Streszczenie treści zawartej na stronie nr. 1 
                    
                         E6581830  
 
 
 
 
 
 
 
 
 
 
 
TOSVERT VF-S15 series 
 
®
 option unit Function Manual 
CCL003Z
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
NOTICE 
 
 
 
 
1. Read this manual before installing or operating. Keep this instruction manual on 
 
hand of the end user, and make use of this manual in maintenance and inspection.  
 
2. All information contained in this manual will be changed without notice. Please 
 
contact your Toshiba distributor to confirm the latest information. 
 
 
 
 
 
 
 
 
 
 
     
                    
                    Streszczenie treści zawartej na stronie nr. 2 
                    
                         E658130  Introduction  ® Thank you for purchasing the “CC-Link option (CCL003Z)” for TOSVERT VF-S15 drive.  This option can connect with open field network CC-Link and data communications with  the CC-Link master through installing this option in the VF-S15 and using it. Besides this  instruction manual, the “CC-Link option Instruction Manual” is required to develop  software communicating with VF-S15.  This option needs the option adaptor to connect VF-S15 which type form is SBP009Z.  Please m
                    
                    Streszczenie treści zawartej na stronie nr. 3 
                    
                         E658130  Handling in general      Warning   Do not connect or disconnect a network cable while the drive power is on.    It may lead to electric shocks or fire.  Prohibited   See the instruction manual attached with the option unit for cautions the handling.    Otherwise, it may lead to electric shocks, fire, injuries or damage to product.  Mandatory  Network control     Warning   Do not send the value out of the valid range to objects and attributes.    Otherwise, the motor may suddenly start/
                    
                    Streszczenie treści zawartej na stronie nr. 4 
                    
                         E658130  Table of Contents    1. OVERVIEW ............................................................................................................................................ - 4 -  2. BASIC SPECIFICATIONS..................................................................................................................... - 4 -  2.1. CC-Link Version.............................................................................................................................. - 5 -  2.1.1. 
                    
                    Streszczenie treści zawartej na stronie nr. 5 
                    
                         E658130  1. Overview  The option allows the VF-S15 drive to be connected into a CC-Link network. CC-Link supports a  maximum of 42 nodes, allowing for the Master and this option is based on CC-Link V1.1 and V2.0.    The CCL-003Z is able to operate RUN/STOP, monitor the status of the drive, set the drive’s parameter  and etc. by the CC-Link master through installing the VF-S15. And it can use various applications.    2. Basic specifications    Item Specification  Ope
                    
                    Streszczenie treści zawartej na stronie nr. 6 
                    
                         E658130  2.1. CC-Link Version  2.1.1. CC-Link Ver. 1.10  The conventional CC-Link products, whose inter-station cable lengths have equally been  changed to 20cm (7.87 inch) or more to improve the inter-station cable length restriction,  are defined as CC-Link Ver. 1.10. In comparison the conventional products are defined  as CC-link Ver. 1.00.  Refer to the CC-link Master Module Manual for the maximum overall cable lengths and  inter-station cable lengths of CC-Link Ver. 1.00 and Ver. 1.10    C
                    
                    Streszczenie treści zawartej na stronie nr. 7 
                    
                         E658130  3. Names and functions  The drawing below shows names and functions of main parts.    3.1. Outline    Connector to the inverter                                  Release tab    LED indicator  (See 4.5)    CC-Link Connector  DA DB DG SLD FG  - 6 -                                                                                                                                                                                                                                                     
                    
                    Streszczenie treści zawartej na stronie nr. 8 
                    
                         E658130  4. Installation on inverter  Refer to VF-S15 option adapter instruction manual (E6581838) for the installation on the  inverter.     The following steps must be performed before installing.   1. Shut off all input power.  Mandatory  2. Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit.      4.1. Connection cable  In the CC-Link system, use CC-Link dedicated cables.  If the cable used is other than the CC-Link dedicated cable, the performance of the  
                    
                    Streszczenie treści zawartej na stronie nr. 9 
                    
                         E658130  4.3. Connection of CC-Link master unit and inverter  The example of the connection of the CC-Link master unit and the inverter is shown.。  Motor    R/L1  U/T1    S/L2 V/T2   Inverter  I M  T/L3 VF-S15 W/T3     DA DA  CC-Link        DB DB  Master     CCL003Z  DG DG  Unit  SLD SLD  FG FG     *Connection of Several Inverters   Factory Automation can be applied to several inverters which share a link system as   CC-Link remote device stations and are controlled and monitored by PLC user pr
                    
                    Streszczenie treści zawartej na stronie nr. 10 
                    
                         E658130  4.4. The maximum connection number of units  1. Maximum number of units connected to one master station (CC-Link Ver.1.10)  42 units (when only inverters are connected)  If any other units are included, the number of stations occupied depends on the unit and   therefore the following conditions must be satisfied:  {(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≦ 64  a: Number of units occupying 1 station  b: Number of units occupying 2 stations  c: Number of units occupying 3 stations  d: Num
                    
