Streszczenie treści zawartej na stronie nr. 1 
                    
                        DO NOT
DISCARD
Owner’s Manual
Installation and Operation
Models:    
SL-750TRS-IPI-E
SL-550TRS-IPI-E
SL-350TRS-D
SL-350TRS-IPI
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating • Read, understand and follow • Leave this manual with 
and maintenance these instructions for safe 
party responsible for use 
instructions included. installation and operation.
and operation.
WARNING
WARNING: If the information in these 
HOT! DO NOT TOUCH. 
instructions is not followed exactly, a fi re 
SEVERE BUR
                    
                    Streszczenie treści zawartej na stronie nr. 2 
                    
                        Read this manual before installing or operating this appliance.  Please retain this owner’s manual for future reference. Congratulations Congratulations on selecting a Heat & Glo gas appliance This Owner’s Manual should be retained for future  —an elegant and clean alternative to wood burning reference. We suggest that you keep it with your other  important documents and product manuals. appliances. The Heat & Glo gas appliance you have  selected is designed to provide the utmost in safety,  The
                    
                    Streszczenie treści zawartej na stronie nr. 3 
                    
                        Table of Contents 1 Listing and Code Approvals  9 Gas Information   A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 A. Fuel Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 B. Glass Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 B. Gas Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 C. G
                    
                    Streszczenie treści zawartej na stronie nr. 4 
                    
                        Listing and Code Approvals   1 1   A. Appliance Certifi cation C. BTU Specifi cations Models Maximum Minimum Orifi ce    MODELS:  SL-750TRS-IPI-E,SL-550TRS-IPI-E, U.S. (0-2000 ft.) or Input Input Size       SL-350TRS-D, SL-350TRS-IPI Canada (2000-4500 ft.) BTU/h BTU/h (DMS) LABORATORY:  Underwriters Laboratories, Inc. (UL) U.S. 30,800 20,200 #37 SL-750TRS-IPI-E (NG) TYPE: Direct Vent Gas Appliance Heater Canada 27,720 18,180 #38 U.S. 30,700 23.300 #52 STANDARD: ANSI Z21.88a-2007 • CSA 2.33a-2007  S
                    
                    Streszczenie treści zawartej na stronie nr. 5 
                    
                        Inspection Note: The following requirements reference various  The state or local gas inspector of the side wall horizon- Massachusetts and national codes not contained in this  tally vented gas fueled equipment shall not approve the  document. installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed  G. Requirements for the Commonwealth of  in accordance with the provisions of 248 CMR 5.08(2)(a)1  Massachusetts through 4.  For all side wall 
                    
                    Streszczenie treści zawartej na stronie nr. 6 
                    
                        Getting Started   2 2  A. Design and Installation Considerations C. Inspect Appliance and Components Heat & Glo direct vent gas appliances are designed to  operate with all combustion air siphoned from outside of  WARNING the building and all exhaust gases expelled to the out- Inspect appliance and components for damage.  side. No additional outside air source is required. Damaged parts may impair safe operation. • Do NOT install damaged components. • Do NOT install incomplete components. CAUTIO
                    
                    Streszczenie treści zawartej na stronie nr. 7 
                    
                        Framing and Clearances   3 3   Note: WARNING • Illustrations reflect typical installations and are FOR  Fire Risk DESIGN PURPOSES ONLY. Provide adequate clearance: • Illustrations/diagrams are not drawn to scale. • Around air openings • Actual installation may vary due to individual design  preference. • To combustibles • For service access A. Selecting Appliance Location Locate appliance away from traffi c areas. When selecting a location for your appliance it is important to  NOTE:   For actual
                    
                    Streszczenie treści zawartej na stronie nr. 8 
                    
                        insulation. If the appliance is being installed on a cement  B. Constructing the Appliance Chase slab, a layer of plywood may be placed underneath to pre- A chase is a vertical boxlike structure built to enclose the  vent conducting cold up into the room. gas appliance and/or its vent system. Vertical vents that  run on the outside of a building may be, but are not re- C. Clearances quired to be, installed inside a chase. Construction of the chase may vary with the type of build- WARNING ing. Th
                    
