Краткое содержание страницы № 1 
                    
                        2000 Fire Door-Fan Manual 
with Model N digital OR, Model L digital OR, Model E analog 
Single Blower Panel Set 
gauge clip 
console control panel 
Up 
 
 
 
Or, E43 Aluminum Smoke test &  
Leak check at + 15Pa 
Large room testing with 
measure static pressure 
Frame  Set Up 
2 Blowers  Room pressure 
 
 
 
 
 
 
 
 
 
 
 
 
Range Selection 
 
Room and Flow 
Mixing or NO mixing? 
Windy test conditions 
Pressure Readings 
 
2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 1 o
                    
                    Краткое содержание страницы № 2 
                    
                                Run from CA2001      Lower leak Estimates   Lower leak tests using:  Lower leak tests using:  using: Leak audit   Plastic-on-Ceiling  Flex-duct ceiling  What to do if room fails. procedure  neutralization      Sub-floor Only tests using  Field Calibration  Floor neutralization    procedure  Tall doorways Packing up and moving  equipment       Recalibration of Troubleshooting and    Large building Testing  repair  Retrotec Infiltrometer  …rent additional  equipment if needed  2000 Fire Do
                    
                    Краткое содержание страницы № 3 
                    
                        Single Blower Panel Set Up       Select a doorway where the air will be blown into Open panel bag and remove the Blower Panel with  the largest space so the air can find its way back to the 22-inch hole in it.  the leak.  Set the panel bag close to the door.     Open Blower Panel and position back edge against Pull top strap tight and secure strap in the nylon  the doorstop. cleat. Press the loop against the Velcro to keep strap  ends neat.    2000 Fire Door-Fan Manual                  updated 2
                    
                    Краткое содержание страницы № 4 
                    
                             Cinch lower strap tight and secure strap in cleat. The small fill-in sheet is positioned first in the  groove.  It fills in the gap for doors up to 36”     Smooth down the fill-in sheet from top to bottom Place the large X-Panel in the top of the doorway.     Cinch and lock the pull strap to secure the panel. Place blower case next to the doorway.    2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 4 of 58                                                                 
                    
                    Краткое содержание страницы № 5 
                    
                             Hook the bottom foot on the blower through the Align the nylon block on top of the blower with the  hole in the center of the panel. panel cutout, insert and rotate the blower till the  top is horizontal to lock it into the panel.  The blower is mounted in the Flow Away position.  This is always first.  When the test is complete in  this direction, the blower is removed and installed  with the Flow Towards the operator.    Blower is upright and locked in place.     2000 Fire Door-Fan Manual
                    
                    Краткое содержание страницы № 6 
                    
                        Set up Model N digital console      Place Laptop Console on blower case. Set rocker switches OFF by pressing the “0” so  blowers don’t come on accidentally.     Remove the control cords  Place the cords next to the panel set.  Power to console comes from:    1. Blower receives power from wall.   Cord from console picks up this  power to run the printer, computer  and thermometers.    2. When blower is not plugged in, the  console can get power from the short  adapter plug that fits onto the end 
                    
                    Краткое содержание страницы № 7 
                    
                          Your laptop computer power supply plugs  into the female plug inside the console.   The power supply cord is then led through  this hole to the computer above.        2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 7 of 58                                                                                                                                                                                                                                                              
                    
                    Краткое содержание страницы № 8 
                    
                          OR, Model L digital control panel for Models L64 and L63      The control panel can sit on top of the blower case with your laptop beside it.  2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 8 of 58                                                                                                                                                                                                                                                                                      
                    
                    Краткое содержание страницы № 9 
                    
                        OR, Model E analog gauge clip  for models E43, E53, E54        The Gauge Clip attaches to the door Gauges mounted on door.   or the Aluminium frame. Top 60-gauge slides up and  off to be used as handheld  1.  Loosen knob on gauge plate to  as needed.  accommodate door thickness.  2.  Hold gauges at eye level.    3.  Rotate clamp to grip door.  4.  Tighten knob.    Zero gauges by blowing in the tubes and capping them    off with your thumb so the gauge stays at the top of its  range for 30 second
                    
                    Краткое содержание страницы № 10 
                    
                        OR, DM-1 digital gauge for models J64    The digital gauge can be hand held and used to  measure static pressure, room pressure and flow  pressure.  Connect a tube from the panel to the right  hand port of the DM-1 to get room pressure.  Then  connect a tube from the DM-1 to the blower to get  flow pressure.   OR, DM-1 digital gauge  2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 10 of 58                                                                                      
                    
