DVPDNET-SL 
DeviceNet Network Scanner 
Operation Manual 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                              
                                                                               DVP-0204520-03             
 
2012-3-27          
                                                                                                                                                                 
                    
                    Summary of the content on the page No. 2 
                    
                        DeviceNet Network Scanner DVPDNET-SL  Warning     Please read this instruction carefully before use and follow this instruction to operate the device in order to  prevent damages on the device or injuries to staff.    Switch off the power before wiring.   DVPDNET-SL is an OPEN TYPE device. Therefore it should be installed in an enclosure free of airborne  dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from  operating the device (e.g. key or speci
                    
                    Summary of the content on the page No. 3 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4 CONFIGURATION OF DVPDNET-SL.................................................................................................... 8 4.1  Configuration through DeviceNet Builder Software ...........................................................................8  4.1.1  Selection of Communication Channel......................................................................................... 8  4.1.2  Setup of Scan Module ....................................
                    
                    Summary of the content on the page No. 4 
                    
                        DeviceNet Network Scanner DVPDNET-SL  1 Introduction  1) Thank you for choosing Delta DVPDNET-SL. To ensure correct installation and operation of DVPDNET-SL,  please read this chapter carefully before using your DVPDNET-SL.   2) DVPDNET-SL running on the left side of PLC can serve as the DeviceNet master or slave with PLC MPU  together. It can be configured through DeviceNet software.  1.1 Features   Serves as DeviceNet master by connecting to PLC MPU and Supports standard DeviceNet protocol.   
                    
                    Summary of the content on the page No. 5 
                    
                        DeviceNet Network Scanner DVPDNET-SL  1.3 Specifications   PLC that DVPDNET-SL supports  Item Specification  DVPDNET-SL supports PLC MPU which can be extendable in its left side  PLC Model  g. DVP-SV, DVP-EH2_L, DVP-SX2, DVP-SA2, DVP10MC11T etc. )   DeviceNet Interface  Item Specification  Transmission  CAN  method  Electrical  500V DC  isolation  Interface Removable connector (5.08mm)  Transmission TAP-CB01 cable and TAP-CB02 cable are recommended. (The shielded wire  cable must be grounded and
                    
                    Summary of the content on the page No. 6 
                    
                        9 9 8 8 7 7 6 6 DeviceNet Network Scanner DVPDNET-SL  2 Product Profile & Outline  2.1 Dimension  DVPDNET MS NS 5 1 x10 5 0 x10 DR 1 DR 0 IN 1 IN 0   2.2 Product Profiles    1. Model name  2. Extension port  3. Power, MS, NS LED  4. DIN rail clip  5. Digital indicator  6. Extension clip  7. Address switch  8. Function switch  9. DeviceNet connection port        2.3 DeviceNet Connection Port  The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with  DVPDNET-
                    
                    Summary of the content on the page No. 7 
                    
                        9 9 8 8 7 7 6 6 DeviceNet Network Scanner DVPDNET-SL  2.4 Address Switch  The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99  are forbidden).  Switch setting Content 5 5 0 … 63 Valid DeviceNet node address  64…99 Invalid DeviceNet node address    Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding  1 0 switch of x10 to 2 and the corresponding switch of x10 to 6.  Note:   Please set up the node addres
                    
                    Summary of the content on the page No. 8 
                    
                        DeviceNet Network Scanner DVPDNET-SL  2.6 Digital Indicator  The digital indicator provides the following two functions:    DVPDNET POWER MS NS     1) Displaying the node address and error messages of DVPDNET-SL .  2) Displaying the error message of slave.  Note:    When the module works normally, the digital displayer will show its own node ID.    When "E1" and "03" are on display continuously, it indicates that the error that "E1" refers to  occurs in the slave of node 03.     When the error c
                    
                    Summary of the content on the page No. 9 
                    
                        DeviceNet Network Scanner DVPDNET-SL  3 Installation  3.1 Connecting DVPDNET-SL to DVP-SV MPU   Adjust the extension clip on the left side of DVP-SV.   Meet the extension port of the MPU with DVPDNET-SL as shown in the figure below.   Fasten the extension clip.  DVPDNET DVP28SV RUN STOP   3.2 Installing DVPDNET-SL and DVP-SV MPU on DIN Rail   Use 35mm DIN rail.   Open the DIN rail clip on DVP-SV and DVPDNET-SL. Insert DVP-SV and DVPDNET-SL onto the DIN  rail.   Clip up the DIN rail clips on DVP-
                    
                    Summary of the content on the page No. 10 
                    
                        DeviceNet Network Scanner DVPDNET-SL  3.3 Connecting to DeviceNet Connection Port   The colors on the PINs on the DeviceNet connection port match the colors of the connection cables.  Make sure you connect the cable to the right PIN.   We recommend you also apply Delta’s power module in the connection.    DVP-PLC Operation Manual 7                                                                                                                                                                       
                    
