Краткое содержание страницы № 1 
                    
                        90MA/MU 
Single-Package Marine Cooling Units 
 
 
Installation, Operation and Service Instructions 
SAFETY CONSIDERATIONS  CONTENTS Page 
 The 90MA/MU Units are designed to provide safe and SAFETY CONSIDERATIONS........................................1 
reliable service when operated within design specifications. GENERAL .....................................................................1 
However, due to system pressures, electrical components, 
INSTALLATION...................................
                    
                    Краткое содержание страницы № 2 
                    
                          TABLE 1A - 90MA/MU PHYSICAL DATA – R-134A , ENGLISH UNITS (See Table 2A for SI units)    BASE UNIT (90MA/MU) UNITS 308 312 NOMINAL CAPACITY Tons 5.5 8 REFRIGERANT R- OPERATING WEIGHT  Base unit 90MA Pounds 895 950 Base Unit 90MU Pounds N/ N/ Discharge Plenum Pounds 50 50 COMPRESSOR TYPE Semi-Hermetic, Recip Qty Cylinders 4 6 Qty Unloading Cylinders 0 2 Qty Capacity Steps 1 2 DISCHARGE PRESSURE SWITCH  Opens (90MA) PSIG 335+/-10  Closes (90MA) PSIG 235+/-10  Opens (90MU) PSIG N/ Closes (90MU) P
                    
                    Краткое содержание страницы № 3 
                    
                            TABLE 1B - 90MA/MU PHYSICAL DATA – R-407C , ENGLISH UNITS (See Table 2B for SI units)    BASE UNIT (90MA/MU) UNITS 404 406 408 412 NOMINAL CAPACITY Tons 3 5 7.5 10 REFRIGERANT R-407C  OPERATING WEIGHT  Base unit 90MA Pounds 390 427 895 950 Base Unit 90MU Pounds 330 360 835 890 Discharge Plenum Pounds 25 25 50 50 COMPRESSOR TYPE Scroll Semi-Hermetic, Recip Qty Cylinders N/ 4 6 Qty Unloading Cylinders N/ 0 2 Qty Capacity Steps 1 1 2 DISCHARGE PRESSURE SWITCH  Opens (90MA) PSIG 395+/-10  Closes
                    
                    Краткое содержание страницы № 4 
                    
                            TABLE 1C - 90MA/MU PHYSICAL DATA – R-404A , ENGLISH UNITS (See Table 2C for SI units)    BASE UNIT (90MA/MU) UNITS 504 506 508 512 NOMINAL CAPACITY Tons 3 5 7.5 10 REFRIGERANT R- OPERATING WEIGHT  Base unit 90MA Pounds 390 427 895 950 Base Unit 90MU Pounds 330 360 835 890 Discharge Plenum Pounds 25 25 50 50 COMPRESSOR TYPE Scroll Semi-Hermetic, Recip Qty Cylinders N/ 4 6 Qty Unloading Cylinders N/ 0 2 Qty Capacity Steps 1 1 2 DISCHARGE PRESSURE SWITCH  Opens (90MA) PSIG 395+/-10  Closes (90M
                    
                    Краткое содержание страницы № 5 
                    
                            TABLE 2A - 90MA/MU PHYSICAL DATA – R-134A , SI UNITS     BASE UNIT (90MA/MU) UNITS 308 312 NOMINAL CAPACITY kW 19.3 28.1 REFRIGERANT R- OPERATING WEIGHT  Base unit 90MA kg 406 431 Base Unit 90MU kg N/ N/ Discharge Plenum kg 22.7 22.7 COMPRESSOR TYPE Semi-Hermetic, Recip  Qty Cylinders 4 6 Qty Unloading Cylinders 0 2 Qty Capacity Steps 1 2 DISCHARGE PRESSURE SWITCH  kPa 2310+/-69  Opens (90MA) Closes (90MA) kPa 1620+/-138 Opens (90MU) kPa N/ Closes (90MU) kPa N/ SUCTION PRESSURE SWITCH  Opens
                    
