System Sensor PDRP-1002 Series user manual

User manual for the device System Sensor PDRP-1002 Series

Device: System Sensor PDRP-1002 Series
Category: Home Security System
Manufacturer: System Sensor
Size: 1.93 MB
Added : 7/9/2014
Number of pages: 60
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for System Sensor PDRP-1002 Series. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with System Sensor PDRP-1002 Series.

For your convenience

If looking through the System Sensor PDRP-1002 Series user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual System Sensor PDRP-1002 Series on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual System Sensor PDRP-1002 Series to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
System Sensor PDRP-1002 Series User manual - Online PDF
Advertisement
« Page 1 of 60 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual System Sensor PDRP-1002 Series but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to System Sensor PDRP-1002 Series. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1


3825 Ohio Avenue
St. Charles, IL 60174
1-800-SENSOR2
Fax: (630) 377-6495
PDRP-1002
Series
Agent Release Control
System
Instruction Manual
Document 51135
I56-1358-01
B
04/06/2001 Rev:
PN 51135:B0 ECN 00-543

Summary of the content on the page No. 2

While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede- ing devices, and a fire alarm control with remote notification termined rate or reaches a predetermined level. Rate-of-rise capability–c

Summary of the content on the page No. 3

Adherence to the following will aid in problem-free Installation Precautions installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to light- of power before servicing. Control unit and associated equip- ning-induced transients. Although no system is completely ment may be damaged

Summary of the content on the page No. 4

NFPA Standards NFPA Standards This control panel complies with the following NFPA standards: • NFPA 2001 - Clean Agent Fire Extinguishing Systems  NFPA 17 - Dry Chemical Extinguishing Systems  NFPA 17A - Wet Chemical Extinguishing Systems •NFPA 12 - CO2 Extinguishing Systems (High Pressure Only)  NFPA 12A - Halon 1301 Extinguishing Systems NFPA 12B - Halon 1211 Extinguishing Systems  NFPA 72 - Central Station Signaling Systems (Automatic, Manual, and Waterflow) - Protected Premises Unit R

Summary of the content on the page No. 5

Table of Contents Table of Contents NFPA Standards.......................................................................................................... 4 NFPA Standards .................................................................................................... 4 Underwriters Laboratories Documents ................................................................. 4 Other..................................................................................................................

Summary of the content on the page No. 6

Table of Contents Zone Relay Module - 4XZM ........................................................................ 26 LED Interface Module - 4XLM .................................................................... 27 Setting Mode of Operation ....................................................................................... 28 DIP Switch Functions........................................................................................... 28 Switch #1 - Cross Zone...........................

Summary of the content on the page No. 7

1. Product Description Overview The PDRP-1002 Agent Release Control System has been designed as a control center for use in automatic fire supression systems. The panel is a feature-packed control unit suitable to perform detection and control functions associated with the release of gaseous agent/special hazard fire protection systems. The PDRP- 1002 is designed for maximum reliability with 100% solid state circuitry and isolated relay contacts for outside interfacing and features programmab

Summary of the content on the page No. 8

1. Product Description Circuits Circuits Input Circuits Detector Zone 1 (Style B/D) Detector Zone 2 (Style B/D) Abort (Style B/D) Manual Release (Style B/D) Note: Optional auxiliary relay module 4XZM tracks these four circuits. Output circuits Notification Appliance Circuit 1 (Style Y/Z) Notification Appliance Circuit 2 (Style Y/Z) Releasing Circuit 1 (Style Y) Releasing Circuit 2 (Style Y) / Supervisory Input (StyleB) Front Panel Control Switches Switch 1 - Tone Silence Switch 2 - Alarm Silenc

Summary of the content on the page No. 9

Control Panel 1. Product Description Control Panel Notification Appliance Circuits Relays Style Z (Class A) / Style Y (Class B) Alarm Contacts Trouble Contacts Releasing Circuits Style Y (Class B) 24VDC #1 - Initiating Device Circuit Regulated Nonresettable #2 - Initiating Device Circuit Regulated Resettable #3 - Abort Switch RMS-Regulated #4 - Manual Release Style D (Class A) / Style B (Class B) OUT#1 OUT#2 OUT#3 OUT#4 IN #1 IN #2 IN #3 IN #4 B+ A+ A– B– B+ A+ A– B– B+ B– B+ B– B+ A

Summary of the content on the page No. 10

1. Product Description DIP Switch Functions DIP Switch Functions The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode of Operation" on page 28. #1 Cross Zone Determines how NACs and Releasing Circuits respond to an alarm. #2 Supervisory Selects Releasing Circuit #2 to function as a Supervisory Circuit. #3 & #4 Timer Selects Timer Delay setting. #5 & #6 Abort Selects a variety of abort functions. Note: See “Setting Mode of Operation” on page 28

Summary of the content on the page No. 11

Options 1. Product Description Remote Annunciator - RZA-4X The Remote Annunciator mounts on a standard single-gang box, and provides LED indication of the same functions as the zone relay module. For example, with DIP switch #1 ‘ON’ and DIP switch #2 ‘OFF’:  One zone in alarm (red) SYSTEM TR OU BLE  Two zones in alarm (red) RE-SOUND  Releasing Circuit 1 (red) TONE SILENCE  Releasing Circuit 2 (red)  System Trouble (yellow) FIRE ALARM ANNUNCIATO R A local trouble sounder and silence switc

