                        DIRECT-VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
NATURAL GAS “TUDOR” MODEL (V)T36ENA SERIES
PROPANE/LP GAS “TUDOR” MODEL (V)T36EPA SERIES
WARNING: If the information in this manual is not fol-
lowed exactly, a fire or explosion may result causing 
property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable 
vapors and liquids in the vicinity of this or any other 
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
•
                    
                    Краткое содержание страницы № 2 
                    
                        TALE b OF CONTENTS Safety Information ............................................... 2 Inspecting Burners............................................. 29 Local Codes......................................................... 4 Cleaning and Maintenance ................................ 30 Product Identification ........................................... 4 Troubleshooting  ................................................ 31 Product Features ................................................. 4 Illust
                    
                    Краткое содержание страницы № 3 
                    
                        SAFETy INFORMATION  WARNING: Do not allow fans  Continued to blow directly into the fireplace.  This fireplace must be installed by a qualified (cer- Avoid any drafts that alter burner  tified or licensed) service person. It has a sealed  flame patterns. gas combustion chamber that uses a coaxial pipe  (pipe within a pipe and having the same center)  venting system. It brings in fresh air for combus- Due to high temperatures, the  tion through the outer pipe and combustion gases  appliance shoul
                    
                    Краткое содержание страницы № 4 
                    
                        SAFETy INFORMATION LOCAL CODES Continued Install and use fireplace with care. Follow all local  codes. In the absence to local codes, use the cur- 2. If you smell gas rent National Fuel Gas Code ANSI Z223.1/NFPA  • shut off gas supply 54* (USA) or the current CSA-B149.1 Installation  • do not try to light any appliance Code (Canada). • do not touch any electrical switch; do not use  *Available from: any phone in your building American National Standards Institute, Inc. • immediately call your ga
                    
                    Краткое содержание страницы № 5 
                    
                        • Your fireplace is designed to be used in zero clear- PRODUCT FEATURES ance installations. Wall or framing material can be  Continued placed directly against any exterior surface on the  • The blower requires electricity if installed and  back, sides or top of your fireplace, except where  if you plan to install the blower at a later date,  standoff spacers are integrally attached. If standoff  do not forget to wire the outlet at the bottom of  spacers are attached to your fireplace, these spac
                    
                    Краткое содержание страницы № 6 
                    
                        PRE-INSTALLATION  PREPARATION Continued CLEARANCES Minimum clearances to combustibles for the fire- place are as follows: *Back and sides 0" 1 3 / " 8 Perpendicular walls 6" Floor 0" 1 Ceiling to louver opening 42" 41 /4" 1 Front 36" 23 / " 2 Top of Standoffs 0" Figure 4 - Framing Clearances for  Vent (See venting  Installation Against an Exterior Wall  instructions for specific   venting clearances.) Combustible material with a maximum thickness of  5 D 3 15" B 49 C /8" 10 /8" 5/8" may be flus
                    
                    Краткое содержание страницы № 7 
                    
                        V G G V A E D V B L LOCATION OF TERMINATION CAP N N H C I B Fixed V V Fixed Openable Closed Closed Openable B F V G V J X B B M A V K X TERMINATION CAP G GAS METER RESTRICTED AREA V X AIR SUPPLY INLET (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or I = clearance to service regulator vent outlet [*72" (182.9 cm)   balcony [*12" (30.5 cm) minimum]  minimum] B =  clearance to window or door that may be opened J = clearance to non-mechanical air supply inlet to building 
                    
                    Краткое содержание страницы № 8 
                    
                        VENTING INSTALLATION   WARNING: Read all instruc- INSTRUCTIONS tions completely and thoroughly  NOTICE: Read these instruc- before attempting installation.  tions completely before at- Failure to do so could result in  serious injury, property damage  tempting installation. or loss of life.  These models are tested and approved for use with  DESA (direct-vent) pipe components and termina- NOTICE: Failure to follow these in- tions as well as Simpson-Duravent direct-vent pipe  structions will void
                    
                    Краткое содержание страницы № 9 
                    
                        5. Carefully determine the location where the  VENTING INSTALLATION  vent pipe assembly will penetrate the outside  INSTRUCTIONS wall. The center of the hole should line up  Continued with the center-line of the horizontal vent pipe.  Mark the wall for a 10" x 10" square hole. Cut  INSTALLATION LANNING p and frame the square hole in the exterior wall  There are two basic types of direct-vent in- where the vent will be terminated. If the wall  stallation: being penetrated is constructed of noncom
                    
                    Краткое содержание страницы № 10 
                    
                        VENTING INSTALLATION  Apply Mastic to  INSTRUCTIONS All Four Sides Continued Vent Cap  WARNING: Do not recess  vent termination into any wall.  This will cause a fire hazard. 6. Noncombustible Exterior Wall: Position the  3 horizontal vent cap in the center of the 7 /4"	 round hole and attach to the exterior wall with  four wood screws provided. Before attaching  the vent cap to exterior wall, run a bead of  Wood Screw non-hardening mastic (pliable sealant) around  Figure 10 - Installing Horizon
                    
                    Краткое содержание страницы № 11 
                    
                        GROUND FLOOR INSTALLATION VENTING INSTALLATION  Recommended Applications: INSTRUCTIONS • Installation using cabinet surrounds Continued • Through the wall using round or square termina- Minimum Pipe  Siding Standoff tion (up to 12" horizontal pipe) 1 Overlap 1 /4" • NOT FOR CORNER INSTALLATION Direct-Vent  Adjustable  Pipe Horizontal  Screws Pipe 12" Max. 45° Elbow High Wind  Square  Wall  Termination Firestop Wall Firestop Maintain 1"  Minimum Air  High Wind  Space Around  Termination Outer Pip
                    
