                        Room Air Conditioners
AUTO F
C
AUTO FAN AM
CONTINUOUS PM
SET POINT ON OFF
ROOM TEMP  SCHEDULE
CHECK $MART
AUTO SPEED FILTER
SYSTEM FAN MODE
POWER
FAN SPEED SCHEDULE
Q Chassis Models
115-Volt: SQ05, SQ06, SQ08, SQ10
115-Volt: EQ08 
93001003_01 
Installation and Operation Manual                                                                                                                                                                                                                               
                    
                    Краткое содержание страницы № 2 
                    
                        Thank you for your decision to purchase the Friedrich High Effi ciency Air Conditioner.  Your new Friedrich has been carefully engineered and manufactured to  give you many years of dependable, effi cient operation, maintaining a comfortable temperature and humidity level.  Many extra features have been built into  your unit to assure quiet operation, the greatest circulation of cool, dry air, and the most economic operation. THANK YOU, on behalf of our entire company,  for making such a wise purc
                    
                    Краткое содержание страницы № 3 
                    
                        Table of Contents Table of Contents ......................................................................................................................................................................................................................................................................................3 Safety Precautions .....................................................................................................................................................................
                    
                    Краткое содержание страницы № 4 
                    
                        Safety Precautions Your safety and the safety of others are very important. We have provided many important safety messages in this manual and on your appliance. Always read and obey all  safety messages. This is a safety Alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol with the word “WARNING”  or “CAUTION”. These words mean: Indicates a hazard which, if not avoided, can result in severe person
                    
                    Краткое содержание страницы № 5 
                    
                        Unpacking Instructions STEP 1. CUT ALL PACKING STRAPS. STEP 4. SLOWLY REMOVE OUTER BOX. STEP 2. CUT TAPE AND OPEN. STEP 5. REMOVE CORNER POSTS. STEP 3. REMOVE TOP PACKAGING MATERIAL AND CARTON STEP 6. REMOVE UNIT FROM SHIPPING TRAY. CONTAINING SIDE CURTAINS. STEP 7. REMOVE CARBON FILTER AND HARDWARE FROM  BOTTOM TRAY. STEP 2 STEP 1 STRAPS X4 STEP 4 STEP 3 STEP 6 STEP 7 STEP 5 5                                                                                                                        
                    
                    Краткое содержание страницы № 6 
                    
                        Table 1. WARNING: Before Operating Your Unit CIRCUIT RATING  REQUIRED WALL  OR TIME DELAY  Make sure the wiring is adequate for your unit. RECEPTACLE FUSE MODEL If you have fuses, they should be of the time delay type.  Before you install  AMP VOLT NEMA NO. or relocate this unit, be sure that the amperage rating of the circuit breaker  or time delay fuse does not exceed the amp rating listed in Table 1. SQ05  SQ06 SQ08  SQ10 15 125 5-15P DO NOT use an extension cord. EQ08 The cord provided will 
                    
                    Краткое содержание страницы № 7 
                    
                        Standard Filter Cleaning / Installation Instructions STEP 1. Swing the door open and remove the fi lter by grasping the STEP 2. Clean the front frame by washing the dirt from the fi lter. Use a  fi lter grip and pushing the fi lter holder upward and outward. mild soap solution if necessary. Allow fi lter to dry. STEP 3. Install the fi lter back into the unit. Follow the Instructions on  the inside of the front door. Figure 3 Figure 2 FILTER DOOR FILTER FILTER FRAME DOOR INSTRUCTIONS FRR075 FRR076 Prem
                    
                    Краткое содержание страницы № 8 
                    
                        Control Panel Operation Let’s check out how to control your air conditioner. On the control panel, just above the POWER , is a liquid crystal display ( LCD). All of the control panel function  buttons and mode icons can be viewed in Figure 6. Power On – Press the button to turn on the air conditioner. The power button illuminates to indicate that the power is on. The backlight on the power switch  will automatically dim to 20% intensity after 15 seconds of inactivity. The remote control can also
                    
                    Краткое содержание страницы № 9 
                    
                        Kühl Control Options The “Residential” (40 Hr. Work Week) Schedule has four (4) time periods: 06:00,  The  Kühl gives you a variety of options for control, programming, and  08:00, 18:00, and 22:00.  This option will cause your Kühl Q unit to raise the room  scheduling including wireless capabilities temperature temporarily to 85°F during the hours wh en most people are away  at work, lower them again to 78°F prior to the time when most people will return  Wireless Programming and Control: home,
                    
                    Краткое содержание страницы № 10 
                    
                        FAN MODE AUTO FAN FAN MODE – The  button allows you to select between  and  Control Panel Operation Instructions CONTINUOUS  modes. SYSTEM - The SYSTEM button allows you to sequentially select three modes  AUTO FAN (No Cooling Demand) of operation: COOL   HEAT    Not available on some models FAN ONLY   F COOL MODE AUTO FAN 79 SET POINT F AUTO FAN FRR112 74 SET POINT AUTO FAN When in the  mode, the fan only  operates when the system has  a demand to cool or heat the room. Note: the fan is off (no
                    
                    Краткое содержание страницы № 11 
                    
                        The  icon illuminates. UP  and DOWN  - arrows - Pressing either   or  button changes  the system's set point (desired room temperature). These buttons are also  The TIMER function (option 1, system default) allows you to de  ne a daily  used to make system parameter changes later in this manual. system ON and OFF time window. For example, you can command the  system to turn ON at 8:15 am and turn OFF at 1:30 pm everyday. The SCHEDULE function allows you to choose either Residential (option  2) o
                    
