Slant/Fin VSPH-60 user manual

User manual for the device Slant/Fin VSPH-60

Device: Slant/Fin VSPH-60
Category: Boiler
Manufacturer: Slant/Fin
Size: 0.89 MB
Added : 3/24/2014
Number of pages: 28
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Slant/Fin VSPH-60. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Slant/Fin VSPH-60.

For your convenience

If looking through the Slant/Fin VSPH-60 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Slant/Fin VSPH-60 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Slant/Fin VSPH-60 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Slant/Fin VSPH-60 User manual - Online PDF
Advertisement
« Page 1 of 28 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Slant/Fin VSPH-60 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Slant/Fin VSPH-60. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

®

This manual must be left
with owner and should be
hung on or adjacent to
the boiler for reference.
VICTORY VSPH
DIRECT-VENT SEALED COMBUSTION BOILERS
HOT WATER MODELS VSPH-60 THROUGH VSPH-180
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
INSTALLATION AND OPERATING INSTRUCTIONS
TABLE OF CONTENTS
IMPORTANT
Dimensions, Rating and Orifice Sizes ........................................2
READ ALL OF THE FOLLOWING
Identification of Parts.............................................

Summary of the content on the page No. 2

2 VICTORY VSPH Models RATINGS AND DIMENSIONS NOTE: Height dimensions increase by 1 1 1 ⁄2" and depth increases to 28 ⁄2" when combustible floor kit is used. Figure 1. Dimensions data Input No. of Boiler Model Btuh Sections A B 1 3 VSPH-60 60,000 3 11 ⁄8"17 ⁄8" 1 3 VSPH-90 90,000 4 14 ⁄8"20 ⁄8" 1 3 VSPH-120 120,000 5 17 ⁄8" 23 ⁄8" 1 3 VSPH-150 150,000 6 20 ⁄8"26 ⁄8" 1 3 VSPH-180 180,000 7 23 ⁄8"29 ⁄8" Victory VSPH boiler Gas Orifice Size Orifice Sizes for High Altitudes Includes 4% Reduction for

Summary of the content on the page No. 3

VICTORY VSPH Models 3 LOCATION AND IDENTIFICATION OF PARTS Base Assembly Figure 2. Location and identification of parts

Summary of the content on the page No. 4

4 VICTORY VSPH Models MINIMUM CLEARANCES FROM COMBUSTIBLE INSTALLATION REQUIREMENTS CONSTRUCTIONS The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such A. Minimum clearances to the exterior surfaces of the boiler requirements, to the National Fuel Gas Code, ANSI Z223.1- shall be as follows: latest edition. MINIMUM ALCOVE AND CLOSET CLEARANCE For Combustible Recommended This installation must also conform to the additional require- Surf

Summary of the content on the page No. 5

VICTORY VSPH Models 5 VENTING APPLICATION If additional non-direct vent appliances are installed in the same VSPH Series are sealed combustion type boilers, they maybe space and adequate air openings are provided for them, there installed and vented either as a direct vent boiler which all air are no additional air openings required for the VSPH boiler. for combustion is obtained directly from outside or as a non- direct vent boiler which air for combustion is taken from inside For both direct a

Summary of the content on the page No. 6

6 VICTORY VSPH Models When joining the various components of the above listed EXAMPLE: Boiler model VSPH-180 is to be installed at sea vent systems, the manufacturers’ instructions should be level. The combustion air is provided by air intake piping closely followed to insure proper sealing. Use sealant speci- directly to the boiler (direct-vent installation). Flue piping fied by vent system manufacturer for sealing of pipe and fit- includes 2 elbows and using Heat-Fab system. Air intake is ting

