Краткое содержание страницы № 1 
                    
                        GOLD CGs
Gas-Fired Water Boilers
• Installation • Maintenance
Boiler Manual
• Startup • Parts
	 This	 manual	 must	 only	 be	 used	 by	 a	 qualified	 heating	 installer/service	 technician.	 Before	 installing,	 read	 all	
instructions,	 including	 this	 manual,	 the	 burner	 manual	 and	 any	 related	 supplements.	 Perform	 steps	 in	 the	 order	
given.	Failuret 	 oc 	 omplyc 	 ould	result	in	severe	personalinj 	 ury, 	deatho 	 r	substantialp 	 ropertydamag 	 e.	
	 DO NOT USE BOILER DURING CONS
                    
                    Краткое содержание страницы № 2 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual How it works . . . 	 Control	module ① The	 control	 module	 responds	 to	 signals	 from	 the	 room	 thermostat,	 air	 pressure	 switch	 and	 boiler	 limit	 circuit	 to	 operate	 the	 boiler	 circulator,	 pilot	 burner,	 gas	 valve	 and	 inducer.	 When	 roomthe 	 rmostat	callsf 	 or	heat, the 	 c 	 ontrol	module	startsthe 	 	system	circulatorand 	 	inducer. The	 control	 module	 runs	 the	 inducer	 long	 enough	 to	 purge	 the	 boiler	 flue	 passage
                    
                    Краткое содержание страницы № 3 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual GOLD CGs Gas-Fired Induced-Draft Water Boiler 3 Part number 550-110-260/0107                                                                                                                                                                                                                                                                                                                                                                                        
                    
                    Краткое содержание страницы № 4 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual Contents 	 Howit 	 	works 	 ....................................................2–3 	 Hazard	definitions 	 ............................................... 4 	 Please	read	before	proceeding 	............................ 5 		1	 Prepare	boiler	location 	 ...................................6–11 		2	 Prepare	boiler 	...............................................12–13 		3	 Water	piping 	 .................................................14–23 		4	 Ventin
                    
                    Краткое содержание страницы № 5 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual Please read before proceeding Installer User •	 This manual is for use only by your qualified  	 Read all instructions before in- heating installer/service technician. stalling.	 Follow	 all	 instructions	 in	 •	 Please	 refer	 to	 the	 User’s Information Manual	 for	 proper	 order	 to	 prevent	 personal	 your	reference. injuryo 	 r	death. •	 We 	 recommend	 regular	 service by a qualified  •	 Alsor 	 efer	toCGs 	 	 Venting Supplements. service tec
                    
                    Краткое содержание страницы № 6 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1a Prepare boiler location — codes & checklist Installations	must	followthese 	 	codes: •	 Local, 	state, 	provincial, 	andnat 	 ional	codes, 	la ws,r 	 egulations	and	ordinances. •	 National	Fuel	Gas	Code, 	 ANSIZ 	 3.1–latest	edition. •	 Standard	 for	 Controls	 and	 Safety	 Devices	 for	 Automatically	 Fired	 Boilers,	 ANSI/ ASME	CSD-1, w 	 hen	required. •	 National	Electrical	Code. •	 For 	 Canada	 only:	 B149.1	 or	 B149.	 Installation	 Cod
                    
                    Краткое содержание страницы № 7 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1b Prepare boiler location — clearances Recommended	SERVICE	clearances	 Figure 2 Required MINIMUM clearances (Fig. 1) 1.	 Provide	 clearances	 for	 cleaning	 and	 servicing	 the	 boiler	 and	 for	 access	 to	 controls	 and	 components.	 See	 Figure1 	 	 for	 recommenda- tions. .  	 Provide	 at	 least	 screwdriver	 clearance	 to	 jacket	 front	 panel	 screws	 for	 removal	 of	 front	 panel	 for	 inspection	 and	 minor	 service.	 If	 unable	 to	 pro
                    