                    Streszczenie treści zawartej na stronie nr. 9 
                    
                        D. Elevated Hearth Systems Use the table below to identify the hearth system that will be used.  The table will also help identify effects on the various dimensions.   Some hearth systems will elevate the appliance off the fl oor at a given dimension.  For example, if appliance will be used with a  Kenwood Cabinet with Base, the appliance will be elevated 9-1/4 inches.  The 9-1/4 inch elevation will also have to be added to the  following:  Extension Wall Hole referenced in Figure 6.3 (Exterior W
                    
                    Streszczenie treści zawartej na stronie nr. 10 
                    
                        E. Mantel Projections All measurements are in inches. CEILING 1/2 IN.  MINIMUM 12 11 10 9 2-7/8 IN.  8 7 32 MINIMUM 3 FT. MAXIMUM 6 5 Note: Clearance from opening  13 4 12 to perpendicular wall. 11 3 10 9 8 7 6 5 4 Figure 3.5 Clearances to Mantel Legs or Wall Projections    (Acceptable on both sides of opening.) TOP OF HOOD OR FIREPLACE OPENING Figure 3.3 Clearances to mantels or other combustibles  above appliance 1/2 in. SHEETROCK 3-1/2 in. NON-COMBUSTIBLE 3 IN.  BOARD SHIPPED  MINIMUM WITH AP
                    
                    Streszczenie treści zawartej na stronie nr. 11 
                    
                        Termination Locations   4 4   HORIZONTAL A. Vent Termination Minimum Clearances OVERHANG 2 FT. 20 INCHES MIN. WARNING VERTICAL MIN. WALL LOWEST Fire Risk. DISCHARGE OPENING Explosion Risk. GAS DIRECT VENT  TERMINATION CAP Maintain vent clearance to combustibles as  specifi ed. X 12 • Do not pack air space with insulation or other  materials. ROOF PITCH IS  X/ 12 Failure to keep insulation or other materials  away from vent pipe may cause fi re. H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHAR
                    
                    Streszczenie treści zawartej na stronie nr. 12 
                    
                        M N P R Q (See Note 2) V T S S Electrical V V Service D* V = VENT  TERMINAL X V = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTED A  = 12 inches.................clearances above grade, veranda,  L** = 7 ft. ......................... clearance above paved  (See Note 1) (See Note 1) porch, deck or balcony sidewalk or a paved driveway  located on public property B = 12 inches.................clearances to window or door  M*** = 18 inches................ clearance under veranda, porch,  that
                    
                    Streszczenie treści zawartej na stronie nr. 13 
                    
                        Vent Information and Diagrams   5 5  A. Vent Table Key The abbreviations listed in this vent table key are used in  the vent diagrams. Symbol Description Vertical First section (closest to appliance) of vertical length V1 Second section of vertical length V2 First section (closest to appliance) of horizontal length H1 8-1/2 in. Second section of horizontal length H2 WARNING Horizontal Fire Hazard. Explosion Risk. Figure 5.1 Asphyxiation Risk. Do NOT connect this gas appliance to a chimney  fl ue 
                    
                    Streszczenie treści zawartej na stronie nr. 14 
                    
                        D. Use of Flex Vent The fl ex vent must be supported with  TERMINATION the spacing between support intervals  CAP 3in. CLEARANCE not exceeding 4 feet, with no more  than ½ inch sag between supports. A support is required at each change  in venting direction, and in any location  where it is necessary to maintain the  necessary clearance to combustibles.  FLEX-VENT A simple “up and out” installation (Fig- ure 5.3) requires only enough support  to maintain the necessary clearance  1in. to combustib
                    
                    Streszczenie treści zawartej na stronie nr. 15 
                    
                        E. Vent Diagrams WARNING Fire Risk.   Explosion Risk. Do NOT pack insulation or other combustibles between ceiling fi restops. • ALWAYS maintain specifi ed clearances around venting and fi restop systems. • Install wall shield and ceiling fi restops as specifi ed. Failure to keep insulation or other material away from vent pipe may cause fi re. 1.  Top Vent - Horizontal Termination Venting H Maximum 1 V Minimum One Elbow SL-350TRS-D SL-550, SL-750TRS-E 90º Elbow 1-1/2 ft. 457 mm 1 ft. 305 mm Note: Use
                    
