TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL
TECHNICAL MANU TECHNICAL MANUAL AL
GPC15 SEER Multi-Position
Package Air Conditioners
with R-410A
• Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.
• All safety information must be followed as provided in the Service Manual.
• Refer to the appropriate Parts Catalog for part number information.
• Models listed on page 3.
• Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficie
ページ2に含まれる内容の要旨
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GP C 15 24 M 4 1 * * BRAND: MINOR ® G: Goodman REVISION: Brand or Distinctions CONFIGURATION H: Horizontal PRODUCT M: Multi Position MAJOR SERIES: 15: 15 SEER REVISION: Rating PRODUCT TYPE: REFRIGERANT: Package 2: R-22 Cooling/Heating 4: R-410A
ページ3に含まれる内容の要旨
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GPC1524M41A* GPC1530M41A* GPC1536M41A* GPC1542M41A* GPC1548M41A* Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency** **Note that these tax credits are subject to specific requirements set forth in the American Recovery and Reinvestment Act of 2009 and in the Int
ページ4に含まれる内容の要旨
PRODUCT DESIGN GPC Package Cooling Units are designed for outdoor instal- are a number of design characteristics which are different lations only in either residential or light commercial applica- from the traditional reciprocating compressor. tions and are available in 2, 2-1/2, 3, 3-1/2 and 4 ton sizes. - Due to their design Scroll Compressors are inherently They are designed for 208/230 volt single phase applications. more tolerant of liquid refrigerant. NOTE: Even though the The connecting d
ページ5に含まれる内容の要旨
PRODUCT DESIGN WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING IF A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING. IMPORTANT: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Refer to Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with Roof Curb t
ページ6に含まれる内容の要旨
PRODUCT DESIGN GPC15[24-48]M41* HKR ELECTRICAL DATA Circuit #1 Circuit #2 Maximum Maximum Actual Minimum Circuit Minimum Circuit Model and Heat Kit Usage kW & BTU Overcurrent Overcurrent Ampacity Ampacity at 240V Protection (amps) Protection (amps) at 208 / 240V at 208 / 240V at 208 / 240V at 208 / 240V GPC1524M41* HKR05A,CA 24 / 27 30 / 30 ---- ---- 4.75 / 16,200 HKR08A,CA 33 / 28 40 / 40 ---- ---- 7.00 / 23,800 HKR10A,CA 45 / 51 60 / 60 ---- ---- 9.50 / 32,400 GPC1530M41* HKR05A,CA 24 / 27 3
ページ7に含まれる内容の要旨
PRODUCT DIMENSIONS GPC15[24-48]M41* 47 51 POWER WIRE ? A ENTRANCE 16 4 1/8 2 1/8 1 3/8 5 ½ 16 6 ½ B 8 2 34 SUPPLY ? B SUCTION/LIQUID PRESSURE PORT RETURN 3 CONDENSATE DRAIN CONTROL 18 7/8 CONNECTION WIRE 3/4” NPT FEMALE ENTRANCE BLOWER ACCESS PANEL MEDIUM CHASSIS GPC1524M41* GPC1530M41* GPC1536M41* LARGE CHASSIS GPC1542M41* GPC1548M41* 7
ページ8に含まれる内容の要旨
GPC15[24-48]M41A* PACKAGE COOLING SPECIFICATIONS GPC1524M41* GPC1530M41* GPC1536M41* GPC1542M41* GPC1548M41* COOLING COOLING CAPACITY, BTUH 24,000 28,000 35,000 40,000 45,500 CAPACITY SEER / EER 14.5 / 12. 0 14.5 / 12. 0 14.5 / 12. 0 14.5 / 12. 0 15.0 / 12.0 UNIT VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 ELECTRICAL AMPS 15.8 17.5 20.1 22.2 24.2 SPECIFICATION MIN CIRCUIT AMPACITY 19.0 21.0 24.2 26.7 29.2 MAX OVERCURRENT PROTECTION 30 35 40 40 45 COMPRE
ページ9に含まれる内容の要旨