                    Streszczenie treści zawartej na stronie nr. 11 
                    
                         E658130  2. Maximum number of units connected to one master station (CC-Link Ver.2.00)  42 units (when connections are inverter only)  If any other units are included, the number of stations occupied depends on the unit and   therefore the following conditions must be satisfied:  {(a + a2 + a4 + a8) + (b + b2 + b4 + b8) × 2 + (c + c2 + c4 + c8) × 3   + (d + d2 + d4 + d8) × 4} ≦ 64  {(a × 32 + a2 × 32 + a4 × 64 + a8 × 128) + (b × 64 + b2 × 96 + b4 × 192 + b8 × 384)  + (c × 96 + c2 × 160 + c4 × 3
                    
                    Streszczenie treści zawartej na stronie nr. 12 
                    
                         E658130  4.5. LED indicator  The LEDs shows the present status of the network and module  Refer to 7.3 for detail.    L.RUN SD        RD  L.ERR             ■ Layout of LED  L.RUN Light on during communication.   SD Light on during send the data of CC-Link.  RD Light on during receive the data of CC-Link.  L.ERR Light on during communication error.      - 11 -                                                                                                                                          
                    
                    Streszczenie treści zawartej na stronie nr. 13 
                    
                         E658130  5. Functions  This option is a communication interface unit that allows the PLC program to operate, monitor   and set the parameter of the inverter as a remote station of CC-Link. It is able to communicate   with a maximum speed of 10Mbps not only transmitting bit data but also by word data.  Moreover, more data transmissions are possible by the use of CC-Link V2.0.    5.1. Initial setting  Set the following parameters of the inverter.    Factory CC-Link  Title Function Description  se
                    
                    Streszczenie treści zawartej na stronie nr. 14 
                    
                         E658130  5.2.  Communication parameters for CCL003Z    Title Function Description  Communication error detection   c100  0.0 - 100.0 sec.  delay time  0: Stop and controlled by cmod, fmod  c101  1: Operation continue  Inverter operation at the 2: Deceleration stop  communication loss action 3: Coast stop  4: Network error stop (err8 trip)  5: Preset speed operation (by c102 setting)  Preset speed  0: None  c102  operation selection 1 to 15: Preset speed  0: Disconnection detection  c103  Commun
                    
                    Streszczenie treści zawartej na stronie nr. 15 
                    
                         E658130  5.3. CC-Link function setting    5.3.1. Station number setting  Use parameter c120 to set station number of the inverter.  Set this parameter within the range of 1 to 64.  Title Function Description  CC-Link station   c120 1 to 64  number selection    *Use different station numbers for different devices. (If different devices have the same station  number, the communication cannot be performed properly.)    ・ Set consecutive numbers for the station numbers. (Do not skip a number in seq
                    
                    Streszczenie treści zawartej na stronie nr. 16 
                    
                         E658130  5.3.3. CC-Link extended setting  Remote register function can be extended.    Title Function Description  CC-Link extended selection  * 0: Occupies one station (V1.10)  c122  1: Occupies one station double (V2.0)  2: Occupies one station quadruple (V2.0)  3: Occupies one station octuple (V2.0)    ・ When using double, quadruple and octuple settings of the CC-Link Ver.2, station data   of the master station must be set to double, quadruple and octuple also.  (If the master station is CC-
                    
                    Streszczenie treści zawartej na stronie nr. 17 
                    
                         E658130  5.4. Basic functions  This clause shows the basic function of this CC-Link option using by CC-Link communication.    5.4.1. Run and frequency operation command  The PLC program can operate the inverter to run, stop, set the operation frequency and  change the parameters.  If the PLC controls these operations, select the command mode and the frequency setting  mode.     The parameter setting of the inverter  Command mode selection   cmod     : 4[Communication option] (Factory setting: 1
                    
                    Streszczenie treści zawartej na stronie nr. 18 
                    
                         E658130  5.5. I/O signal list    5.5.1. One station is occupied (CC-Link Ver.1) (c122=0)  This option occupies one station area of the buffer memory of the PLC.  In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register  (RWw, RWr both 4 word) in the communication data for one station area.     Remote I/O (Default value = 0)  Inverter (Slave) → PLC (Master) PLC (Master) → Inverter (Slave)  Device No. Signal Device No. Signal  RXn0 Forward running RYn0 Forward r
                    
                    Streszczenie treści zawartej na stronie nr. 19 
                    
                         E658130  5.5.2. Double setting is selected (CC-Link Ver.2) (c122=1)  This option occupies one station area of the buffer memory of the PLC.  In the case of c122 = 1, there are remote I/O (RX, RY both 32 bits(same as CC-LINK   Ver.1)) and the remote register (RWw, RWr both 8 word) in the communication data for one   station area.  * Default value of RY and RX is 0.    Remote register (Default value = 0)  RWr                    Inverter → PLC RWw                    PLC → Inverter  Address Signal 
                    
                    Streszczenie treści zawartej na stronie nr. 20 
                    
                         E658130  5.5.4. Octuple setting is selected (CC-Link Ver.2) (c122=3)  This option occupies one station area of the buffer memory of the PLC.  In the case of c122 = 3, there are remote I/O (RX, RY both 32 bits(same as CC-LINK   Ver.1)) and the remote register (RWw, RWr both 32 word) in the communication data for one   station area.  * Default value of RY and RX is 0.    Remote register (Default value = 0)  RWr                    Inverter → PLC RWw                    PLC → Inverter  Address Signa