Emerson GXT2U user manual

User manual for the device Emerson GXT2U

Device: Emerson GXT2U
Category: Power Supply
Manufacturer: Emerson
Size: 1.27 MB
Added : 9/15/2014
Number of pages: 40
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Emerson GXT2U. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Emerson GXT2U.

For your convenience

If looking through the Emerson GXT2U user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Emerson GXT2U on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Emerson GXT2U to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Emerson GXT2U User manual - Online PDF
Advertisement
« Page 1 of 40 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Emerson GXT2U but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Emerson GXT2U. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

DISCONTINUED
PRODUCT
AC Power Systems
For Business-Critical Continuity™
® ™
Liebert GXT2U
User Manual - 208V, 2700VA

Summary of the content on the page No. 2

DISCONTINUED PRODUCT

Summary of the content on the page No. 3

TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . . 1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 MAJOR COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Transient Voltage Surge Suppression and EMI/RFI Filters . . . 5 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . 5 Inverter. . . . . . . . .

Summary of the content on the page No. 4

OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Normal Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Bypass Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 5

IMPORTANT SAFETY INSTRUCTIONS WARNING ! Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone. SAVE THESE INSTRUCTIONS This

Summary of the content on the page No. 6

DO NOT CONNECT equipment that could overload the UPS or demand half- wave rectification from the UPS, for example: electric drills, vacuum cleaners, laser printers or hairdryers. Storing magnetic media on top of the UPS may result in data loss or corruption. Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow. When replacing batteries, replace with th

Summary of the content on the page No. 7

GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual i Indicates the unit contains a valve-regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Standby DISCONTINUED 3 PRODUCT

Summary of the content on the page No. 8

INTRODUCTION Congratulations on your choice of the Liebert GXT2U™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure that may interrupt computer operations, cause data loss, or even damage equipment. The Liebert GXT2U protects equipment from these disturban

Summary of the content on the page No. 9

MAJOR COMPONENTS Input Output Dynamic Bypass TVSS & Rectifier L1 EMI/RFI Inverter L1 /PFC Filters DC to DC Converter Battery Battery Charger L2 L2 G G Transient Voltage Surge Suppression and EMI/RFI Filters These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected. Rectifier/Power Factor Correction (P

Summary of the content on the page No. 10

DC-to-DC Converter The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability. Battery The Liebert GXT2U utilizes valve-regulated, nonspillable lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional external battery

Summary of the content on the page No. 11

Liebert GXT2U—Rear View Liebert ® IntelliSlot DB-9 Port Communications Port Cooling Fans AC Input (L6-20) Input Circuit External Breaker Battery (20 amp) Connector Output Receptacle (L6-20R) Support Base Output Receptacles (L6-15R) DISCONTINUED 7 PRODUCT

Summary of the content on the page No. 12

INSTALLATION Preparation 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative. CAUTION ! The UPS is heavy (see Specifications section). Take proper precautions when lifting or moving it. 2. Decide where to place the Liebert GXT2U. Install the UPS indoors in a con- trolled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flamma- ble liqui

Summary of the content on the page No. 13

UPStation GXT –+ AC INPUT BATTERY UPS ON BYPASS Rack-Mount UPS Conversion and Installation NOTE When rack mounted, the UPS must be supported by a shelf, brackets or slide rails on each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack. 1. For slide rail installations, first remove the top/side fin. Slide the top/side fin forward, then lift it up to remove. If desired, install the optional rack mount handles that were s

Summary of the content on the page No. 14

Install rear member of each M5 screws bracket assembly into rack enclo- Front rack sure with two (2) M5 screws pro- mounting rails vided in this kit. (See figure at right.) Return flanges on bracket assembly fit to the inside of rack mounting rails. Insert screws loosely (finger-tight) into top and bottom holes of return flange on rear member. Extend bracket assembly by sliding front mem- Rear rack ber forward until it touches the mounting front rack mounting rail. Insert rails two

Summary of the content on the page No. 15

6. Open grease packet provided Apply in this kit. Apply a 1" long grease bead of grease four (4) places UPS or inside the bottom, curved battery tracks of front members as cabinet shown at right. The grease will allow the equipment to slide into the bracket assem- blies more easily. Apply grease (inside) CAUTION ! Lifting equipment into rack may be a two-person job, depending on weight of equipment. See equipment’s user manual. 7. Insert the equipment, with inner members attached f

Summary of the content on the page No. 16

9. To orient the display for horizontal Vertical Horizontal viewing, remove the front plastic overlay overlay bezel by pulling forward evenly on for both sides. The unit has two front tower panel overlays. Remove the outer UPS overlay (used for tower installation). This reveals a horizontally oriented front panel overlay for rack mount- ing. Snap the front bezel back into place. 10.Once the UPS is installed in the rack, the load may be connected. Ensure the load equipment is turned of

Summary of the content on the page No. 17

4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet. 5. Connect the supplied external battery cabi- net cable to the rear of the external battery cabinet, then to the rear of the UPS. 6. Turn ON the battery breaker on the rear of the external battery cabinet. 7. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to the Batter

Summary of the content on the page No. 18

CONTROLS AND INDICATORS All LEDs illuminated for illustrative purposes only. ON/Alarm Silence/Manual Battery Test Button This button controls output power to connected load(s) and has three functions: • ON • Alarm Silence • Manual Battery Test ON - Pressing this button will start up the UPS in order to provide conditioned and protected power. Alarm Silence - To silence alarms, press this button for at least one second. After the alarm is silenced, the Liebert GXT2U will reactivate the alarm

Summary of the content on the page No. 19

Standby/Manual Bypass Button This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass. CAUTION ! While the UPS is in Normal Mode operation, pressing the Standby/ Manual Bypass button once will put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press the Standby/ Manual Bypass button two distinct times (for about one second each time) to turn off the UPS. Perform all necessary shutdown procedures on connected loads before t

Summary of the content on the page No. 20

Output Voltage Selection The Output Voltage is user configurable and is designed to allow selecting or changing the desired output voltage to match the utility via the Liebert GXT2U Configuration Program provided with the UPS. The settings to choose from are 200, 208, 220, 230, and 240 VAC output. The factory default setting is 208 VAC. CAUTION ! Never change the voltage settings while the UPS is ON and powering connected loads. NOTE Setting output voltage to 200 VAC will cause the UPS unit


Alternative user manuals
# User manual Category Download
1 Emerson 1000 User manual Power Supply 64
2 Emerson 1500VA User manual Power Supply 15
3 Emerson 2200 User manual Power Supply 4
4 Emerson 3000 User manual Power Supply 41
5 Emerson 250-400kVA User manual Power Supply 16
6 Emerson 1000VA User manual Power Supply 3
7 Emerson 40-120KVA User manual Power Supply 2
8 Emerson 500VA User manual Power Supply 3
9 Emerson 4-16kVA User manual Power Supply 2
10 Emerson 60HZ User manual Power Supply 0
11 Emerson 650VA User manual Power Supply 1
12 Emerson 12-20kVA User manual Power Supply 11
13 Emerson 480VAC User manual Power Supply 1
14 Emerson 6 kVA User manual Power Supply 18
15 Emerson Albr BDS-256XL User manual Power Supply 0
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2