Lennox International Inc. XC21 user manual

User manual for the device Lennox International Inc. XC21

Device: Lennox International Inc. XC21
Category: Air Conditioner
Manufacturer: Lennox International Inc.
Size: 0.71 MB
Added : 1/16/2014
Number of pages: 19
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Lennox International Inc. XC21. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Lennox International Inc. XC21.

For your convenience

If looking through the Lennox International Inc. XC21 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Lennox International Inc. XC21 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Lennox International Inc. XC21 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Lennox International Inc. XC21 User manual - Online PDF
Advertisement
« Page 1 of 19 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Lennox International Inc. XC21 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Lennox International Inc. XC21. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

INSTALLATION
INSTRUCTIONS
2012 Lennox Industries Inc.
Dallas, Texas, USA
®
Dave Lennox Signature
Collection XC21 System
AIR CONDITIONERS
506923−01
7/2012
Litho U.S.A.
Supersedes 4/2012
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or
WARNING
maintenance can cause property damage, personal inju-
The State of California has determined that this product ry or loss of life.
may contain or produce a chemical or chemica

Summary of the content on the page No. 2

UNIT DIMENSIONS − INCHES (MM) DISCHARGE 39−1/2 35−1/2 ELECTRICAL AIR (1003) (902) INLETS 47 (1194) SUCTIOn LINE INLET 4−1/2 (114) LIQUID LINE INLET 18−1/2 (470) 8 (203) 1 (25) SIDE VIEW ACCESS VIEW UNIT SUPPORT FEET 26−7/8 (683) 16−7/8 (429) 8−3/4 (222) 3−3/4 (95) 30−3/4 3−1/8 4−5/8 (781) (79) (117) BASE WITH ELONGATED LEGS NOTICE ! STEP 1 −− SETTING THE UNIT (Continued) −− Unit Placement Roof Damage! This system contains both refrigerant and oil. Some rubber roofing material may absorb oil, cau

Summary of the content on the page No. 3

STABILIZING UNIT ON UNEVEN SURFACES PLACEMENT #10 X 1/2" LONG SELF−DRILLING INSTALL UNIT AWAY SHEET METAL FROM WINDOWS COIL SCREWS STABILIZING BRACKET (18 GAUGE METAL  2" BASE PAN WIDTH; HEIGHT AS REQUIRED) #10 X 1−1/4" LONG HEX HD SCREW AND FLAT WASHER CORNER POST Concrete slab  use two plastic anchors (hole drill 1/4") TWO 90 ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION ! IMPORTANT ! FIGURE 2 Unit Stabilizer Bracket Use (field−provided): Always use stabilizers when unit is ra

Summary of the content on the page No. 4

IMPORTANT ! WARNING If this unit is being matched with an approved line set or indoor unit coil that was previously charged Fire, Explosion and Personal Safety Haz- with mineral oil, or if it is being matched with a coil ard. Failure to follow this warning could re- which was manufactured before January of 1999, sult in damage, personal injury or death. the coil and line set must be flushed prior to installa- Never use oxygen to pressurize or purge tion. Take care to empty all existing traps. Po

Summary of the content on the page No. 5

VAPOR LIQUID STEP 2 −− REFRIGERANT PIPING −− Removing Existing Indoor Metering Device TYPICAL EXISTING FIXED ORIFICE TYPICAL EXISTING EXPANSION VALVE REMOVAL REMOVAL PROCEDURE OR PROCEDURE (UNCASED COIL SHOWN) 1B 1A (UNCASED COIL SHOWN) STUB END TWO−PIECE PATCH PLATE LIQUID LINE DISTRIBUTOR TUBES (UNCASED COIL ONLY) ORIFICE EXPANSION LIQUID LINE ORIFICE HOUSING HOUSING VALVE DISTRIBUTOR TUBES ® TEFLON ® TEFLON RING RING FIXED ORIFICE BRASS NUT ® TEFLON SENSING RING LINE DISTRIBUTOR ASSEMBLY DIS