Summary of the content on the page No. 7

VICTORY VSPH Models 7 Maximum allowed flue and air intake equivalent length (Feet) for Heat-Fab Saf-T vent system (Including EZ Seal) 0 - 5,000 Ft. 5,000 - 7,500 Ft. 7,500 - 10,000 Ft. Boiler Model Piping Elevation Elevation Elevation Number VSPH-60 Flue 40 40 40 Air Intake 40 40 40 VSPH-90 Flue 40 40 35 Air Intake 40 40 40 VSPH-120 Flue 40 35 30 Air Intake 40 40 40 VSPH-150 Flue 35 30 25 Air Intake 40 40 35 VSPH-180 Flue 33 28 23 Air Intake 40 35 30 Maximum allowed flue and air intake equivalen

Summary of the content on the page No. 8

8 VICTORY VSPH Models VENTING INSTALLATION sage, an appropriate UL listed roof flashing must be used. Follow the vent material manufacturer’s instructions in con- junction with these instructions for venting system installa- An existing chimney (see Figure 8) may be used as a chase tion. for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe with in the chimney. I. Non-Direct Vent Installation The vertical vent piping must terminate with a screened tee, The ai

Summary of the content on the page No. 9

VICTORY VSPH Models 9 VICTORY VSPH MODELS NON - DIRECT VENT, SIDEWALL VENTING All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 5). Figure 5. Non-direct vent, side wall venting. Figure 6. Non-direct vent, side wall venting. Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE. AL 29-4C IS A REGISTERED TRADEMAR

Summary of the content on the page No. 10

10 VICTORY VSPH Models VICTORY VSPH MODELS- NON- DIRECT VENT, VENTING THROUGH A ROOF All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S. venting materials (See page 5). Figure 7. Victory VSPH models-non-direct vent, venting through the roof AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP. *

Summary of the content on the page No. 11

VICTORY VSPH Models 11 VICTORY VSPH MODELS- NON - DIRECT VENT, UTILIZING AN EXISTING CHIMNEY AS A CHASE All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S. venting materials (See page 5). Figure 8. Victory VSPH models-non-direct vent, utilizing an existing chimney as a chase AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP. *

Summary of the content on the page No. 12

12 VICTORY VSPH Models VICTORY VSPH MODELS - DIRECT VENT, SIDEWALL VENTING All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S. venting materials (See page 5). Figure 9. Direct vent, sidewall venting illustration; with straight horizontal vent. Figure 10. Direct vent, sidewall venting illustration; horizontal vent using elbows. ** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.

Summary of the content on the page No. 13

VICTORY VSPH Models 13 10. From inside, install inside termination plate using 4 B. DIRECT VENT - VENTING AND AIR INTAKE screws. Make sure the 4" collar on the plate, penetrate- THROUGH A ROOF ed into the galvanized pipe. Figure 12 shows typical vertical venting. The vent pipe must 11. Assemble and seal straight screened termination to pass through the ceiling, floor and the roof vertically through a the slip joint connector. 7" minimum diameter cutout. A fire stop is required for each ceiling

Summary of the content on the page No. 14

14 VICTORY VSPH Models VICTORY VSPH MODELS DIRECT VENT, VENTING AND AIR INTAKE THROUGH A ROOF All joints in vent system must be liquid and pressure tight. Use U/L listed single wall 3” dia. AL29-4C S.S. venting materials (See page 5). Figure 12. Direct vent, venting and air intake through a roof.

Summary of the content on the page No. 15

VICTORY VSPH Models 15 VENTING AND AIR INTAKE SYSTEM REGULAR C. The boiler and its gas connection must be leak tested INSPECTION before placing the boiler in operation. Use liquid soap solu- tion for all gas leak testing. DO NOT use open flame. This A. Inspect the system regularly for condensation, corrosion boiler and its individual shutoff valve must be disconnected and/or physical damage. A qualified professional should ser- from the gas supply piping system during any pressure test- 1 vice t

