Краткое содержание страницы № 1 
                    
                        TECHNICAL & SERVICE MANUAL
INDOOR UNIT : KMS0772
FILE NO.
KMS0972
KMS1272
KMS1872
KMS2472
Destination: North America
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
Capacity Indoor Model No. Product Code No.
7,500BTU / h KMS0772 1 852 099 87
9,000BTU / h KMS0972 1 852 099 88
11,900BTU / h KMS1272 1 852 099 89
17,500BTU / h KMS1872 1 852 099 90
24,200BTU / h KMS2472 1 852 099 91
Wall Mounted Type Indoor Unit
< Applicable Multi-Outdoor Units >
CM1972 (3-room multi unit)
CM2472 (4-room multi unit)
CM3172 
                    
                    Краткое содержание страницы № 2 
                    
                        When Transporting Important!  Be careful when picking up and moving the indoor and  Please Read Before Starting outdoor units. Get a partner to help, and bend your knees  when lifting to reduce strain on your back. Sharp edges or thin  This air conditioning system meets strict safety and operating  aluminum fins on the air conditioner can cut your fingers.  standards. As the installer or service person, it is an  important part of your job to install or service the system so it When Installing o
                    
                    Краткое содержание страницы № 3 
                    
                        Table of Contents Page ................................................................................... 4     APPLICABLE MULTI-OUTDOOR UNITS ................................................................................................................... 5 1. OPERATING RANGE 2. SPECIFICATIONS ............................................................................................................. 6 2-1.    Unit Specifications  ............................................................
                    
                    Краткое содержание страницы № 4 
                    
                            APPLICABLE MULTI-OUTDOOR UNITS Multi-Outdoor Unit 3-Room 4-Room 4-Room 3-Room 4-Room 4-Room CM1972 CM2472 CM3172 CLM1972 CLM2472 CLM3172 Indoor Unit KMS0772 YES YES YES YES YES YES KMS0972 YES YES YES YES YES YES KMS1272 YES YES YES YES YES YES KMS1872 YES YES YES YES YES YES KMS2472 NO YES YES NO YES YES 4                                                                                                                                                                                            
                    
                    Краткое содержание страницы № 5 
                    
                        1.  OPERATING RANGE Combination with cooling outdoor unit CM1972, CM2472 or CM3172 Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95 °F D.B. / 71 °F W.B. 115 °F D.B. Cooling Minimum 67 °F D.B. / 57 °F W.B.  67 °F D.B. Combination with low ambient cooling outdoor unit CLM1972, CLM2472 or CM3172 Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95 °F D.B. / 71 °F W.B. 115 °F D.B. Cooling Minimum 67 °F D.B. / 57 °F W.B.  *1 *1 32 °F D.B.: When combined with 
                    
                    Краткое содержание страницы № 6 
                    
                        2.  SPECIFICATIONS 2-1.  Unit Specifications Indoor Unit KMS0772 < 230V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 230V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 7,500 kW 2.20 3 3  Air Circulation  (High) ft /min (m /h) 241 (410)  Moisture Removal  (High) Pints/h 2.77  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.11  Power Input W 25  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remo
                    
                    Краткое содержание страницы № 7 
                    
                        Indoor Unit KMS0772                                                                                                                                                  < 208V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 208V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 7,500 kW 2.20 3 3  Air Circulation  (High) ft /min (m /h) 241 (410)  Moisture Removal  (High) Pints/h 2.77  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.12  Power Input W 25 
                    
                    Краткое содержание страницы № 8 
                    
                        Indoor Unit KMS0972 < 230V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 230V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 9,000 kW 2.65 3 3  Air Circulation  (High) ft /min (m /h) 259 (440)  Moisture Removal  (High) Pints/h 3.4  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.15  Power Input W 35  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Time
                    
                    Краткое содержание страницы № 9 
                    
                        Indoor Unit KMS0972 < 208V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 208V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 9,000 kW 2.65 3 3  Air Circulation  (High) ft /min (m /h) 259 (440)  Moisture Removal  (High) Pints/h 3.4  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.17  Power Input W 35  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Time
                    
                    Краткое содержание страницы № 10 
                    
                        Indoor Unit KMS1272 < 230V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 230V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 11,900 kW 3.50 3 3  Air Circulation  (High) ft /min (m /h) 282 (480)  Moisture Removal  (High) Pints/h 4.26  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.15  Power Input W 35  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Ti
                    
                    Краткое содержание страницы № 11 
                    
                        Indoor Unit KMS1272 < 208V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 208V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 11,900 kW 3.50 3 3  Air Circulation  (High) ft /min (m /h) 282 (480)  Moisture Removal  (High) Pints/h 4.26  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.17  Power Input W 35  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Ti
                    
                    Краткое содержание страницы № 12 
                    
                        Indoor Unit KMS1872 < 230V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 230V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 17,500 kW 5.15 3 3  Air Circulation  (High) ft /min (m /h) 500 (850)  Moisture Removal  (High) Pints/h 4.89  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.15  Power Input W 35  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Ti
                    