                    Краткое содержание страницы № 11 
                    
                             Take the 7ft red tube and throw outside, away from Insert the motor control connector into the  the air blast of the door fan and if outdoors, away receptacle till it clicks.  from wind if possible. If you were testing from E and J models will not have a control connector  outside the room, this tube would then get thrown since the knob on the blower is used.  inside.     Plug the clear flow pressure pick-up tube into the Make sure the 7ft red cord and thermometer are in  nylon quick-connec
                    
                    Краткое содержание страницы № 12 
                    
                           Install the X-Y Panel. Expand the X-Y panel horizontally by hand.     Expand the X-Y Panel vertically with the center Cinch and lock the vertical strap in the cleat.  strap.          Tighten and lock the horizontal straps in their cleats. Ensure rocker switches are OFF at the control panel.   Plug power cord into wall outlet then into blower.   Set rocker switch on blower to “remote” so it can be  controlled by the console or control panel.  2000 Fire Door-Fan Manual                  updated 
                    
                    Краткое содержание страницы № 13 
                    
                            Red tube is always extended   away from the air-stream on  the opposite side of the door.  2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 13 of 58                                                                                                                                                                                                                                                                                                                                       
                    
                    Краткое содержание страницы № 14 
                    
                            This detailed picture shows white dots that should line up.  Later models may  have molded dots.    This vertical bar should line up on each sheet.    2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 14 of 58                                                                                                                                                                                                                                                                           
                    
                    Краткое содержание страницы № 15 
                    
                        Large room testing with 2 Blowers    Models N64 and L64    Use the second blower panel.  Install it above the lower blower  panel. Install the second blower in the upper panel.  For added  security:  1. mount the panels on the far side of the doorstop so the  weight of the blowers pulls them into the stop  2. apply 2-inch clear tape to both sides of the upper panel  where it contacts the doorframe   Use second cord set from console to control the speed of blower #2.      Models E64 and J64    Us
                    
                    Краткое содержание страницы № 16 
                    
                        Or, E43 Aluminum Frame  Set Up      Open case Take out pieces Assemble flat.  Line up numbers.      Connect corners Fit frame loosely into doorway. Adjust knobs to hold the size       Cover with cloth Fit frame and cloth into door way.   2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 16 of 58                                                                                                                                                                                        
                    
                    Краткое содержание страницы № 17 
                    
                             Actuate cam levers Frame is installed. Hook elastic under blower.        Use Velcro to hold blower Finished installation.     This install will take about 20 The main advantage of the  minutes the first time.   It will Aluminum frame is slightly smaller  take less time with practice. package for shipment and lower   cost.        2000 Fire Door-Fan Manual                  updated 2002-05-28    Page 17 of 58                                                                                      
                    
                    Краткое содержание страницы № 18 
                    
                        Leak Check  The Purpose of the leak check is to locate the major leaks in the enclosure before performing the door fan test.   Often large holes are located that must then be sealed before the door fan test can begin.   Sometimes the smoke  test identifies dampers that are not closing correctly or not at all.  If so, that damper must be repaired before the  test can proceed. Leak check. Blow air in to get +15 Pa room pressure & use smoke to locate leaks in:           Rocker switch selects betwee
                    
                    Краткое содержание страницы № 19 
                    
                           Smoke test & measure static pressure    The purpose of this test is to see whether there is a static pressure in the room prior to the  door fan test.  The door fan is not running and smoke is puffed in front of an open hole in the  blower.  If it moves slowly or not at all, no pressure exists.  Minor pressures are cancelled out  by testing both directions so we are therefore looking for significant movement of 2 mph  (3kph).   If the zone outside the enclosure is not completely connected wit
                    
                    Краткое содержание страницы № 20 
                    
                        Select Blower Range      Principles of Infiltrometer Air Flow Measurement  The Infiltrometer can accurately measure airflow between 18 CFM and 6500 CFM.  However, in order to  measure accurately over this wide range, the range must be changed as described in the following section.     The Infiltrometer fan blade pushes air out the back of the fan creating a negative pressure in front of the  blades.  This negative pressure pulls air through the fan's rounded (venturi) shaped inlet.  More negativ