                        Instruction Manual
 coMMercIal Gas water heaters
power vented Gas Models w/hot surface IGnItIon
Model he 50 76n serIes 100
www.reliancewaterheaters.com
500 Tennessee Waltz Parkway
Ashland City, TN 37015
Technical Support 800-365-4054
Parts 800-821-2017
Low Lead Content
• for Your safety •
AN ODORANT IS ADDED TO THE GAS USED 
BY THIS WATER HEATER.
all technIcal and warrantY questIons: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS 
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE
                    
                    Краткое содержание страницы № 2 
                    
                        safe InstallatIon, use and servIce The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and  others of a potential injury hazard.  Read and obey all safety messages and instructions throughout this manual.  It is very important  that the meaning of each safety message is understood by you and others who
                    
                    Краткое содержание страницы № 3 
                    
                        General safetY InforMatIon 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        
                    
                    Краткое содержание страницы № 4 
                    
                        General safetY InforMatIon at least 18" (45.7 cm) above the floor. This  will reduce, but not eliminate, the risk 4                                                                                                                                                                                                                                                                                                                                                                                                 
                    
                    Краткое содержание страницы № 5 
                    
                        taBle of contents SAFE INSTALLATION, USE AND SERVICE........................................ 2 Vent Pipe Assembly .................................................................... 19 APPROVALS ........................................................................................ 2  Venting ....................................................................................... 19 GENERAL SAFETY INFORMATION ................................................. 3-4  Vent Pipe Termination .........
                    
                    Краткое содержание страницы № 6 
                    
                        InstallatIon requIreMents for the coMMonwealth of Massachusetts coMMonwealth of Massachusetts InspectIon The state or local gas inspector of the side wall horizontally  For all side wall terminated, horizontally vented power vent, direct  vented gas fueled equipment shall not approve the installation  vent, and power direct vent gas fueled water heaters installed in  unless, upon inspection, the inspector observes carbon monoxide  every dwelling, building or structure used in whole or in part fo
                    
                    Краткое содержание страницы № 7 
                    
                        tYpIcal InstallatIon Get to Know Your water heater - Gas Models  a v ent pipe hh Bushing  q rating plate   B anode II nipple  r  Insulation  c hot w ater outlet jj condensate t ee  s v ent t erminal  D Outlet (120 VAC) KK adapter  t drain v alve  f Gas supply ll plug  u Igniter and Main Burner  G Main Manual Gas shut off v alve MM vent pipe assembly #1  w  drain pan  h Ground joint union nn v ent pipe assembly #2  X  control  j dirt leg oo v ent pipe assembly #3  Y control harness*  K outer door
                    
                    Краткое содержание страницы № 8 
                    
                        tYpIcal InstallatIon condensate hose and draIn pan FIGURE 1 (continued). 8                                                                                                                                                                                                                                                                                                                                                                                                                                          
                    
                    Краткое содержание страницы № 9 
                    
                        tYpIcal InstallatIon MIXInG valve / therMal eXpansIon tanK usaGe and space heatInG fIGure 2. Mixing valves are available at plumbing supply stores. Consult a  MIXInG v alves Qualified	 Installer	 or	 Service	 Agency .	 Follow	 mixing 	 valve	 manufacturer’ s	 instructions for installation of the valves. taBle 1.  Water temperature over 125°F (52°C) DANGER can cause severe burns instantly Time to Produce 2nd & 3rd Water Temperature resulting in severe injury or death. Degree Burns on Adult Skin C
                    
                    Краткое содержание страницы № 10 
                    
                        rouGh-In-dIMensIons rough-In-dimensions T op/Side	Inlet	and	Outlet:	3/4”	NPT Gas	Inlet:	1/2”	NPT capacity and Gas and electrical characteristics All	models	-	Maximum	Supply	Pressure:	14	inches	W .C.	(3.48kPa) Minimum	Supply	Pressure	Natural	Gas:	5.0	inches	W .C.	(1.24kPa) Minimum	Pressure	must	be	maintained	under	both	load	and	no	load	(static	and	dynamic)	conditions. recovery capacities - u.s. Gallons/hr. and liters/hr. at t emperature rise Indicated Recovery	capacity	based	on	90%	thermal	effici
                    
                    Краткое содержание страницы № 11 
                    
                        locatInG the new water heater f acts to consIder aBout the locatIon Carefully choose an indoor location for the new water heater, because  the placement is a very important consideration for the safety of the  occupants in the building and for the most economical use of the  appliance. this water heater is not for use in manufactured  (mobile) homes or outdoor installation. Whether replacing an old water heater or putting the water heater in  a new location, the following critical points must be
                    
                    Краткое содержание страницы № 12 
                    
                        in	 an	 alcove	 or	 closet,	 the	 entire	 floor	 must	 be	 covered	 by	 the	 panel.	 If this water heater will be used in beauty shops, barber shops,  Failure	to	heed	this	warning	may	result	in	a	fire	hazard. cleaning establishments, or self-service laundries with dry cleaning  equipment, it is imperative that the water heater or water heaters  be installed so that combustion and ventilation air be taken from  outside these areas.   Propellant s	 of 	 aerosol 	 sprays	 and	 volat ile	 compounds,
                    