Summary of the content on the page No. 6

STEP 2 −− REFRIGERANT PIPING −− Brazing Procedures CAP AND CORE REMOVAL PIPING PANEL REMOVAL / PREPARING LINE SET Remove service cap and core from both the suction / Remove piping panel to access service valves. Cut 2 1 vapor and liquid line service ports. ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain SERVICE PORT CAP round. Do not crimp end of the line. SERVICE PORT CORE CUT AND DEBUR LINE SET SIZE MATCHES SERVICE VALVE CONNECTION SERVI

Summary of the content on the page No. 7

CAUTION WARNING Brazing alloys and flux contain materials which are Danger of fire. Bleeding the refrigerant hazardous to your health. charge from only the high side may result Avoid breathing vapors or fumes from brazing in pressurization of the low side shell and operations. Perform operations only in well−ventilated suction tubing. Application of a brazing areas. torch to a pressurized system may result Wear gloves and protective goggles or face shield to in ignition of the refrigerant and oi

Summary of the content on the page No. 8

STEP 3 −− INSTALLING INDOOR EXPANSION VALVE This outdoor unit is designed for use in systems that include an expansion valve metering device. See the XC21 Product Specifications bulletin (EHB) for approved expansion valve kit match−ups and application information. The expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−pro- vided plenum, install the expansion valve in a manner that will provide access for

Summary of the content on the page No. 9

STEP 4 −− LEAK TEST AND EVACUATION LOW HIGH MANIFOLD GAUGE SET OUTDOOR UNIT A B TO VAPOR SERVICE VALVE NOTE − Position canister to deliver liquid refrigerant. NITROGEN HFC−410A CONNECT GAUGE SET A. Connect the high pressure hose of an HFC−410A manifold gauge set to the vapor valve service port. 1 NOTE  Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage. B. With both mani

Summary of the content on the page No. 10

STEP 4 −− LEAK TEST AND EVACUATION (Continued) EVACUATION LOW HIGH CONNECT GAUGE SET NOTE  Remove cores from service valves (if not already done). 3 A. Connect low side of manifold gauge set with 1/4 SAE in−line tee to vapor line service valve B. Connect high side of manifold gauge set to OUTDOOR MANIFOLD liquid line service valve 1/4 SAE TEE WITH SWIVEL UNIT GAUGE SET C. Connect available micron gauge connector COUPLER A on the 1/4 SAE in−line tee. D. Connect the vacuum pump (with vacuum 500 g

Summary of the content on the page No. 11

STEP 5 −− ELECTRICAL −− Circuit Sizing and Wire Routing In the U.S.A., wiring must conform with current local codes IMPORTANT ! and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current If unit is equipped with a crankcase heater, it should Canadian Electrical Code (CEC). be energized 24 hours before unit start−up to pre- vent compressor damage as a result of slugging. Refer to the furnace or air handler installation instructions for ad

Summary of the content on the page No. 12

A. ROUTE CONTROL WIRES  NON−COMMUNICATING 3 Install low voltage control wiring from outdoor to indoor unit and from thermostat to indoor unit. All low voltage wiring must enter unit through provided field−installed busing installed in electrical inlet. Run 24VAC control wires through hole with grommet. Make 24VAC control wire connections to outdoor control (A175). CONTROL (A175) NOTE  Do not bundle any excess 24VAC control wires inside control box. B NOTE  Wire tie provides low voltage wire s

Summary of the content on the page No. 13

STEP 5 −− ELECTRICAL (Continued) −− Outdoor Control (A175) Jumpers and Terminals Communication System The Lennox icomfort−enabled thermostat must be used in communicating applications. The jumper settings and link are default settings and ONLY control system operation if configuration settings in the icomfort−enabled thermostat are not available. NOTE  Fan cycling routine when activated will cycle the Non −Communicating System fan ON for five minutes if the outdoor ambient air The unit will

