Hydro Unit – Exploded View        1 : Expansion vessel  2 : Hi pressure switch (4.15 MPa)  3 : Temperature sensor (for Heat pump outlet -TWO)  4 : Pressure sensor  5 : Heat exchanger  6 : Flow switch (13.0 L/min 17.5 L/min)  7 : Temperature sensor (for refrigerant -TC)  8 : Temperature sensor (for water inlet -TWI)  9 : Drain nipple  10 : Water inlet connection  11 : Refrigerant liquid connection  12 : Air relief valve  13 : Pressure relief valve (0.3 MPa (3 bar
                    
                    Résumé du contenu de la page N° 7 
                    
                        Quick Reference Guide  -  Page 7  Refrigerant Piping  Refrigerant Pipe Lengths and Height  The length and height of the refrigeration pipe must be within the following values.    Minimum Pipe Length  HWS-802H-E :  5 m  HWS-1102H-E :  3 m  HWS-1402H-E :  3 m    Maximum Pipe Length and Height  H: Max. ±30 m (above or below)  L: Max. 30 m    Note  The maximum pipe length cannot be increased using additional  refrigerant.          Refrigeration and Water Cycle Diagrams  Hydro Unit    Pressure   reli
                    
                    Résumé du contenu de la page N° 8 
                    
                        Quick Reference Guide  -  Page 8  Outdoor Unit    HWS-802H-E        HWS-1102H-E, 1402H-E                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    Résumé du contenu de la page N° 9 
                    
                        Quick Reference Guide  -  Page 9  Water Piping  • Install water pipes according to the regulations of respective countries.  • Install water pipes in a freeze-free place.  • Make sure that water pipes have sufficient pressure resistance (The setting value of the pressure  relief valve is 0.3 MPa).  • Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.    Water Connections  • Install a strainer with 30 to 40 meshes (procure locally) at  the water inlet 
                    
                    Résumé du contenu de la page N° 10 
                    
                        Quick Reference Guide  -  Page 10  Checking water volume and initial pressure of expansion vessel  The expansion vessel of the Hydro Unit has a capacity of 12 litres.  The initial pressure of the expansion vessel is 0.1 MPa (1 bar).  The suggested initial water charge is 0.2MPa (2 bar).  The pressure of the safety valve is 0.3 MPa (3 bar).  Verify whether the capacity of the expansion vessel is sufficient using the following expression. If  the volume is insufficient, install an appropriate exte
                    
                    Résumé du contenu de la page N° 11 
                    
                        Quick Reference Guide  -  Page 11  Pump operation / configuration  Change Pump speed, so that water flow is always greater than the minimum flow rate. If water flow  is lower than the minimum rate during operation, the unit detects error.      Water charging  Charge water until the pressure gauge shows 0.2 MPa (2 bar).  Hydraulic pressure may drop when the trial run begins. In that case, add water.    Air may enter if the charged hydraulic pressure is low.  Loosen the purge valve cap by two turn
                    
                    Résumé du contenu de la page N° 12 
                    
                        Quick Reference Guide  -  Page 12  Electrical Connections    E Box layout    Terminal Block Connections                                                                                                                                                                                                                                                                                                                                                                                                             
                    
                    Résumé du contenu de la page N° 13 
                    
                        Quick Reference Guide  -  Page 13  Power Lines Schematic    Control Lines Schematic                                                                                                                                                                                                                                                                                                                                                                                                                                 
                    
                    Résumé du contenu de la page N° 14 
                    
                        Quick Reference Guide  -  Page 14  Electrical supply / cable specifications  Wiring specifications (power line)  POWER Maximum Installation Connection  Description Cable size  SUPPLY current fuse rating destination  14 kW 230 V ~ 50 Hz 22.8 A 25 A 2.5 mm² or more  L N Outdoor unit power  ,   11 kW 230 V ~ 50 Hz 22.8 A 25 A 2.5 mm² or more  8 kW 230 V ~ 50 Hz 20.8 A 25 A 2.5 mm² or more  1 2 3 Outdoor-Hydro –   – 1.5 mm² or more  ,  ,   L N 3 kW 230 V ~ 50 Hz 13 A 16 A 1.5 mm² or more  ,   (TB02)
                    
                    Résumé du contenu de la page N° 15 
                    
                        Quick Reference Guide  -  Page 15  Input line specifications  Description  Input  Maximum length   Emergency stop control  Non-voltage  12 m   Cylinder thermostat input  Non-voltage  12 m   Cooling thermostat input  Non-voltage  12 m   Heating thermostat input  Non-voltage  12 m     CAUTION  Earthing arrangements  The Hydro Unit and related equipment must be earthed in accordance with your local and national  electrical regulations.  It is essential that the equipment is earthed to prevent the e
                    
                    Résumé du contenu de la page N° 16 
                    
                        Quick Reference Guide  -  Page 16  Electrical connection for external booster heater    CAUTION   The maximum current available from the booster heater output is 1 A. Do not connect the  booster heater directly to Terminal Block 05 on the Hydro Unit. The AC230 V 1 A output  from the Hydro Unit must only be used to energize an external contactor (Supplied locally).    • The booster heater can be installed only for room heating and cannot be used for hot water  supply.  • Install the booster heate
                    
                    Résumé du contenu de la page N° 17 
                    
                        Quick Reference Guide  -  Page 17  2-way valve (for cooling) connection  Required Valve Specification:  Electrical Specification: 230 V; 50 Hz; <100 mA  Return Mechanism: 2-wire spring return.   • The Hydro Unit has the facility to connect a 2-way valve to  isolate Space Conditioning Units that do not perform cooling,  when Cooling Mode is selected.  • Connect the 2-way valve in accordance with the diagram  (opposite):-    3-way valve (diverter) connection  Required Valve Specification:  Electri
                    
                    Résumé du contenu de la page N° 18 
                    
                        Quick Reference Guide  -  Page 18  3-way mixing valve connection  Required Actuator Specification  Electrical Specification:230 V; 50 Hz; <100 mA  The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating  system.  • Connect the 3-way mixing valve in accordance with the diagrams below:-        Hot water cylinder connection (optional)  • Please refer to “Electrical supply/cable specifications” for fuse/cable size and for  connection details.  Electrical Con
                    
                    Résumé du contenu de la page N° 19 
                    
                        Quick Reference Guide  -  Page 19  Setting DIP Switches on the Board  in the Hydro Unit   • Detach the front cover and the electric parts box cover of  the Hydro Unit.   • Set the DIP switches on the main board.                       Switch mode    SW10  Description   Default setting  Alternate  Internal pump P1 operating  1  Continuous operation  OFF ON  HP synchronized   mode   Interlocked with the  3  External P2 pump operation  Continuous operation  OFF ON  internal pump  synchronized with P
                    
                    Résumé du contenu de la page N° 20 
                    
                        Quick Reference Guide  -  Page 20  Hydro Unit Remote Control     Buttons and Functions           1. TEMP. button: 10. NIGHT button:  Changes the set temperature for  Controls the night set back  each operation mode (ZONE1/2 hot  operation.  water) by 1°C step.  2. SCHEDULE 11. AUTO TEMP.  Switches setting temperature  button: button:  automatically according to outside  Sets the current time and  temperature. (Pressing this button  scheduled weekly operation.  long changes the mode to data  sett