                    Краткое содержание страницы № 13 
                    
                        Such a condition often will result in a yellow, luminous burner free area and metal louvers and grilles will have 75% free area. Non  flame, causing sooting of the combustion chamber, burners and  motorized	louvers	and	grilles	shall	be	fixed	in	the	open	position. flue tubes and creates a risk of asphyxiation. fresh aIr openInGs for confIned spaces Do 	 not 	 install 	 the 	 water 	 heater 	 in 	 a 	 confined 	 space 	 unless 	 an	 adequate supply of air for combustion and ventilation is brought 
                    
                    Краткое содержание страницы № 14 
                    
                        Figure 7. The water heater shall have clearances of at least 1 inch T h e	 c o n fi n e d	 s p a c e	 s h a l l	 b e	 p r o v i d e d	 w i t h	 t w o	 p e r m a n e nt	 v e r t i c a l	 (25	 mm)	 from	 the	 sides	 and	 back	 and	 6	 inches	 (150	 mm)	 from	 the	 d u c t s ,	 o n e	 c o m m e n c i n g	 w i t h i n	 1 2	 i n c h e s	 ( 3 0 0	 m m )	 o f	 t h e	 t o p	 a n d	 front of the appliance. The opening shall directly communicate with  o n e	 c o m m e n c i n g	 w i t h i n	 1 2	 i n c h 
                    
                    Краткое содержание страницы № 15 
                    
                        InstallInG the new water heater This water heater should not be connected to any heating systems or  cheMIcal vapor corrosIon c o m p o n e n t (s) 	 u s e d 	 w i t h 	 a 	 n o n - p o t a b l e 	 w a t e r 	 h e a t i n g 	 a p p l i a n c e . CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY  All piping components connected to this unit for space heating  OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL  applications should be suitable for use with potable water. VAPORS. SUCH CORROSION MAY R
                    
                    Краткое содержание страницы № 16 
                    
                        therMal eXpansIon As	 water	 is	 heated,	 it	 expands	 (thermal	 expansion).	 In	 a	 closed	 system	 the volume of water will grow when it is heated. As the volume of water  grows there will be a corresponding increase in water pressure due  to thermal expansion. Thermal expansion can cause premature tank  failure	 (leakage).	 This	 type	 of	 failure	 is	 not	 covered	 under	 the	 limited	 warranty. Thermal expansion can also cause intermittent Temperature- Pressure Relief Valve operation: water
                    
                    Краткое содержание страницы № 17 
                    
                        discharge opening must not be blocked or reduced in size under  hIGh altItude InstallatIon any 	 circumstances. 	 Excessive 	 length, 	 over 	 30 	 feet 	 (9.14 	 m), 	 or	 use of more than four elbows can cause restriction and reduce  the discharge capacity of the valve. No valve or other obstruction is to be placed between the  Temperature-Pressure Relief Valve and the tank. Do not connect  discharge 	 piping 	 directly 	 to 	 the 	 drain 	 unless 	 a 	 6” 	 (15.2 	 cm)	 air gap is provided. T
                    
                    Краткое содержание страницы № 18 
                    
                        A 	 gas	 line 	 of	 sufficient	 size	 must	 be	 run	 to	 the	 water	 heater .	 	 Consult	 sedIMent traps the	 current	 edition	 of	 National	 Fuel	 Gas	 Code	 (ANSI	 Z223.1/NFP A 	 54)	 or	 the	 Natural	 Gas	 and	 Propane	 Installation	 Code	 (CAN/CSA 	 B149.1)	and	your	gas	supplier	concerning	pipe	size. There must be: •	 A 	 readi ly	 accessible	 manual	 shut	 of f	 valve	 in	 the	 gas	 supply	 line	 serving the water heater, and •	 A 	 drip	 leg	 (sediment	 trap)	 ahead	 of 	 gas	 control	 val
                    
                    Краткое содержание страницы № 19 
                    
                        Never use this water heater unless it is completely full of water. To should 	 be 	 appro ximately	 0. 25”	 ( 0.6 4 	 c m ) , 	 see 	Figure 16. Disassemble  p r e v e nt	 d a m a g e	 t o	 t h e	 t a n k ,	 t h e	 t a n k	 m u s t	 b e	 fi l l e d	 w i t h	 w a t e r .	 W a t e r	 the parts and cement back together using the alignment marks. After  m u s t	 fl o w	 f r o m	 t h e	 h o t	 w a t e r	 f a u c et	 b e f o r e	 t u r n i n g	 “ O N ”	 g a s	 t o	 t h e	 the cement dries, attach the a
                    
                    Краткое содержание страницы № 20 
                    
                        v v terMInatIon clearances sIdewall power vent POWER VENT (using room air for combustion) EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION D E L B VENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED V X fIGure 15.   Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion. 1 2 1 2 canadIan InstallatIons us InstallatIons canadIan InstallatIons us InstallatIons  Clearance to each side 3	feet	(91	cm)	within	a	 Clearance above gra