Краткое содержание страницы № 1 
                    
                        ®
VenT-FRee CoMP aCT FIRePla Ce
oWneR’s oPeRa TIon and InsT alla TIon ManU al
Shown with Optional Cabinet Mantel/Hearth Base Accessory
Models VMH26TPC and VMH26TnC
14,000 to 26,000 Btu/Hr with Thermostat
 WARNING: If the information in this manual is not 
followed exactly, a fire or explosion may result causing 
property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable  
vapors and liquids in the  vicinity of this or any other 
appliance.
— WHAT TO DO I
                    
                    Краткое содержание страницы № 2 
                    
                        TaBle oF ConTenTs Safety .................................................................. 2 Cleaning and Maintenance ................................ 23 Local Codes......................................................... 4 Troubleshooting ................................................. 24 Product Identification ........................................... 4 Specifications .................................................... 28 Product Features ................................................
                    
                    Краткое содержание страницы № 3 
                    
                        saFeTy Continued Keep the appliance area clear   WARNING: Any change to  and free from combustible ma- this heater or its controls can  terials, gasoline, and other flam- be dangerous. mable vapors and liquids. 1. This appliance is only for use with type of   WARNING: Do not allow fans  gas indicated on rating plate. This appli- to blow directly into the fireplace.  ance is not convertible for use with other  Avoid any drafts that alter burner  gases. flame patterns. Ceiling fans can  2. Do not 
                    
                    Краткое содержание страницы № 4 
                    
                        saFeTy Continued 10. This fireplace needs fresh air ventilation to 14. Turn off and unplug fireplace and let  run properly. This fireplace has an Oxygen cool before servicing. Only a qualified  Depletion Sensing (ODS) safety shutoff service person should service and repair  system. The ODS shuts down the fire- fireplace. place if not enough fresh air is available.  15. Operating fireplace above elevations of  See Air for Combustion and Ventilation,  4,500 feet could cause pilot outage. page 6. I
                    
                    Краткое содержание страницы № 5 
                    
                        PRodUCT Fea TURes SAFETY PILOT THERMOSTATIC HEAT CONTROL This fireplace has a pilot with an Oxygen This fireplace has a thermostat sensing bulb  Depletion Sensing (ODS) safety shutoff and a control valve. The thermostat will auto- system. The ODS/pilot is a required feature matically modulate the heat output to maintain  for vent-free room fireplaces. The ODS/pilot a consistent room temperature. This results in  shuts off the fireplace if there is not enough greater fireplace comfort. This can a
                    
                    Краткое содержание страницы № 6 
                    
                        asseMByl Continued Assembling Hood Louver 1. Locate four black phillips sheet metal  screws from the hardware packet. Hood Tabs 2. Rotate hood as shown in Figure 3. Make  sure hood tabs point toward fireplace. 3. Insert hood tabs between baffle and lou- vers (see Figure 3). 4. Gently rotate hood to upright position.  Make sure hood tabs are behind louvers  Hood Tab Hood and hood is resting on firebox top (see  Figure 3). Baffle 5. Align screw holes on hood with screw  holes on firebox top. Sheet
                    
                    Краткое содержание страницы № 7 
                    
                        aIR FoR CoMBUsTIon and VenTIla TIon Continued c. caulking or sealants are applied to 2. Multiply the space volume by 20 to determine  the maximum Btu/Hr the space can support. areas such as joints around window    ________ (volume of space) x 20 = (Maxi- and door frames, between sole plates  mum Btu/Hr the space can support) and floors, between wall-ceiling joints,  between wall panels, at penetrations  Example: 2560 cu. ft. (volume of space) x 20  for plumbing, electrical, and gas lines, = 51,2
                    
                    Краткое содержание страницы № 8 
                    
                        aIR FoR CoMBUsTIon and VenTIla TIon Continued Ventilation Air From Outdoors  WARNING: If the area in which  Provide extra fresh air by using ventilation  the heater may be operated does grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling  not meet the required volume for  and one within 12" of the floor. Connect these  indoor combustion air, combus- items directly to the outdoors or spaces open  tion and ventilation air shall be  to the outdoors. These space
                    
                    Краткое содержание страницы № 9 
                    
                        InsT alla TIon IMPORTANT: Vent-free fireplaces add mois- NOTICE: This heater is intended  ture to the air. Although this is beneficial,  for use as supplemental heat.  installing fireplace in rooms without enough  Use this heater along with your  ventilation air may cause mildew to form from  primary heating system. Do not  too much moisture. See Air for Combustion  install this heater as your pri- and Ventilation, page 6. mary heat source. If you have a Note: Your Vanguard fireplace is designed
                    
                    Краткое содержание страницы № 10 
                    
                        InsT alla TIon Continued Note: When installing fireplace directly on  LOCATING FIREPLACE carpeting, tile or other combustible material,  other than wood flooring, the fireplace shall be   WARNING: Maintain the  installed on a metal or wood panel extending  minimum clearances shown  the full width and depth of the fireplace. in Figures 6 and 7. If you can,  provide greater clearances from   CAUTION: If you install the  floor, ceiling, and joining wall. fireplace in a home garage • fireplace pilot
                    