                    Краткое содержание страницы № 8 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1c Prepare boiler location — vent system 	 Failure	 to	 follow	 all	 instructions	 can	 result	 in	 flue	 gas	 spillage	 and	 carbon	 monoxide	 emissions,	 causing	 severe	 personal	injury	ord 	 eath. 	 Inspect	 existing	 chimney	 before	 installing	 boiler.	 Failure	 to	 clean	 or	 replace	 perforated	 pipe	 or	 tile	 lining	 will	 cause	 severe	personal	injury	or	death. 	 DO	 NOT	 COMMON	 VENT	 —	 Do	 not	 install	 the	 CGs	 into	 a	 common	 vent
                    
                    Краткое содержание страницы № 9 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1d Prepare boiler location — contamination Please	 review	 the	 following	 information	 on	 potential	 Refer	 to	 Table 1	 for	 products	 and	 areas	 which	 may	 cause	 combustionair 	 c 	 ontamination	problems. contaminated	combustionair 	 . 	 To	 prevent	 potential	 of	 severe	 personal	 injury	 or	 death,	 check	 for	 products	 or	 areas	 listed	 below	beforeinstal 	 ling	boiler. 	If 	anyo 	 f 	thesec 	 ontaminants	are	found: •	 removec 	 ontami
                    
                    Краткое содержание страницы № 10 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 1e Prepare boiler location — air openings mended	 in	 Figure	 3	 will	 allow	 adequate	 ventilation	 and	 	 Combustion air opening location and sizing  combustion	 air	 provided	 the	 boiler	 room	 is	 not	 sub- requirements depend on the clearances around  jected	 to	 negative	 pressure	 due	 to	 exhaust	 fans	 or	 other	 the boiler.	 Check	 the	 boiler	 placement	 compared	 to	 mechanical	 ventilation	 devices.	 Refer	 to	 the	 National	 Figure1,
                    
                    Краткое содержание страницы № 11 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual Figure 3 Sizing air openings for CGs installations ✷ 11 Part number 550-110-260/0107                                                                                                                                                                                                                                                                                                                                                                                
                    
                    Краткое содержание страницы № 12 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 2a Prepare	 boiler	 —	 placement	 &	 setup 	 Inlet	 air	 box	 top	 panel	 must	 be	 in	 Place	boiler/crate	near 	 position	 during	 boiler	 operation.	 position Failure	 to	 do	 so	 could	 result	 in	 severe	 personal	 injury,	 death	 or	 1.	 Leave	 boiler	 in	 crate	 and	 on	 pallet	 until	 installation	 substantial	propertydamag 	 e. site	is	ready. .	 Move	 entire	 crate	 and	 pallet	 next	 to	 selected	 loca- tion. 3.	 Remove	crate. Orifice	 re
                    
                    Краткое содержание страницы № 13 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 2b Prepare	boiler	—	pressure	test 5.	 Slowly	 reopen	 boiler	 drain	 valve	 until	 test	 pressure	 Hydrostatic	pressuretest 	 on	 the	 pressure/temperature	 gauge	 reaches	 no	 more	 Pressure	 test	 boiler	 before attaching	 water	 or	 gas	 piping	 than: (except	as	noted	below)	or	electrical	supply. •	 45 psigf 	 orb 	 oilersw 	 ith	 30 psig relief valve. Prepareboiler 	 for 	 	test •	 75 psig	for	boilersw 	 ith	 50 psig relief valve. 1.	 Remove	 t
                    
                    Краткое содержание страницы № 14 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3a Water piping — general information Generalpiping 	 information 	 Circulator If	 installation	 is	 to	 comply	 with	 ASME	 or	 Canadian	 requirements,	 an	 ad- The	 circulator	 is	 shipped	 loose	 (wiring	 pre-attached	 to	 ditional	 high temperature limit	 is	 needed.	 Install	 control	 in	 supply	 piping	 boiler)	 to	 allow	 you	 to	 locate	 it	 either	 in	 the	 return	 or	 between	 boiler	 and	 isolation	 valve.	 Set	 second	 control	 to	 mini
                    