Summary of the content on the page No. 16

M 16 VICTORY VSPH Models 120V/24V BLOWER AQUASTAT PRESSURE TRANSFORMER (INDUCER) P2 ROLL-OUT SWITCH L4080B SWITCH PINK BLUE RED BLACK BLACK 2 1 YELLOW G/Y 24V BROWN THERMOSTAT BLACK RED P3 1 4 7 4 1 WHITE P6 YELLOW 5 2 2 5 8 1 P5 BLACK 6 3 3 6 9 1 2 WHITE GREEN 2 1 3 P1 BLACK RED RED 2 3 P4 4 PV DISCONNECT MV BLACK 1 WHITE SWITCH GREEN L1-HOT GND MV/PV WHITE VR8204A 120V/60Hz GAS VALVE WHITE WIRE LEGEND: L2-NEUTRAL FACTORY WIRED JUNCTION FIELD WIRED, FIELD SUPPLIED CIRCULATOR BOX 1 PROVIDE

Summary of the content on the page No. 17

VICTORY VSPH Models 17 MULTIZONING OF VSPH BOILER ZONE VALVE SYSTEM USING V8043E/F ZONE VALVES Figure 14. MULTIZONING OF VSPH BOILER PUMP ZONING SYSTEM USING R845A RELAY Figure 15. MULTIZONING OF VSPH BOILER PUMP ZONING SYSTEM USING R882A/B RELAYS Figure 16.

Summary of the content on the page No. 18

18 VICTORY VSPH Models 2. Power Connection 2 2.. Circulating Systems Victory VSPH boilers are equipped with a water circulating A. Remove electrical junction box cover. pump mounted to the return water connection on the boiler. This pump location is appropriate for most installations. It may be B. Hot connection lead is black. Neutral connection lead is white. desired and proper to locate this pump to the alternate location Proper polarity is important for VSPH boilers. Reversed shown in Figure

Summary of the content on the page No. 19

VICTORY VSPH Models 19 5. Cold Water Fill Pressure reducing (fill) valve and shut-off valve should be installed. 6. Relief Valve Discharge Piping Use same size or larger piping than valve outlet. Must ter- minate 6" minimum from floor with a plain (no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT hard-pipe to drain piping. Figure 18. Cooling system to a water boiler and chiller. 7. Providing Protection from Freezing Anti-freeze

Summary of the content on the page No. 20

20 VICTORY VSPH Models II. Initial Start 11. Set thermostat to desired setting. Safe lighting and other performance criteria were met when 12. If the appliance will not operate, follow the instructions testing various gas manifold and control assemblies used “To Turn Off Gas to Appliance” and call your service on the Victory VSP Series Boilers under the ANSI Z21.13- technician or gas supplier. latest edition. To Turn Off Gas to Appliance Instructions 1. Set thermostat to lowest setting. Follow


Alternative user manuals
# User manual Category Download
1 Slant/Fin Bobcat B-120 User manual Boiler 6
2 Slant/Fin Bobcat B-200 User manual Boiler 2
3 Slant/Fin Caravan LZDF series User manual Boiler 3
4 Slant/Fin Caravan L-Series User manual Boiler 2
5 Slant/Fin B-120A User manual Boiler 4
6 Slant/Fin CB Series User manual Boiler 12
7 Slant/Fin GALAXY GX User manual Boiler 15
8 Slant/Fin GALAXY GXH User manual Boiler 13
9 Slant/Fin B-200A User manual Boiler 2
10 Slant/Fin Eutectic EC20 User manual Boiler 1
11 Slant/Fin S User manual Boiler 14
12 Slant/Fin Eutectic EC10) User manual Boiler 0
13 Slant/Fin GALAXY GXHA User manual Boiler 2
14 Slant/Fin GALAXY GG User manual Boiler 51
15 Slant/Fin Gas Condensation Within s User manual Boiler 2
16 Sony HDV 1080I HVR-M15N/M15P User manual Boiler 67
17 Sony HDV 1080I HVR-M25N/M25P User manual Boiler 50
18 A.O. Smith 200 User manual Boiler 2
19 A.O. Smith 201 User manual Boiler 7
20 A.O. Smith 750 & 1000 User manual Boiler 6