                    Краткое содержание страницы № 6 
                    
                            TABLE 2B - 90MA/MU PHYSICAL DATA – R-407C , SI UNITS     BASE UNIT (90MA/MU) UNITS 404 406 408 412 NOMINAL CAPACITY kW 10.5 17.6 26.4 35.1 REFRIGERANT R-407C  OPERATING WEIGHT  Base unit 90MA kg 177 194 406 431 Base Unit 90MU kg 150 163 379 404 Discharge Plenum kg 11.3 11.3 22.7 22.7 COMPRESSOR TYPE Scroll Semi-Hermetic, Recip Qty Cylinders N/ 4 6 Qty Unloading Cylinders N/ 0 2 Qty Capacity Steps 1 1 2 DISCHARGE PRESSURE SWITCH  kPa  Opens (90MA) 2725+/-69 Closes (90MA) kPa 2034+/-138 Opens 
                    
                    Краткое содержание страницы № 7 
                    
                            TABLE 2C - 90MA/MU PHYSICAL DATA – R-404A , SI UNITS     BASE UNIT (90MA/MU) UNITS 504 506 508 512 NOMINAL CAPACITY kW 10.5 17.6 26.4 35.1 REFRIGERANT R- OPERATING WEIGHT  Base unit 90MA kg 177 194 406 431 Base Unit 90MU kg 150 163 379 404 Discharge Plenum kg 11.3 11.3 22.7 22.7 COMPRESSOR TYPE Scroll Semi-Hermetic, Recip Qty Cylinders N/ 4 6 Qty Unloading Cylinders N/ 0 2 Qty Capacity Steps 1 1 2 DISCHARGE PRESSURE SWITCH Opens (90MA) kPa 2725+/-69  Closes (90MA) kPa 2034+/-138  Opens (90MU
                    
                    Краткое содержание страницы № 8 
                    
                           Step 4 - Rig and Place Unit -     NOTE: Install accessories before placing unit.    a. Provide space around unit for service, filter access, and  overhead clearance as indicated in Figure 2.  b. Move and store unit in upright position.  c. Use slings with spacer under base skid to prevent panel  damage when using hoist.   d. Units as shipped are adequately dampened against  vibration. If additional dampening is desired, place  sponge rubber or rubber mat, between deck and base of  unit or ins
                    
                    Краткое содержание страницы № 9 
                    
                            Step 7 - Install Ventilation-Air Ductwork (If required)-  Connect ventilation ducts to flanges on outside-air supply  opening (Figure. 2) using a flexible connection. Attach  ductwork to ship structure, insulate and cover with vapor  barrier to reduce sound transmission and prevent vapor  condensation.   Weatherproof external ductwork, joints, and openings  in accordance with applicable codes. Ducts passing  through an unconditioned space must be insulated and  covered with a vapor barrier. 
                    
                    Краткое содержание страницы № 10 
                    
                          a. Route regulating valve capillary with its flare nut to the  fitting on refrigerant discharge line (Figure. 1), using  any convenient unused opening on side of unit. Use a  grommet in panel to prevent chafing of capillary.  b. Remove cap from discharge line fitting.  c. Remove cotter pin taped to discharge line fitting. Insert  pin, split end first, into regulating valve flare    d. Hold flare tightly against fitting while connecting flare  nut. Round end of cotter pin will depress core of f
                    
                    Краткое содержание страницы № 11 
                    
                          TABLE 3 - RECOMMENDED LINE SIZES (INCHES) REMOTE CONDENSERS    LENGTH OF RUN UNIT    REFRIGERANT  90MU TYPE 0-25 26-50 51-75 76-100 DISCH LIQUID DISCH LIQUID DISCH LIQUID DISCH LIQUID 404 R-407C 1/2 3/8 5/8 3/8 5/8 3/8 5/8 3/8 406 R-407C 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8 408 R-407C 3/4 1/2 3/4 1/2 7/8 1/2 7/8 1/2 412 R-407C 7/8 1/2 7/8 1/2 7/8 1/2 1-1/8 5/8 504 R-404A 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 506 R-404A 3/4 1/2 3/4 1/2 7/8 1/2 7/8 1/2 508 R-404A 7/8 1/2 7/8 1/2 1-1/8 1/2 1-1/8 5/8 512 R-4
                    
