                        Installation
Operation
Service Manual
for
Forced Draft Steam
Boilers
BRYAN BOILERS
783 N. CHILI AVENUE, PERU, INDIANA  46970
Telephone: 765-473-6651  /  Fax: 765-473-3074
E-Mail: bryanboilers@iquest.net / Internet: www.bryanboilers.com                                                                                                                                                                                                                                                                         
                    
                    Краткое содержание страницы № 2 
                    
                                          INSTALLATION INSTRUCTIONS   FORCED DRAFT   STEAM BOILERS                                                                                                                                              NOTE:  • Please read all of instruction manual before attempting installation.  • Insurance and local or state regulatory codes may contain additional or more stringent requirements  than those contained in this manual. Installation must conform to these codes and any other  authorit
                    
                    Краткое содержание страницы № 3 
                    
                                        MINIMUM CLEARANCES    NOTE: These boilers are intended to be installed in a room which is large compared to the size of  the boiler. They are not intended for alcove installation and are suitable for installation on non- combustible flooring only.         1  D-SERIES F-SERIES CL-SERIES K-SERIES RV, RW & AB SERIES      DIMENSION   WATER/ STEAM WATER STEAM WATER STEAM WATER STEAM WATER STEAM  STEAM OVER /STEAM OVER /STEAM OVER /STEAM OVER /STEAM OVER  TO 50# 50# TO 50# 50# TO 50# 5
                    
                    Краткое содержание страницы № 4 
                    
                                          1.4 BOILER CONNECTIONS     1.4.1 GENERAL tank. This valve can then be adjusted to  Do not run any pipes along the access panel bypass excess pump capacity to better  side of the boiler. Maintain clearances as control the boiler feed rate.  shown on the dimensional drawing for   servicing of the boiler tubes. Provide at least 1.4.4 SAFETY RELIEF VALVE(S)  36" from the gas train and burner, unless a A connection is provided in the top of the  larger dimension is indicated on the 
                    
                    Краткое содержание страницы № 5 
                    
                                         1.5 GAS SUPPLY CONNECTION - FORCED DRAFT UNITS    The installation must conform completely to the Drip leg must be installed on gas supply piping.  requirements of the authority having jurisdiction,   or in the absence of such, requirements shall Consult the local gas utility company for  conform in the U.S. to the current National Fuel inspection and authorization of all gas supply  Gas Code, ANSI Z223.1-1984, or in Canada to piping and flue connections.  the current Installati
                    
                    Краткое содержание страницы № 6 
                    
                                         1.6 ELECTRICAL CONNECTION    IMPORTANT: All electrical connections must details.  conform to the National Electrical Code and to all   other applicable State and Local Codes. Forced Equipment Grounding - The boiler must be  draft boilers may require a high voltage grounded in accordance with the American  connection. See boiler wiring diagram and National Standard Electrical Code, ANSI/NFPA  equipment list for  #70-1981.  1.7 COMBUSTION AIR SUPPLY    IMPORTANT: Positive means fo
                    
                    Краткое содержание страницы № 7 
                    
                                       Ventilation Air: In addition to air needed for disposal. The boiler room and the combustion air  combustion, sufficient air must be supplied for supply must not be exposed to the fumes. Such  ventilation, including air required for comfort and fumes include, but are not limited to, carbon  proper working conditions for personnel in the monoxide, hydrogen sulfide, ammonia, chlorine,  boiler room. In colder climates, provision should and halogenated hydrocarbons.  also be made to he
                    
                    Краткое содержание страницы № 8 
                    
                                                                     FIG. 1.8.1: VENT DESIGN INSTRUCTION -    REFERENCES      TABLE 1.8.1A: ESTIMATING FLUE GAS VOLUMETRIC FLOW RATE    Approximate Flue Gas VOLUMETRIC FLOW RATE   (Per 1000 Btu/hr Input)  (Multiply factor listed times boiler input in MBH)   SCFM Per ACFM Per APPROXIMATE  BOILER TYPE  1000 Btu/hr 1000 Btu/hr FLUE GAS  INPUT INPUT TEMPERATURE  Water & 15# Steam     Gas Fired 0.230 0.402 450F       Oil Fired 0.230 0.402 450F  150# Steam     Gas Fired 0.230
                    