                    Краткое содержание страницы № 12 
                    
                        VENTING INSTALLATION INSTRUCTIONS Continued CORNER AND ALTERNATE INSTALLATION Not to Exceed  (H) Limits Recommended Applications: Square  Termination • Corner ground floor installation 90° Elbow • Ground floor installation where pipe vents horizon- tally through wall (over 12" horizontal pipe) • Basement installation where one foot clearance  from ground to termination is possible Wall  90° Elbow 12" Min. Not to Exceed (H) Limits Firestop Square  As Required  Termination  for (V), See  Chart for
                    
                    Краткое содержание страницы № 13 
                    
                        VENTING INSTALLATION INSTRUCTIONS Continued HORIZONTAL SYSTEM INSTALLATION  USING TWO 90° ELBOWS The following configurations show the minimum  vertical rise requirements for a horizontal system  using two 90° elbows. 45° Elbow Venting with Two 90° Elbows Horizontal (H ) +  1 Vertical (V) Horizontal (H ) Horizontal (H ) 1 2 5' min. 2' max. ' max. ' min. 4' max. 12' max. 7' min. ' max. 18' max. 8' min. 8' max. 20' max. 20' max. 8' max. 20' max. Figure 17 - Horizontal Termination Configuration 
                    
                    Краткое содержание страницы № 14 
                    
                        Flat Ceiling Installation VENTING INSTALLATION  1. Cut a 10" square hole in the ceiling using the  INSTRUCTIONS locating hole as a center point. The opening  Continued should be framed to 10" x 10" inside dimen- sions, as shown in Figure 9 on page 9 using  INSTALLATION FOR vERTICAL  framing lumber the same size as the ceiling  TERMINATION joists. If the area above the ceiling is an insu- Note: Vertical restrictor must be installed in all  lated ceiling or attic space, nail firestop from  vertica
                    
                    Краткое содержание страницы № 15 
                    
                        Vertical Termination Configurations VENTING INSTALLATION  Figures 21 through 24 show four different con- INSTRUCTIONS figurations for vertical termination.  Continued Venting with Two 90° Elbows 5. Place the flashing over the pipe section(s)  Horizontal (H ) +  1 extending through the roof. Secure the base of  Vertical (V) Horizontal (H ) 2 the flashing to the roof and framing with roof- 5' min. 2' max. ing nails. Be sure roofing material overlaps the  ' min. 4' max. top edge of the flashing as
                    
                    Краткое содержание страницы № 16 
                    
                        VENTING INSTALLATION  INSTRUCTIONS Continued Vertical Venting V = 40' max. Note: Install  restrictor into  Note: Install  inner collar of  restrictor into  fireplace as  inner collar of  shown. fireplace as  shown. 45° Elbow 45° Elbow Venting with Two 90° Elbows Figure 24 - Vertical Venting  vertical (v ) Horizontal (H) 1 Configuration With No Horizontal Run  5' min. ' max. (Vertical Round High Wind Termination  ' min. 12' max. Shown) 7' min. 18' max. 8' min. 20' max. HIGH ALTITUDE INSTALLATIO
                    
                    Краткое содержание страницы № 17 
                    
                        Number Description VENTING INSTALLATION  HTK Horizontal Round Termination Kit INSTRUCTIONS  (Includes: Round Termination,   Continued  Wall Firestop and 45° Elbow) PARTS LIST FOR VENTING KITS  HTKS-47 Horizontal Square Termination Kit   AND COMpONENTS (Includes: Square Termination,    Wall Firestop, 45° Elbow) DESA Pipe & Vent Kits DESA Elbows Number Description Number Description P47- " Section Coaxial Pipe,   Galvanized E47-45 45° Elbow, Galvanized P47-12 12" Section Coaxial Pipe, E47-90 90°
                    
                    Краткое содержание страницы № 18 
                    
                        6.  While supporting speed control, secure control  FIREPLACE  shaft with lock nut by pushing and turning  INSTALLATION lock nut with pliers clockwise until it is tight  against front panel. Place control knob pro- CHECK GAS TYPE vided on shaft. Use proper gas type for fireplace unit you are  7.  Turn on power to duplex outlet if previously  installing. If your gas supply is not correct, do not  turned off per the warning above. install fireplace. See retailer where you purchased  the fireplace 
                    
                    Краткое содержание страницы № 19 
                    
                        4.  Be certain that all wire terminals are securely  FIREPLACE  attached to terminals on blower motor and  INSTALLATION thermal switch, and that screw for thermodisc  Continued bracket and green ground wire is tight.  5.  Mount speed control box against mounting  9. Check to make sure power cord is completely  plate provided in lower fireplace cavity by  clear of blower wheel and there are no other  foreign objects in blower wheel. Turn blower placing plastic control shaft forward through  round
                    
                    Краткое содержание страницы № 20 
                    
                        Installation Items Needed FIREPLACE  Before installing fireplace, make sure you have the  INSTALLATION items listed below. Continued • external regulator (supplied by installer) 11.  Peel off backing paper and stick supplied  • piping (check local codes) wiring diagram decal on firebox bottom ap- • sealant (resistant to propane/LP gas) proximately 12" in front of blower (see Figure  • equipment shutoff valve * 27, page 19).  • test gauge connection * • sediment trap Blower Wiring Diagram • tee j