                    Краткое содержание страницы № 12 
                    
                          Step 12 - Make Electrical Connections  OPERATION    GENERAL - Provide an adequate fused disconnect switch   within sight of the unit. Provision for locking switch open  CAUTION  (OFF) is advisable to prevent power from being turned on    when unit is being serviced.  Compressor crankcase heater must be    energized for 24 hours prior to startup to  POWER WIRING - Conduit opening for all units is on left  prevent compressor bearing damage.  side of unit near control box. Connect field power wir
                    
                    Краткое содержание страницы № 13 
                    
                              SERVICE    WARNING    NEVER reach into unit while  fan is running. LOCK OPEN  AND TAG unit disconnect  before working on fan. Remove  fuses and take them with you  after noting this on tag.    CAUTION     1. Sharp edges of coil fins are exposed. To  prevent injury, cover top of evaporator  with cardboard or a few layers of heavy  tape.  2. To avoid coil damage, cover evaporator  face with plywood or other rigid sheet  material. If any coil fins are mashed or  FIGURE 8 - FAN PULLEY ADJUSTME
                    
                    Краткое содержание страницы № 14 
                    
                          Evaporator Coil - Observe fan compartment Caution note  at the beginning of the Service section.   Remove dirt and debris from evaporator coil as  required by condition. Clean coil with a stiff brush, vacuum  cleaner or compressed air. Use a fin comb of the correct  tooth spacing (Refer to Tables 1A/B/C/2A/B/C  for coil  fins/inch) when straightening mashed or bent coil fins.    Water Regulating Valve    PREPARATION FOR OPERATION.  1. Open the water regulating valve inlet and outlet  isolation
                    
                    Краткое содержание страницы № 15 
                    
                          Charging the System (90MA) - These units are shipped Evaporator-Fan Motor Removal - Motor power wires  with a full operating charge. If recharging is necessary need not be disconnected from motor terminals before  (complete charge lost), weigh in amount of refrigerant motor is removed from unit.  indicated on unit nameplate and in Table 1. 1.  Shut off unit main power supply.   If unit has partial charge, it must be recharged by   removing existing charge and recharging by weighing in  WARNING
                    
                    Краткое содержание страницы № 16 
                    
                          compressor equipped units and on the suction line on all  other units.    Oil Charge - All units are factory charged with oil. On 06D  compressors, observe the oil level in the sight glass at  start-up. If unit oil level is below sight glass, add oil until  level reaches approximately 1/4 sight glass.   If oil charge is above sight glass, do not remove any oil  until the compressor crankcase heater has been energized  for at least 24 hours.   When additional oil or a complete charge is require
                    
                    Краткое содержание страницы № 17 
                    
                                    FOR NOTES AND LEGEND, SEE FIGURE 13        FIGURE 12 WIRING SCHEMATIC - 90MA/MU*04/*06    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations  Printed in U.S.A. 90MA-3SI     SUPERCEDES FORM 62-02971-00   09-2009  Pg 17                                                                                                                                                                                
                    
                    Краткое содержание страницы № 18 
                    
                              FIGURE 13 COMPONENT ARRANGEMENT - 90MA/MU*04/*06    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations  Printed in U.S.A. 90MA-3SI     SUPERCEDES FORM 62-02971-00   09-2009  Pg 18                                                                                                                                                                                                                            
                    
                    Краткое содержание страницы № 19 
                    
                                  FOR NOTES AND LEGEND, SEE FIGURE 15        FIGURE 14 - ELECTRICAL SCHEMATIC - 90MA/MU*08/*12    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations  Printed in U.S.A. 90MA-3SI     SUPERCEDES FORM 62-02971-00   09-2009  Pg 19                                                                                                                                                                            
                    
                    Краткое содержание страницы № 20 
                    
                              FIGURE 15 - COMPONENT ARRANGEMENT - 90MA/MU008/012      Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations  Printed in U.S.A. 90MA-3SI     SUPERCEDES FORM 62-02971-00   09-2009  Pg 20