TOSHIBA G9000 
80/100/160/225 kVA 
 
 
GUIDE SPECIFICATION 
THREE PHASE UNINTERRUPTIBLE POWER SUPPLY 
 
 
 
1                                                                                                                                                                                                                          
                    
                    Streszczenie treści zawartej na stronie nr. 2 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      2                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    Streszczenie treści zawartej na stronie nr. 3 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      Table of Contents    1 SCOPE ......................................................................................................................................................................... 5  1.1 SYSTEM ............................................................................................................................................................................ 5  2 SYSTEM DESCRIPTION ...................
                    
                    Streszczenie treści zawartej na stronie nr. 4 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply    9.2 REMOTE STATUS ALARM PANEL (RSAP)............................................................................................................................... 15  10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION) ..................................................................................................... 16  11 MAINTENANCE BYPASS PANEL (OPTION) ..........................................................................
                    
                    Streszczenie treści zawartej na stronie nr. 5 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      1 SCOPE    1.1 System  These specifications describe a high efficiency continuous duty, three-phase, on-line, solid-state  Uninterruptible Power Supply system (UPS).  The UPS shall operate utilizing the existing power  distribution system to provide high quality, uninterruptible power to critical loads.  The UPS shall consist of an AC/DC multi-level Insulated Gate Bipolar Transistor (IGBT)  Rectifier, DC/DC Converter/Battery 
                    
                    Streszczenie treści zawartej na stronie nr. 6 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      2.3 System Operation:  The UPS shall operate as a fully automatic on-line system in the following modes:  2.3.1 Normal  IGBT Rectifier converts AC input power to DC power for the inverter and for charging the  batteries. The IGBT inverter supplies clean and stable AC power continuously to the critical  load.  The UPS Inverter output shall be synchronized with the bypass AC source when the  bypass source is within the AC input
                    
                    Streszczenie treści zawartej na stronie nr. 7 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      3.2.3 Clearances for installation   Ceiling Level    : 20” minimum from top of UPS to ceiling   Front     : 40” minimum for maintenance           (Local and regional codes may apply)   Bottom    : Knockouts for power cable access   Rear     : Zero clearance required   Sides     : Zero clearance if using bottom cable access          (Standard knockouts for left/right side            cable access )   Base     : Channel mounted 
                    
                    Streszczenie treści zawartej na stronie nr. 8 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply     Current THD    : <3% THD at 60%–100% load          <6% THD at 25%–59% load        (No input harmonic filter required)    4.1.3  Charging Function:   DC Nominal Voltage   : 480 V   AC Ripple on DC Bus  : < 0.2% of DC Voltage   DC Voltage Range   : 400 V to 545 V   DC Float Charging Voltage  : 545 V   Maximum charging current:      80 kVA   : 20 A      100 kVA   : 25 A      160 kVA   : 40 A      225 kVA   : 56 A   AC Ripple on D
                    
                    Streszczenie treści zawartej na stronie nr. 9 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply     Harmonic Voltage Distortion  : < 2% THD (100% Linear Load)        : < 5% THD (100% Non-linear Load)   Phase Displacement    : 1° Maximum at 100% load   Voltage Transients:     100% Load Step Change : +/-2% Maximum (Without battery assistance)    Loss or Return of Input  : +/-1% Maximum    Transfer from Bypass  to Inverter    : +/-5% Maximum     (At Bypass Rated Voltage)    Recovery Time  : 1 cycle     5 FUNCTIONAL DESCRIPTION 
                    
                    Streszczenie treści zawartej na stronie nr. 10 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply    5.2.3  Battery Protection  The converter shall be provided with monitoring and control circuits to protect the battery  system from damage due to excessive discharge. Converter shutdown shall be initiated  when the battery voltage reaches a discharge cutoff voltage of 400 VDC.  Automatic  shutdown based on discharge time is not acceptable.    5.2.4 DC Ripple  AC Ripple on the DC Bus shall be less than 0.2%.  AC Ripple on the Ba
                    
                    Streszczenie treści zawartej na stronie nr. 11 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply    5.3.5  Overload Capacity:  The Inverter output shall be capable of providing an overload current of 125% for 2 min.  and 150% for 1 min.  A message on the control panel shall indicate this condition.  If the  time limit associated with the overload condition expires, or the overload is in excess of  the set current limit, the load power shall transfer to the bypass source without  interruption.    5.4 Static Bypass Circuit:    
                    
                    Streszczenie treści zawartej na stronie nr. 12 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      If the bypass source is beyond the conditions stated below, interrupted transfer shall be  made upon detection of a fault condition.   Bypass voltage greater than + 10%, -10% from the UPS rated output voltage.   Bypass frequency greater than + 1 Hz from the UPS rated output frequency.    5.4.2 Overload Capacity in Bypass:   Continuous duty  : 125% of the system rated capacity   Overload duty   : 1000% of ampere rating for 1 c
                    
                    Streszczenie treści zawartej na stronie nr. 13 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      5.5.4 Mimic Panel  A one-line diagram of the system shall be displayed on the touch panel display panel to  provide a visual status of contactors within UPS.  The panel shall display the followings:  AC Input, DC Input  Rectifier in Operation  Inverter in Operation  UPS/Bypass supply  Battery Operating Condition (float charge/discharge)  Fault, Warning  Operation Guidance (LCD Display)  Fault Guidance (LCD Display)    5.5.5 I
                    
                    Streszczenie treści zawartej na stronie nr. 14 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply    6 MECHANICAL DESIGN    6.1 UPS Enclosure  The UPS shall be a freestanding NEMA1 enclosure equipped with a leveling channel base. The  enclosure shall include provisions for hoisting, jacking, and forklift handling.    6.2 Cable Access   Cable access to the UPS shall be    Bottom entry   Side entry,   Top entry with when using optional side cabinet    7 WARRANTY     7.1 UPS Warranty  The UPS shall come with a 36-month warranty o
                    
                    Streszczenie treści zawartej na stronie nr. 15 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply    9.1.2 HTTP Familiarity  The RemotEye II shall provide a HTTP interface for the UPS to allow easy access of the UPS  information from any machine with a web browser. At any time, a network workstation or  management station shall be able to open a RemotEye II website. RemotEye II website shall  enable the UPS system information to be configured and monitored remotely. RemotEye II  shall provide access to 3 java applets for monit
                    
                    Streszczenie treści zawartej na stronie nr. 16 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply    10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION)    The manufacturer can optionally provide a matching TDC for the UPS.   The TDC can include a step-down, 480/208/120 V transformer in a matching NEMA1  cabinet.   The TDC can include a three-breaker MBS with a slidebar interlock.  Interlock keys and  Solenoid Key-Retractable Unit (SKRU) can be provided.   The TDC can include up to eight 225 A sub-feed breakers.   The TDC can includ
                    
                    Streszczenie treści zawartej na stronie nr. 17 
                    
                        Guide Specification – 3-Phase Static Uninterruptible Power Supply      14 EXTENDED SERVICES (OPTION)    The UPS manufacturer can offer  :   Startup Service   Maintenance Contracts (Silver, Gold, Platinum)   Preventive Maintenance Contracts   Spare-parts kits (A, B, and C level)   Extended warranty coverage  for up to an additional 5 years   Enhanced warranty contract (24/7 + Holiday coverage)   Load bank testing   Factory witness testing   Site monitor and power audits        17