                    Summary of the content on the page No. 11 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4 Configuration of DVPDNET-SL  4.1 Configuration through DeviceNet Builder Software  Before DVPDNET-SL starts to work normally, it must be configured through DeviceNet Builder  software.  4.1.1 Selection of Communication Channel  Max 8 DVPDNET-SL modules can be connected to the left side of PLC and every DVPDNET-SL is a  communication channel. When there are three DVPDNET-SL modules connected to PLC’s left side and  DeviceNet Builder software is on line, the
                    
                    Summary of the content on the page No. 12 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4.1.2 Setup of Scan Module  The following dialog is for setting DVPDNET-SL’s current mode: master mode or slave mode.      Parameter Explanation  Master  For setting DVPDNET-SL as master mode.  mode  Scan  The cycle time for master to send and receive the real time data after real-time  interval  data connection is successful.  time  The result value of the parameter multiplied by 4. (Unit:ms)  Timeouts   Master assumes that the slave is offline if it receiv
                    
                    Summary of the content on the page No. 13 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4.1.3 Setup of Scan List   Double click the existing icon of DVPDNET-SL in the DeviceNet Builder interface and then the following  dialog box appears for configuring the scan module.      Parameter Explanation  All already scanned slaves appear in “Available list”.  Available  After the configuration information is downloaded to DVPDNET-SL, the slave in  node  “Available node” will not conduct the real-time data exchange with DVPDNET-SL. After the configurat
                    
                    Summary of the content on the page No. 14 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4.1.4 Input Table and Output Table  Select the device in “Scan list” and then the data length of input and output of the device will be displayed  respectively in the lower part of the following dialog box.      Parameter Explanation  PLC MPU’s registers and the corresponding output data are shown in “Output list”.  Output  The values in PLC’s registers will be sent to slave in real time as the control data  Table  of slave.  PLC MPU’s registers and the corr
                    
                    Summary of the content on the page No. 15 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4.2 Data Mapping Areas   The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The  mapping relation is unchanged and user has no right to revise this area.  Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected  to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL.  DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVP28SV RUN STOP   Th
                    
                    Summary of the content on the page No. 16 
                    
                        DeviceNet Network Scanner DVPDNET-SL  Note: If the unit No. is 2, the number of the registers above will all be added by 500 respectively; if the unit No.  is 3, the number of the registers above will all be added by 1000 respectively; if the unit No. is 4, the number of  the registers above will all be added by 1500 respectively and so on.  4.4 I/O Mapping Table (as slave mode)   As DVPDNET-SL serves as slave mode, the data mapping areas are distributed as below table and these  registers are a
                    
                    Summary of the content on the page No. 17 
                    
                        DeviceNet Network Scanner DVPDNET-SL  5 Sending Explicit Message from Ladder Diagram  DVPDNET-SL supports the sending of explicit messages through WPL programs.  5.1 The Principle of Explicit Message Sending  1 Explicit request message (PLC   DVPDNET-SL) 4 Explicit response message (DVPDNET-SL   PLC)  DVPDNET DVP28SV RUN STOP Explicit request message from master 2 DeviceNet DNA02 RJ12 VFD-B Explicit response message from slave 3    ①: DVP-SV MPU sends out explicit request message to DVPDNET-SL a
                    
                    Summary of the content on the page No. 18 
                    
                        DeviceNet Network Scanner DVPDNET-SL  5.2 Structure of Explicit Message  You can edit explicit messages in “explicit request message editing area” and “explicit response message  editing area”. See the table below for the corresponding relation between the two areas and PLC devices. If  you transmit the request message to be sent out to D6250 ~ D6281, DVPDNET-SL will fill the response  message to D6000 ~ D6031.  PLC device Mapping area Mapping length  D6000 ~ D6031 Explicit response message edit
                    
                    Summary of the content on the page No. 19 
                    
                        DeviceNet Network Scanner DVPDNET-SL  2) Structure of response message  See the table below:  Response Message  PLC device   15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 D6000 ReqID Status  D6001 Message Header Port Size  D6002 Service Code MAC ID  D6003 ~ 6031 Message Data Service Response Data   The definitions of ReqID, Port, Service Code and MAC ID are the same as their definitions in request  message.   Size: The length of the message, starting from D6003. Max. 58 bytes. Errors will occur when the
                    
                    Summary of the content on the page No. 20 
                    
                        DeviceNet Network Scanner DVPDNET-SL  4) Application example (I)  Target When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502  1> The connection    DVPDNET DVP28SV RUN STOP Node Address:00 DeviceNet   Node Address:02 RJ12   Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network.  2> Compulsory settings and explanations on devices   Compulsory settings in DVPDNET-SL  Parameter Set value Explanation  Node address 00 Set the node address of DVPDN