ページ1に含まれる内容の要旨
XLS-278 and XLS-270
Manual Pull Stations
S Y S T E M
SPECIFICATION DATA
FEATURES
• Single stage double action XLS-278 features a rugged
Lexan housing
• XLS-270 models have traditional familiar appearance
• XLS-270 models are available for one stage (GA),
two stage (pre-signal), and double action
• Break glass operation on XLS-270 models
• Intelligent device with integral microprocessor
• Non-volatile memory
• Automatic device mapping
• Electronic addressing
ページ2に含まれる内容の要旨
XLS-270 AND XLS-278 MANUAL PULL STATIONS - Number of recorded troubles, alarms, and time and Installation: date of last alarm. - Up to 24 possible trouble codes which can be used to The Signature Series fire alarm manual pull stations mount to specifically diagnose faults. North American 2-1/2in (64 mm) deep 1-gang boxes and 1- 1/2in (38 mm) deep 4insquare boxes with 1-gang covers. The 2 Automatic Device Mapping: terminals are suited for #14 to #18 AWG (1.5 mm to 0.75 2 mm ) wire size. The loop
ページ3に含まれる内容の要旨
XLS-270 AND XLS-278 MANUAL PULL STATIONS SPECIFICATIONS Models: XLS-270: One stage fire alarm station; English markings XLS-270P: Two stage (pre-signal) fire alarm station; English markings XLS-278: Double action, one stage fire alarm station; English markings Addressing Requirements: XLS-270/270F/270B: 1 module address XLS-270P/270PB: 2 module addresses XLS-278: 1 module address Operating Current: XLS-270/270F/270B: Standby: 250μA Activated: 400μA XLS-270P/270PB: Standby: 396μA Activated: 680μA
ページ4に含まれる内容の要旨
XLS-270 AND XLS-278 MANUAL PULL STATIONS Comfort from Experience Home and Building Control Home & Building Control European Centre of Excellence Honeywell Inc. Honeywell GmbH Fire Solutions Honeywell Plaza Honeywellstrasse Lovelace Road, Southern Industrial Area P.O. Box 524 63477 Maintal 1 Bracknell, Berkshire, RG12 8WD Minneapolis MN 55408-0524 Germany United Kingdom EN0C-0741 0599R2-MA 4