Summary of the content on the page No. 12

1. Product Description Specifications Specifications AC Power PDRP-1002: 110/120 VAC, 50/60 Hz, 1.2 amps PDRP-1002E: 220/240 VAC, 50/60 Hz, 0.6 amps Wire size: minimum #14 AWG with 600V insulation Battery (lead acid only) Maximum Charging Circuit: 27.6V, 1.5 amps Maximum Battery Capacity: 18 AH. Note: Batteries larger than 12 AH require FireLite BB-17 or other UL-listed external battery cabinet. Initiating Device Circuits Power-limited circuitry Operation: Style B (Class B) or Style D (Clas

Summary of the content on the page No. 13

2. Installation Cabinet Mounting Carefully unpack the system and check for shipping damage. Select a suitable location in a clean, dry, vibration-free environment that is not subject to extreme temperatures. Locate the top of the cabinet approximately five feet above the floor with the hinge on the left. The panel must be easily accessible for maintenance; the hinged door requires a minimum clearance of 14 in. (35.56cm) to open. Removal of Circuit Board To prevent damage to the printed circui

Summary of the content on the page No. 14

2. Installation Cabinet Mounting The figure below shows the exterior dimensions and mounting hole locations for the cabinet backbox and dimensions of the optional trim ring: 5.375” 14.625” (13.65cm ) (37.15cm ) 16.125” 16.00” (40.96cm ) (40.64cm ) 4.75” (12.07cm ) 1.00” 14.50” (2.54cm ) (36.83cm ) 12.50” (31.75cm ) 1.00” (2.54cm ) 9.50” (24.13cm ) 1.5” (3.81cm) 16.125” (40.96cm) 14.625” (37.15cm) Figure 2 Cabinet Mounting Dimensions Reinstallation of Circuit Board Reinstall the printed circ

Summary of the content on the page No. 15

Installing Optional Voltmeter/Ammeter 2. Installation Installing Optional Voltmeter/Ammeter To monitor battery voltage and battery charging current, a 4XMM Meter Module is required. To install the power meter module follow the steps below: Step Action 1 Cut the jumper wire labeled “AMP”. 2 Secure the module to the backbox with the hardware provided. Refer to Product Installation Drawing (PID) for detailed instructions. 3 Connect meter cable P2 to connector J2 on the main circuit board. 4 Co

Summary of the content on the page No. 16

2. Installation Power Connections Power Connections WARNING: Do not apply any type power to this control panel until all connections have been ! made and verified. AC Connections Disconnect (open) the circuit breaker in the AC main breaker panel and tag it “Out of Service”. Note: Refer to "Power-Up Procedure" on page 31 before closing AC breaker. Primary power required for the PDRP-1002 control panel is 110/120 VAC, 50/60 Hz, 1.2 amps and for the PDRP-1002E is 220/240 VAC, 50/60 Hz, 0.6 amps.

Summary of the content on the page No. 17

Power-limited Wiring Requirements 2. Installation Observe polarity when connecting the batteries. Connect the battery cable (p/n 75203 or 75202, depending on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided. Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries. Do NOT connect battery interconnect wire at this time. TB5 J2 AMP J9 J3 Figure 5 Battery Installation and Connection Power-lim

Summary of the content on the page No. 18

2. Installation Initiating Device Circuits Initiating Device Circuits The control panel provides two Initiating Device Circuits (#1 and #2) and they may be configured as either Style D (Class A) or Style B (Class B). Circuit #3 is designated as an Abort Switch Circuit and Circuit #4 is a Manual Release Circuit. Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and Waterflow alarm devices. Note: Refer to "Appendix B: Compatible Devices" on page

Summary of the content on the page No. 19

Initiating Device Circuits 2. Installation Four-Wire Smoke Detector Connections A maximum of 200mA is available from the 24VDC Resettable Power circuit on TB1 (+24VR terminals). Any power that is drawn from the 24VDC Nonresettable Power on TB2 (+24VNR terminal) must be subtracted from available resettable power. See "Specifications" on page 12 and "Powering External Devices" on page 22. Note: Refer to "Appendix B: Compatible Devices" on page 41 for suitable 4-wire smoke detectors. Notes on S

Summary of the content on the page No. 20

2. Installation Output Circuits Output Circuits Notification Appliance Circuits The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits, which are supervised and power-limited. Each circuit is capable of 1.5 amps of current. Total current drawn from both NACs and both Releasing Circuits (see "Releasing Circuits" on page 21) cannot exceed 2.25 amps. Note: Refer to "Appendix B: Compatible Devices" on page 41 for suitable devices.  For DIP switch co


Alternative user manuals
# User manual Category Download
1 System Sensor S1224MC User manual Home Security System 3
2 System Sensor P2R User manual Home Security System 10
3 3Com 1000BASE-T-GBIC User manual Home Security System 0
4 Sony BRCSDP12 User manual Home Security System 3
5 3Com TECHD-0000000122 User manual Home Security System 1
6 Sony SSC-M354 User manual Home Security System 3
7 Sony DIGITAL 8 DCR-TRV130E User manual Home Security System 9
8 Sony SNC-RX SNC-CS50 User manual Home Security System 4
9 Sony SSC-M183/M183CE/M188CE SSC-M383/M383CE/M388CE User manual Home Security System 10
10 Sony CD-7226 User manual Home Security System 1
11 Sony Ssc-M383 User manual Home Security System 6
12 Sony Snc Df50n User manual Home Security System 1
13 Sony SNC-RX SNC-RZ50 User manual Home Security System 20
14 Sony BLUETOOTH MEX-BT2500 User manual Home Security System 10
15 4XEM IPCAMW40 User manual Home Security System 1