Summary of the content on the page No. 14

STEP 5 −− ELECTRICAL (Continued) −− Field Control Wiring The following two illustrations provide examples of control wiring connections when using a non−communicating thermostat. For examples of control wiring in complete or partial communicating systems, see the icomfort−enabled thermostat Quick Start Guide which is provided with the thermostat. Air Handler ComfortSense 7000 Thermostats Catalog # Y0349 or Y2081 7 DS XC21 Two −Stage Air Conditioner Control R O G W On −board link L W2 Low vol

Summary of the content on the page No. 15

Furnace ComfortSense 7000 Thermostats 5 Catalog # Y0349 or Y2081 XC21 Two −Stage Air DS Conditioner Control R O G W On −board link L W2 Low voltage thermostat L wiring Y2 W1 H Y1 O DH O L R DS H C C 2 D Y1 B 3 Y2 Y2 4 1 Y1 G R C W2 T W1 T 1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional). ® 2. R to L connection is required for this model when using the ComfortSense 7000 − catalog number Y0349 only. Resistor Kit (catalog

Summary of the content on the page No. 16

2. Adjust room thermostat set point 5ºF above (heating Charging operation) or 5ºF below (cooling operation) the room The XC21 unit is factory−charged with enough HFC−410A temperature. refrigerant to accommodate a 15−foot length of refrigerant 3. Remove control access panel. Install refrigeration piping. Charge should be checked and adjusted using the gauges on unit. Attach the amp meter to the common tables provided on the charging procedure sticker on the (black wire) wire of the compressor ha

Summary of the content on the page No. 17

XC21 Field Operational Checklist Cooling*** Heating*** Unit Readings Y1 Expected results Y2 Expected results Y1 Y2 Second First during Y2 demand Second during Y2 demand First Stage Stage Stage (toggle switch ON) Stage (toggle switch ON) Compressor Voltage Same Same Amperage Higher Higher Condenser Fan motor Amperage Same or Higher Same or Higher Temperature Ambient Same Same Outdoor Coil Discharge Air Higher Lower Compressor Discharge Line Higher Higher Indoor Return Air Same Same Indoor Coil Di

Summary of the content on the page No. 18

XC21 Start−Up and Performance Checklist Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Solar Module Mfg and Model Serial Notes: START−UP CHECKS Refrigerant Type: Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps: COOLING MODE Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Temperature: HEATING MODE Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Tempe

Summary of the content on the page No. 19

Routine Maintenance Homeowner Information In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. CAUTION NOTE  The filter and all access panels must be in place Before attempting to perform any service or mainte- any time the unit is in operation. If you are unsure about the nance, turn the electrical power to unit OFF at discon- filter required for your system, call your Len


Alternative user manuals
# User manual Category Download
1 Lennox International Inc. 2SCU13 User manual Air Conditioner 425
2 Lennox International Inc. HS27 User manual Air Conditioner 71
3 Lennox International Inc. 15CHAX Series User manual Air Conditioner 92
4 Lennox International Inc. 506945-01 User manual Air Conditioner 64
5 Lennox International Inc. 506510-01 User manual Air Conditioner 30
6 Lennox International Inc. 06/11 50672801 User manual Air Conditioner 30
7 Lennox International Inc. HSXA12 User manual Air Conditioner 35
8 Lennox International Inc. HSXA15 User manual Air Conditioner 12
9 Lennox International Inc. 15GCSX User manual Air Conditioner 17
10 Lennox International Inc. CONDENSING UNITS User manual Air Conditioner 19
11 Lennox International Inc. Dave Lennox Signature Collection XC17 User manual Air Conditioner 12
12 Lennox International Inc. HVAC Zone Control User manual Air Conditioner 29
13 Lennox International Inc. Dave Lennox Signature Collection XC21 System User manual Air Conditioner 9
14 Lennox International Inc. Lennox Air Handler User manual Air Conditioner 7
15 Lennox International Inc. Lennox Healthy Climate User manual Air Conditioner 5
16 Sony SU-PW2 User manual Air Conditioner 12
17 Sony CV-P12PX User manual Air Conditioner 3
18 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
19 Sony VGN-BX500 User manual Air Conditioner 1
20 Philips 190S5 User manual Air Conditioner 21