                    Краткое содержание страницы № 11 
                    
                        InsT alla TIon Continued IMPORTANT: When finishing your firebox,   WARNING: If pre-wiring, do combustible materials  not connect wiring to any electri-  WARNING: Do not allow any  cal source at this time. combustible/noncombustible  Install fireplace electrical outlet  materials to overlap the firebox  and connect wiring to outlet  front facing. before connecting to electrical  source. The fireplace electri-  WARNING: Do not allow  cal outlet is included with the  noncombustible materials to  GA
                    
                    Краткое содержание страницы № 12 
                    
                        InsT alla TIon Continued OPTIONAL MANTEL INSTALLATION  WARNING: Never modify or  Refer to instructions provided with the mantel  cover the louvered slots on the  for assembly instructions. Refer to the follow- front of the firebox. ing instructions for system installation. Refer  to instructions on page 6 for hood assembly.  Mantel Clearances for Built-In  Blower accessory should be installed prior  Installation to mantel if it is being used (see Installing  If placing mantel above built-in fire
                    
                    Краткое содержание страницы № 13 
                    
                        InsT alla TIon Continued 9. Check all gas connections for leaks. See 4. Slide one end of adjusting plate/shim  Checking Gas Connections, page 18. in slot on mitered edge of top trim (see  Figure 14). 10. Carefully insert fireplace into cabinet  mantel (see Figure 13). Be careful not to 5. Slide other end of adjusting plate/shim  scratch or damage hearth base or cabinet in slot on mitered edge of side trim (see  mantel. Figure 14). 11. Place metal trim on shoulder screws locat- 6. While firmly ho
                    
                    Краткое содержание страницы № 14 
                    
                        3 2 1 InsT alla TIon Continued  Note: If you do not have a short Phillips 4. Carefully disconnect green and white  screwdriver, the screen, log set, and wires at their insulated connectors. branch support must be removed so a  5. In top of heater cabinet, locate 4 mounting  longer screwdriver may be used. See  holes on outer casing. Align these 4 holes  Connecting Equipment Shutoff Valve to  with those on blower bracket assembly.  Heater Control, page 17, steps 1 and 2. Attach blower bracket ass
                    
                    Краткое содержание страницы № 15 
                    
                        InsT alla TIon Continued  Note: When switch is in AUTO position, 4. A licensed electrician must follow the wir- fan will start after heater has run for a ing diagram to connect incoming electri- few moments. Fan will continue to run cal supply to fan kit wiring harness (see  for several moments after heater has Figure 19). been turned off. When switch is in the  5. Plug power cord to the outlet receptacle  ON position, fan will run until turned to  (not provided) as shown in Figure 18.  OFF. Rei
                    
                    Краткое содержание страницы № 16 
                    
                        3 2 1 InsT alla TIon Continued Blower Bracket  Wire Harness Assembly   CAUTION: Never connect pro- pane/LP fireplace directly to the  Screw  propane/LP supply. This fireplace  requires an external regulator  (not supplied). Install the external  regulator between the fireplace  Switch Plate  and propane/LP supply. Power  Switch Cord  Outlet   WARNING: Never connect  Receptacle  natural gas fireplace to private  (non-utility) gas wells. This  Red gas is commonly known as  Blue wellhead gas. Plast
                    
                    Краткое содержание страницы № 17 
                    
                        InsT alla TIon Continued Installation must include an equipment shutoff 2. Remove screws that attach branch sup- valve, union, and plugged 1/8" NPT tap. Lo- port to fireplace (see Figure 23). Carefully  cate NPT tap within reach for test gauge hook lift up branch support and remove from  up. NPT tap must be upstream from fireplace fireplace (see Figure 23). (see Figure 22). 3. Route flexible gas line included from fire- IMPORTANT: Install equipment shutoff valve place control to equipment shutof
                    
                    Краткое содержание страницы № 18 
                    
                        InsT alla TIon Continued 6. Replace branch support back into fire- PRESSURE TESTING GAS SUPPLY  place. Feed flexible gas line into fireplace PIPING SYSTEM base area while replacing branch support.  Test Pressures In Excess Of 1/2 PSIG  Make sure the entire flexible gas line is  (3.5 kPa) in fireplace base area. Reattach branch  1. Disconnect appliance with its appliance  support to fireplace with screws removed  main gas valve (control valve) and equip- in step 2, page 17. ment shutoff valve fro
                    
                    Краткое содержание страницы № 19 
                    
                        InsT alla TIon Continued Equipment PRESSURE TESTING FIREPLACE GAS  Shutoff Valve CONNECTIONS 1. Open equipment shutoff valve (see Figure  Propane/LP  25, page 18). Supply Tank 2. Open main gas valve located on or near  gas meter for natural gas or open pro- pane/LP supply tank valve. 3. Make sure control knob of fireplace is in  the OFF position. 4. Check all joints from equipment shutoff  valve to thermostat gas valve (see Fig- ures 26 and 27). Apply a noncorrosive  Figure 26 - Checking Gas Joi
                    
                    Краткое содержание страницы № 20 
                    
                        oPeRa TIon Continued  Note: If pilot does not stay lit, refer to  LIGHTING  Troubleshooting, page 24. Also contact a  INSTRUCTIONS qualified service person or gas supplier for  repairs. Until repairs are made, light pilot   WARNING: You must operate  with match. To light pilot with match, see  this fireplace with the fireplace  Manual Lighting Procedure, page 21. screen in place. Make sure fire- 7. Keep control knob pressed in for 30 sec- place screen is installed before  onds after lighting pil