                    Краткое содержание страницы № 9 
                    
                                            TABLE 1.8.1C: ESTIMATING FLUE GAS EMISSIONS    Estimated Emissions (Volumetric Flow Rate Per Million Btu/hr Input)  (Multiply PPH listed times boiler input divided by 1,000,000)  PARTICULATES NOx CO SOx Hydrocarbons  BOILER  TYPE   PPH per PPM PPH per PPM PPH per PPM PPH per PPM PPH per PPM  MMBH MMBH MMBH MMBH MMBH  Gas Fired  N/A N/A 0.049 50 0.194 200 N/A N/A 0.010 10              Oil Fired 0.020 20 0.068 70 0.018 18 0.286 290 0.004 4      1.8.2 CLEARANCES    The vent syst
                    
                    Краткое содержание страницы № 10 
                    
                                                                                                                                                                                     1.8.7 ACCEPTABLE VENT TYPES    LISTED GAS VENTS installed in accordance with nationally recognized  Listed gas vents must be applied only on those building codes or standards.  applications for which they are listed. Type B gas   vents are NOT listed for use on forced draft MASONRY CHIMNEYS FOR RESIDENTIAL  appliance vent systems. APPLICATIO
                    
                    Краткое содержание страницы № 11 
                    
                                       1.8.5 VENT CONNECTORS (HORIZONTAL RUNS)    CONSTRUCTION Supports should usually be overhead hangers, of  Vent connectors may be of any of the acceptable load bearing capacity appropriate for the weight  constructions listed in this manual. involved.     AVOID UNNECESSARY BENDS LOCATION  The vent connector must be installed so as to When the vent connector used for an appliance  avoid turns or other construction features which having a draft hood must be located in or pass  create 
                    
                    Краткое содержание страницы № 12 
                    
                                       1.8.6 CHIMNEY & VENT CONSTRUCTION (VERTICAL SECTION)    INSTALLATION OF FACTORY BUILT Alternatively, a non-ventilating thimble not less  SYSTEMS than 18" above and 6" below the roof (with the  Listed gas vents and factory built chimneys must annular space open at the bottom and closed at  be installed in accordance with their listings and the top) may be used.  the manufacturer's instructions. Vents and   venting systems passing through roofs must INSPECTIONS OF CHIMNEYS  extend t
                    
                    Краткое содержание страницы № 13 
                    
                                         1.8.7 MARKING OF GAS VENTS    In those localities where solid and liquid fuels are The authority having jurisdiction must determine  used extensively, gas vents must be plainly and whether their area constitutes such a locality.  permanently identified by a label reading:   "This gas vent is for appliances which  burn gas only. Do not connect to  incinerators or solid or liquid fuel burning  appliances."    This label must be attached to the wall or ceiling  at a point near wher
                    
                    Краткое содержание страницы № 14 
                    
                                       PROTECTION AGAINST BLOCKAGE OR Listed gas vents must be terminated with a listed  OBSTRUCTION cap, approved for use with the particular gas  The chimney or vent exit design must prevent any vent.  possibility of blockage by snow or any other   obstruction. Listed vent caps or roof assemblies must have a   rated venting capacity no less than the vent.  VENTILATING HOODS AND EXHAUST   SYSTEMS Single wall vents must terminate in an approved  Ventilating hoods or exhaust systems may b
                    