                    Краткое содержание страницы № 12 
                    
                        and  4  C FRR130 FRR134 Use the  or  buttons to adjust the day (1 to 7). The day setting is up  A “C” will  ash for 5 seconds and then revert to a normal display. to you the user. If you set the current day = 1, and today is Tuesday,  then Day 1 = Tuesday. C AUTO FAN F AUTO FAN 26 SET POINT 79 SET POINT FRR135 The ºF icon goes away and the ºC icon illuminates on the normal display. FRR131 Press TIMER SET (Refer to Figure 8) button to exit and save the SET  DIM Function TIME function. The TIMER S
                    
                    Краткое содержание страницы № 13 
                    
                        This means there is a compressor demand but the system is not ready  for the compressor to operate. For example a short power outage, the  compressor will not restart until the internal pressures of the compressor  are at the proper level. Lock Control Panel FAN To lock the front panel controls, press and hold the SPEED +  buttons   3 for 3 seconds. The lock icon  illuminates to indicate the locked status.  Control panel buttons will not operate during lockout. FRR194 The 3 indicates a DIM setti
                    
                    Краткое содержание страницы № 14 
                    
                        External Control Status Commercial (Schedule #2) - When selected the unit follows a pre- programmed set of operational parameters that covers 7 days of  $MART The  icon illuminates to indicate that the system is being controlled  the week with 2 time windows during each day. Each time window  remotely. has it's own set of 6 operating parameters. Refer to Addendum.  F AUTO FAN 79  1 SET POINT SCHEDULE $MART FRR125 FRR137 1. To change the  selection, press and hold the TIMER/SCHEDULE  button for 3
                    
                    Краткое содержание страницы № 15 
                    
                        F AUTO FAN 79 SET POINT FRR139 FRR143 The display returns to normal once the settings are saved. To turn on the timer or schedule selected, press            button and let go, the  system will operate in the mode (1, 2 or 3) you selected. Timer Stop Time Modify the TIMER Function Timer Start Time F AUTO FAN F 79 SET POINT AUTO FAN 79 SET POINT FRR144 The display shows a normal system. Press and hold the MIN button (Figure  8) for 3 seconds. Note the Timer start - stop times may be set even when 
                    
                    Краткое содержание страницы № 16 
                    
                        Schedule ON Scenarios F AUTO FAN F AUTO FAN 79 SET POINT 79 SET POINT FRR147 The display returns to normal once the settings are saved. FRR154 The display shows a normal system. Timer - Scheduler Control Block If the Schedule function is turned ON during normal operation F AUTO FAN 79 SET POINT SCHEDULE SCHEDULE FRR148 If the unit is operating in the TIMER or SCHEDULE mode, and then you  FRR153 press any button except the  button, the Timer  icon begins to  SCHEDULE and Timer  icons illuminates.
                    
                    Краткое содержание страницы № 17 
                    
                        Scheduler OFF Scenarios Timer ON Scenarios F F AUTO FAN AUTO FAN 79 79 SET POINT SET POINT SCHEDULE FRR160 FRR156 The display shows a normal system. The display shows the unit in Schedule mode. F AUTO FAN 79 SET POINT FRR157 FRR161 If the Timer function is turned ON during the Off time, the  icon   If the Schedule function is turned OFF during an active state (not off), the    illuminates. The control system immediately turns the unit OFF. SCHEDULE Timer and  icons turn off. The control stays in
                    
                    Краткое содержание страницы № 18 
                    
                        Scenario 2: F AUTO FAN F AUTO FAN 79 SET POINT 79 SET POINT FRR163 FRR168 If the Schedule function is turned OFF during an in-active (OFF) period,  SCHEDULE the Timer  and  icons turn off. The unit wakes up in the last  The display shows the unit in Timer mode during an active (ON) period. known non-schedule state. Timer OFF Scenarios Scenario 1: F AUTO FAN 79 SET POINT FRR169 If the Timer function is turned OFF during the ON time. The Timer  icon  FRR166 turns off. The control stays in the curr
                    
                    Краткое содержание страницы № 19 
                    
                        FAN SPEED Button - Used to sequentially select new fan speed, plus  Remote Control Operation FAN AUTO operation. When the  button is pressed, the fan speed icon  SPEED (triangle) changes to indicate the new speed level.  Fan speed automatically  Remote Control - Refer to Figures 10 and 11 during operation description. varies depending on the set temperature on the control panel and the actual  Getting Started - Install two (2) AAA batteries in the battery compartment  room temperature.  For exam
                    
                    Краткое содержание страницы № 20 
                    
                        Figure 10 DISPLAY AUTO FAN CONTINUOUS 88 AUTO  C F SYSTEM FAN MODE SYSTEM FAN MODE POWER POWER TEMPERATURE TEMPERATURE UP DOWN FAN SPEED SCHEDULE SCHEDULE FAN SPEED FRR081 Figure 11 COOL HEAT FAN ONLY ICON ICON ICON SYSTEM MODE AUTO FAN FAN MODE CONTINUOUS 88 AUTO  FAN SPEED C F °F / °C ICONs SCHEDULE ICON FRR082 20