ACCESSORIES ACCESSORIES - GPC/GPH****M MODELS Part Number Description OT18-60A Outdoor Thermostat Kit w/Lockout Stat OT/EHR18-60 Emergency Heat Relay Kit HKR Electric Heat Kit PGC101/102/103 Roof Curb PEHH101/102 Horizontal Economizer For Heat Pump, Small and Medium Chassis PEHH103 Horizontal Economizer For Heat Pump, Large Chassis PEHC101/102 Horizontal Economizer For A/C, Small and Medium Chassis PEHC103 Horizontal Economizer For A/C, Large Chassis PGMDD101/102 Manual 25% Fresh Air Dampe
ページ10に含まれる内容の要旨
BLOWER PERFORMANCE DATA GPC15[24-48]M41A* Dry Coil Data E.S.P (In. of H O) 2 Model Speed Volts 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 CFM 882 808 727 649 545 --- --- --- T1 (G) 230 WATTS 82 86 92 102 108 --- --- --- CFM 933 873 810 733 637 584 --- --- T2 / T3 230 WATTS 93 103 109 120 126 135 --- --- CFM 1058 1012 945 896 816 723 672 --- T4 / T5 230 WATTS 124 136 142 153 168 172 179 --- CFM 893 824 752 665 575 --- --- --- T1 (G) 230 WATTS 87 95 101 111 115 --- --- --- CFM 1132 1070 1011 959 889 827 733
ページ11に含まれる内容の要旨
BLOWER PERFORMANCE DATA 11 BTU OUTPUT vs TEMPERATURE RISE CHART 100 600 CFM 90 700 80 800 900 1000 70 1100 1200 60 1400 1600 50 1800 2000 2200 40 2400 CFM 30 FORMULAS BTU OUTPUT = CFM x 1.08 x RISE BTU OUTPUT 20 RISE = ÷ CFM 1.08 10 100 30 40 50 60 70 80 90 110 120 130 140 150 OUTPUT BTU/HR x 1000 TEMPERATURE RISE
ページ12に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1524M41* 12 MODEL: GPC1524M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 24.3 25.1 27.5 - 23.7 24.6 26.9 - 23.1 24.0 26.3 - 22.6 23.4 25.6 - 21.4
ページ13に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1524M41* 13 MODEL: GPC1524M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 25.1 25.6 27.4 29.3 24.5 25.1 26.8 28.6 23.9 24.5 26.1 27.9 23.3 23.9 25.
ページ14に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1530M41* 14 MODEL: GPC1530M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 27.9 28.9 31.7 - 27.3 28.3 31.0 - 26.6 27.6 30.2 - 26.0 26.9 29.5 - 24.7
ページ15に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1530M41* 15 MODEL: GPC1530M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 596367 71 59 636771596367 7159 63 67 71 5963 67 7159 636771 MBh 28.929.531.533.728.2 28.830.832.9 27.5 28.1 30.1 32.126.9 27.5 29.3 3
ページ16に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1536M41* 16 MODEL: GPC1536M41 COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 35.6 36.9 40.4 - 34.8 36.0 39.5 - 33.9 35.2 38.5 - 33.1 34.3 37.6 - 31.5
ページ17に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1536M41* 17 MODEL: GPC1536M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 36.8 37.6 40.2 43.0 36.0 36.8 39.3 42.0 35.1 35.9 38.4 41.0 34.3 35.0 37.
ページ18に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1542M41* 18 MODEL: GPC1542M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63 6771596367 7159 63 67 71 596367 7159 636771 MBh 41.2 42.7 46.8 - 40.2 41.7 45.7 - 39.3 40.7 44.6 - 38.3 39.7 43.5 - 36.
ページ19に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1542M41* 19 MODEL: GPC1542M41 EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 42.643.646.649.841.7 42.645.548.640.7 41.5 44.4 47.539.7 40.5 43.3 46.3 3
ページ20に含まれる内容の要旨
COOLING PERFORMANCE DATA GPC1548M41* 20 MODEL: GPC1548M41 COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 7 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5°F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 636771596367 7159 63 67 71 5963677159 636771 MBh 43.9 45.5 49.9 - 42.9 44.5 48.7 - 41.9 43.4 47.6 - 40.9 42.3 46.4 - 38.8