                    Краткое содержание страницы № 15 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3b Water piping — single-zone system Diaphragm-typeor 	 	bladder- Closed-type	expansion	tank 	 type	expansion	tank 	(Figure	4) (Figure	5) 1.	 Ensure	 expansion	 tank	 size	 will	 handle	 boiler	 and	 1.	 Ensure	 expansion	 tank	 size	 will	 handle	 boiler	 and	 system	 water	 volume	 and	 temperature.	 Tank	 must	 system	 water	 volume	 and	 temperature.	 See	 tank	 be	 located	 in	 boiler	 return	 piping	 as	 close	 to	 boiler	 manufacturer’s	inst
                    
                    Краткое содержание страницы № 16 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3c Water piping — multiple zones Piping	multiple	zones Piping	forradiant 	 heating 	 	 Follow	 instructions	 on	 pages	 14	 and	 15	 to	 install	 near- systemsor 	 converted 	 gravity 	 	 boiler	 or	 single-zone	 piping.	 (Also	 refer	 to	 Piping for  systems radiant heating systems or converted gravity sys- tems,b 	 elow, if 	 ap 	 plicable.) Converted	gravity	(or	steam)systems 	 See	 Figure 6	 or	 Figure 7,	 page1 	 ,  	 to	 complete	 instal- Wh
                    
                    Краткое содержание страницы № 17 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3c Water piping — multiple zones (continued) Figure 6 Zoning with circulators Figure 7 Zoning with zone valves  — return water 130°F or higher. — return water 130°F or higher. 1	 Boiler 	 isolation	 (balancing)	 10	Automatic	 air	 vent	 (with	 diaphragm-type	 expansion	 tank),	 or	 connect	 valves to	 tank	 fitting	 (closed-type	 expansion	 tank).	 DO NOT	 use	 an	 automatic	 air	 vent	 when	 using	 closed-type	 expansion	 tank.	 It	 would	 allow	 
                    
                    Краткое содержание страницы № 18 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems the	 water	 temperature	 being	 supplied	 to	 the	 radiant	 Primary/secondary	 (preferred)	 tubing. bypass	piping	method Gauge	 8	 is	 required	 on	 all	 systems	 to	 assure	 the	 return	 Primary/secondary bypass	 piping	 is	 preferred	 because	 water	 temperature	 is	 accurately	 set	 for	 a	 minimum	 of	 the	 flow	 rate	 and	 temperature	 drop	 in	 the	 heating	 130°F.	 If	 this	 gauge	 is	 not	 available	 however,	 a
                    
                    Краткое содержание страницы № 19 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems (continued) Figure 8 Primary/secondary piping Figure 9 Primary/secondary piping  Zoning with circulators Zoning with zone valves   9	Relief v 	 alve 1	 Boiler	isolation	(balancing)	valves 10	Automatic 	 air	 vent	 (with	 diaphragm-type	 expansion	 tank),	 or	 2	 Flow/check	valve connect	 to	 tank	 fitting	 (closed-type	 expansion	 tank).	 DO NOT	 use	 an	 automatic	 air	 vent	 when	 using	 closed-type	 expansion	 3	 Sys
                    
                    Краткое содержание страницы № 20 
                    
                        GOLD CGs Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems (continued) justed	 using	 cold	 (or	 room	 temperature)	 return	 water	 BOILER-bypasspiping 	 	 to	 the	 boiler.	 (When	 setting	 the	 valves	 without	 gauge	 method 4a	 installed	 —	 using	 cold	 or	 room	 temperature	 water	 —	 assume	 the	 return	 water	 temperature	 to	 be	 60°F.	 Set	 This	 piping	 method	 (Figures 10	 and	 11,	 page	 1)	 is	 thev 	 alves	so	gauge	 8	reads	at	least	10°F. called	 a	 boiler-bypass