                    Краткое содержание страницы № 13 
                    
                        Indoor Unit KMS1872 < 208V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 208V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 17,500 kW 5.15 3 3  Air Circulation  (High) ft /min (m /h) 500 (850)  Moisture Removal  (High) Pints/h 4.89  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.17  Power Input W 35  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Ti
                    
                    Краткое содержание страницы № 14 
                    
                        Indoor Unit KMS2472 < 230V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 230V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 24,200 kW 7.10 3 3  Air Circulation  (High) ft /min (m /h) 541 (920)  Moisture Removal  (High) Pints/h 4.89  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.20  Power Input W 45  Features  Control / Temperature Control Microprocessor / I.C. Thermister  Control Unit Wireless Remote Control Unit  Timer 24-Hour ON or OFF Ti
                    
                    Краткое содержание страницы № 15 
                    
                        Indoor Unit KMS2472                                                                                                                                                  < 208V >  Type Wall Mounted Type Indoor Unit  Voltage Rating 208V Single-Phase 60Hz  Performance Cooling  Capacity BTU/h 24,200 kW 7.10 3 3  Air Circulation  (High) ft /min (m /h) 541 (920)  Moisture Removal  (High) Pints/h 4.89  Electrical Rating Cooling  Available Voltage Range V 187 to 253  Running Amperes A 0.22  Power Input W 45
                    
                    Краткое содержание страницы № 16 
                    
                        2-2.  Major Component Specifications 2-2-1.  Indoor Unit Indoor Unit KMS0772  Control PCB  Part No. CB-KMS0772  Controls Microprocessor  Control Circuit Fuse 250V 3A  Remote Control Unit RCS-4VPIS4U  Fan  Type Cross-Flow  Q'ty ... Dia. and Length inch (mm) 1 ... D3-11/16 /  L24-31/ 32 (D94 / L634)  Fan Motor  Type DC Motor  Model ... Q'ty SIC-39CVL-D847-4 ... 1  No. of Poles 8  Rough Measure RPM (Cool) 1,050  Nominal Output W 47  Coil Resistance Ohm - o o  (Ambient Temp. 68 F (20 C))  Safety Devi
                    
                    Краткое содержание страницы № 17 
                    
                        Indoor Unit KMS0972  Control PCB  Part No. CB-KMS0972  Controls Microprocessor  Control Circuit Fuse 250V 3A  Remote Control Unit RCS-4VPIS4U  Fan  Type Cross-Flow  Q'ty ... Dia. and Length inch (mm) 1 ... D3-11/16 /  L24-31/ 32 (D94 / L634)  Fan Motor  Type DC Motor  Model ... Q'ty SIC-39CVL-D847-4 ... 1  No. of Poles 8  Rough Measure RPM (Cool) 1,100  Nominal Output W 47  Coil Resistance Ohm - o o  (Ambient Temp. 68 F (20 C))  Safety Device Type Internal Controller Over- Current Protection Yes
                    
                    Краткое содержание страницы № 18 
                    
                        Indoor Unit KMS1272  Control PCB  Part No. CB-KMS1272  Controls Microprocessor  Control Circuit Fuse 250V 3A  Remote Control Unit RCS-4VPIS4U  Fan  Type Cross-Flow  Q'ty ... Dia. and Length inch (mm) 1 ... D3-11/16 /  L24-31/ 32 (D94 / L634)  Fan Motor  Type DC Motor  Model ... Q'ty SIC-39CVL-D847-4 ... 1  No. of Poles 8  Rough Measure RPM (Cool) 1,200  Nominal Output W 47  Coil Resistance Ohm - o o  (Ambient Temp. 68 F (20 C))  Safety Device Type Internal Controller Over- Current Protection Yes
                    
                    Краткое содержание страницы № 19 
                    
                        Indoor Unit KMS1872  Control PCB  Part No. CB-KMS1872  Controls Microprocessor  Control Circuit Fuse 250V 3A  Remote Control Unit RCS-4VPIS4U  Fan  Type Cross-Flow  Q'ty ... Dia. and Length inch (mm) 1 ... D3-11/16 /  L33-9/ 32 (D94 / L845)  Fan Motor  Type DC Motor  Model ... Q'ty SIC-39CVL-D847-2 ... 1  No. of Poles 8  Rough Measure RPM (Cool) 1,200  Nominal Output W 30  Coil Resistance Ohm - o o  (Ambient Temp. 68 F (20 C))  Safety Device Type Internal Controller Over- Current Protection Yes 
                    
                    Краткое содержание страницы № 20 
                    
                        Indoor Unit KMS2472  Control PCB  Part No. CB-KMS2472  Controls Microprocessor  Control Circuit Fuse 250V 3A  Remote Control Unit RCS-4VPIS4U  Fan  Type Cross-Flow  Q'ty ... Dia. and Length inch (mm) 1 ... D3-11/16 /  L33-9/ 32 (D94 / L845)  Fan Motor  Type DC Motor  Model ... Q'ty SIC-39CVL-D847-2 ... 1  No. of Poles 8  Rough Measure RPM (Cool) 1,300  Nominal Output W 30  Coil Resistance Ohm - o o  (Ambient Temp. 68 F (20 C))  Safety Device Type Internal Controller Over- Current Protection Yes