                    Streszczenie treści zawartej na stronie nr. 16 
                    
                        Two Elbows H Maximum V Minimum Note: Use SL-D Series  SL-350TRS-D, SL-550TRS-E, SL-750TRS-E components only. 90º Elbow NOT ALLOWED 1/2 ft. 152 mm 1 ft. 305 mm 1-1/2 ft. 457 mm 2 ft. 610 mm Note: There MUST be a 25%  reduction in total H when using  2-1/2 ft. 762 mm 4 ft. 1.2 m fl ex vent except when using the  3-1/2 ft. 1.1 m 6 ft 1.8 m simple up and out installation  4-1/2 ft. 1.4 m 14 ft. 4.3 m (see Figure 5.3). H + H Maximum= 14 ft. (4.3 m) 1 2 V + H + H Maximum= 40 ft. (12.2 m) 1 1 2 WARNING 
                    
                    Streszczenie treści zawartej na stronie nr. 17 
                    
                        1.  Top Vent - Horizontal Termination  - (continued) H Maximum H + H Maximum H Maximum H + H Maximum 1 1 2 1 1 2 V Minimum Three Elbows 1 Model: SL-350TRS-D Models: SL-550TRS-IPI-E, SL-750TRS-IPI-E Elbow only 1-1/2 ft. 457 mm 2 ft. 610 mm 1 ft. 305 mm 2 ft. 610 mm 1/2 ft. 152 mm 2 ft. 610 mm 4 ft. 1.2 m 2 ft. 610 mm 4 ft. 1.2 m 1-1/2 ft. 457 mm 3 ft. 914 mm 6 ft. 1.8 m 3 ft. 914 mm 6 ft. 1.8 m 2-1/2 ft. 762 mm 5 ft. 1.5 m 10 ft 3.0 m 5 ft. 1.5 m 10 ft. 3.0 m 3-1/2 ft. 1.1 m 7 ft. 2.1 m 14 ft. 4.
                    
                    Streszczenie treści zawartej na stronie nr. 18 
                    
                        Exhaust restrictor Instructions 2.  Top Vent - Vertical Termination 1. Install the exhaust restrictor over the center of the ex- haust outlet in the fi rebox (see Figure 5.8). No Elbow 2. Center the exhaust restrictor in the open end of the  exhaust outlet and secure through the slots on the ex- Note: Use SL-D Series  haust restrictor with the 2-1/4 in. self tapping screws  components only. provided in the appliance manual bag. Note: If installing a vertical vent/termination off the top of  the a
                    
                    Streszczenie treści zawartej na stronie nr. 19 
                    
                        2.  Top Vent - Vertical Termination  - (continued) Two 90º Elbows H Maximum H Maximum V V + V Minimum 1 1 2 1 2  V Minimum 1  SL-350TRS-D SL-550TRS-E, SL-750TRS-E * * 90º Elbow 1-1/2 ft. 457 mm 1 ft. 305 mm * * 1/2 ft. 152 mm 2 ft. 610 mm 2 ft. 610 mm * * 1 ft. 305 mm 2-1/2 ft. 762 mm 2-1/2 ft. 762 mm * * 2 ft. 610 mm 4 ft. 1.2 m 4 ft. 1.2 m * * 3 ft. 914 m 6 ft. 1.8 m 6 ft. 1.8 m * * 4 ft. 1.2 m 8 ft. 2.4 m 8 ft. 2.4 m * * 5 ft. 1.5 m 15 ft. 4.6 m 15 ft 4.6 m * * H Maximum= 15 ft. (4.6 m) 1 V +
                    
                    Streszczenie treści zawartej na stronie nr. 20 
                    
                        2.  Top Vent - Vertical Termination  - (continued) Three 90º Elbows ALL MODELS Note: Use SL-D Series V H + H Maximum V V + V Minimum  1 1 2  2 1 2   components only. 90º Elbow 0 0 1-1/2 ft. 457 mm 1-1/2 ft. 457 mm 1/2 ft.. 152 mm 1 ft. 305 mm * * * *  Note: There MUST be a 25%  1-1/2 ft. 457 mm 2 ft. 610 mm * * * * reduction in total H when using  2-1/2 ft. 762 mm 4 ft. 1.2 m * * * * fl ex vent except when using the  simple up and out installation  3-1/2 ft. 1.1 m 6 ft. 1.8 m * * * * (see Figure