                    Краткое содержание страницы № 15 
                    
                                       AUTOMATIC VENT DAMPERS MUST BE PERFORMANCE TEST  INSTALLED ONLY BY QUALIFIED SERVICE The automatic vent damper must be tested after  TECHNICIANS. FAILURE TO PROPERLY installation to assure its proper and safe  INSTALL A VENT DAMPER WILL CREATE A operation.  SEVERE HAZARD.    AUTOMATIC VENT DAMPERS MUST BE IN   THE OPEN POSITION AT ANY TIME THE   APPLIANCE MAIN GAS VALVE IS ENERGIZED.    1.8.14 SIZING OF CHIMNEY AND VENT    IMPORTANT the gas input. Consult the factory or the local 
                    
                    Краткое содержание страницы № 16 
                    
                                       be done with 45 elbows and not by provide a relatively constant flue gas velocity  "bullheading" directly into the vent connector at through the vent system. Using a constant  90 angles. "Bullhead" connections generally diameter breeching will often result in poor draft  cause excessive turbulence and poor draft at the outermost appliances.  conditions. On vent connectors serving multiple    appliances, the diameter of the piping should be  increased at each appliance's entrance
                    
                    Краткое содержание страницы № 17 
                    
                                       Table 1.8.15B ALTITUDE CORRECTION FACTOR, F  2 (Multiple factor times sea level input, MBH)  Altitude (ft) Factor, F Altitude (ft) Factor, F  2 2 0 to 1999 1.00    2000 1.075 6000 1.247  2500 1.096 6500 1.272  3000 1.116 7000 1.296  3500 1.136 7500 1.322  4000 1.157 8000 1.346  4500 1.180 8500 1.373  5000 1.202 9000 1.399  5500 1.25 10000 1.453    STEP 3: SELECT TRIAL DIAMETER STEP 4: CALCULATE SYSTEM K-FACTOR  Determine the NET STACK HEIGHT for the vent. The system "k-factor" acc
                    
                    Краткое содержание страницы № 18 
                    
                                       STEP 5: CORRECT EQUIVALENT INPUT FOR   SYSTEM K-FACTOR Multiply the equivalent input calculated in Step 2  The capacities listed in Table 1.8.15C are based times factor F from Table 1.8.15E. This step will  3 on a system k-factor equal to 7.5. For any other yield a new equivalent input, I:  k-factor, the vent capacity must be adjusted. This  I = MBH x F x F x F eq. 15E  1 2 3 is accomplished by adjusting the equivalent input   for the system using a k-factor correction factor, Usi
                    
                    Краткое содержание страницы № 19 
                    
                                         Stack Table 1.8.15C: Approximate Stack Capacities (MBH)  Diam. (Based on Atmospheric Boiler with Draft Hood)  (in.)   5 7 10 12 15 20 25 30 35 40 45 50 60 70 80 90 100 125 150 200  6 100 120 140 150 170 200 220 250 270 280 300 320 350 380 400 430 450 510 550 640  7 130 160 190 210 240 270 310 340 360 390 410 430 480 510 550 580 620 690 760 870  8 180 210 250 280 310 360 400 440 480 510 540 570 620 670 720 760 810 900 990 1140  9 220 270 320 350 390 450 510 560 600 640 680 720 79
                    
                    Краткое содержание страницы № 20 
                    
                                          Table 1.8.15F: CIRCULAR EQUIVALENTS OF RECTANGULAR BREECHINGS & STACKS    WIDTH HEIGHT (INCHES)  (INCHES)   6 8 10 12 14 16 18 20 22 24 26 28 30 36 42 48 54 60  6 7 8 8 9 10 10 11 11 12 12 13 13 14 15 16 17 17 18  8 8 9 10 11 11 12 13 13 14 15 15 16 16 15 19 20 21 21  10 8 10 11 12 13 14 15 15 16 17 17 18 18 17 21 22 23 24  12 9 11 12 13 14 15 16 17 18 18 19 20 20 20 23 25 26 27  14 10 11 13 14 15 16 17 18 19 20 21 21 22 22 26 27 29 30  16 10 12 14 15 16 17 19 20 20 21 22 23 24