Instruction Manual
AC2675
REVISION A 
 
 
 
8200 Series Base Mounted 
Centrifugal Fire Pumps 
Installation, Operation and Service Instructions 
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE. 
 
1                                                                                                                                                                                                                                                                                                     
                    
                    Inhaltszusammenfassung zur Seite Nr. 2 
                    
                        TABLE OF CONTENTS DESCRIPTION......................................................3 MAINTENANCE TIME TABLE........................... 19  OPERATIONAL LIMITS .......................................3 TROUBLE SHOOTING ...................................... 20  MAXIMUM WORKING PRESSURE.....................3 CHANGING ROTATION .................................... 23  SEAL OPERATING LIMITS .................................3 SERVICE INSTRUCTIONS ................................ 24  PACKING ............
                    
                    Inhaltszusammenfassung zur Seite Nr. 3 
                    
                        DESCRIPTION PUMP IDENTIFICATION  The 8200 Series Centrifugal Fire Pumps are There are two identification plates on each  framed mounted pumps which feature – high pump. The pump rating plate gives  efficiency, rugged construction, compact identification and rating information. Figure 1  design, foot mounted volute and regreasable  shows an example of a typical Rating Plate.  bearings. These features, along with the  Permanent records for this pump are  horizontal split case, make installation,  
                    
                    Inhaltszusammenfassung zur Seite Nr. 4 
                    
                        ADDITIONAL SAFETY REQUIREMENTS:  SAFETY INSTRUCTIONS  1. Electrical connections to be made by  qualified Electrician in accordance with all   SAFETY INSTRUCTIONS national, state and local codes.  This safety alert symbol will be used in this  2. Motor must have properly sized starter  manual and on the pump safety instruction decals  with properly sized heaters to provide  to draw attention to safety related instructions.  overload and undervoltage protection.  When used the safety alert symbol 
                    
                    Inhaltszusammenfassung zur Seite Nr. 5 
                    
                        ADDITIONAL SAFETY REQUIREMENTS:  MECHANICAL SAFETY:  ELECTRICAL SAFETY:  WARNING: Unexpected Startup Hazard   WARNING: Electrical Shock Hazard   Disconnect and lockout power before  Electrical connections to be made by a  servicing. Failure to follow these instructions could  qualified electrician in accordance with all  result in serious personal injury or death, and  applicable codes, ordinances, and good practices.  property damage.  Failure to follow these instructions could result in    ser
                    
                    Inhaltszusammenfassung zur Seite Nr. 6 
                    
                        INSTALLATION  PUMP LOCATION  NYLON SLING,  CHAIN OR WIRE  Locate the pump so there is sufficient room  ROPE  for inspection, maintenance and service. If  the use of a hoist or tackle is needed, allow  ample head room.  WARNING: Falling Objects Hazard  Eyebolts or lifting lugs, if provided, are for  lifting only the components to which they are  CHOKER  HITCH  attached. Failure to follow these instructions could  AROUND  BEARING  result in serious personal injury or death, or  FRAME  property dam
                    
                    Inhaltszusammenfassung zur Seite Nr. 7 
                    
                        installation. ITT AC Fire Pump Systems has collect should be blown out with compressed  determined that proper and correct alignment air.  can only be made by accepted erection  Make sure there is a suitable power source  practices. Refer to the following paragraphs  available for the pump driver. If motor driven,  on “Foundation,” “Base Plate Setting,”  electrical characteristics should be identical to  “Grouting Procedure,” “Alignment Procedure”  those shown on motor data plate.  and “Doweling
                    
                    Inhaltszusammenfassung zur Seite Nr. 8 
                    
                        operator). Final alignment procedures are  BASE PLATE SETTING (BEFORE PIPING)  covered under “Alignment Procedures.”  NOTE: This procedure assumes that a  e. Check to make sure the piping can be  concrete foundation has been prepared with  aligned to the pump flanges without  anchor or hold down bolts extending up ready  placing pipe strain on either flange.  to receive unit. It must be understood that  pump and motor have been mounted and  f. Grout in base plate completely (See  rough aligned a
                    
                    Inhaltszusammenfassung zur Seite Nr. 9 
                    
                        vibration, and bearing loads that result in c. Remove the capscrew that holds the inner  premature bearing failure and ultimate seizing guard to the support bracket.  of the pump. Misalignment can be angular,  d. Spread the inner guard and pull it over the  parallel, or a combination of these, and in the  coupler.  horizontal and vertical planes. Final alignment  should be made by moving and shimming the  Installation  motor on the base plate, until the coupling  hubs are within the recommended 
                    
                    Inhaltszusammenfassung zur Seite Nr. 10 
                    
                        ANSI/OSHA Coupling Guard Exploded View  For Typical 8200 Series Fire Pump Installation  INNER GUARD  OUTER GUARD  ATTACH SUPPORT BRACKET  TO BEARING HOUSING  SUPPORT  BRACKET  LOCATE SUPPORT ARM  BETWEEN OUTER GUARD ENDS.  ALIGN THE ARM WITH HOLES IN  THE OUTER GUARD AND HOLES  IN THE SADDLE BRACKET.   NUT  BRACKET SUPPORT  BRACKET  LOCKWASHER  ATTACHED INSIDE HERE  SUPPORT  CAPSCREW  IN LINE WITH BOLT  FLAT WASHER  SPACER WASHER  MOTOR SADDLE  THIS OPTION USED IN PLACE OF SPACER WHERE BRACKET A
                    
                    Inhaltszusammenfassung zur Seite Nr. 11 
                    
                        Final Alignment  Method 2 – For Orange Hytrel Insert, 3500  Final alignment cannot be accomplished until  RPM Operation, or All Other Coupler  the pump has been operated initially for a  Types   sufficient length of time to attain operating  (See Figure 7B)  temperature. When normal operating  a. Make sure each hub is secured to its  temperature has been attained, secure the  respective shaft and that all connecting pump to re-check alignment and compensate  and/or spacing elements are removed a
                    
                    Inhaltszusammenfassung zur Seite Nr. 12 
                    
                        and properly aligned, so that no strain is  SUCTION PIPE INSTALLED WITH A CHECK VALVE  transmitted to the pump when the flange bolts GRADUAL RISE TO PUMP  GATE VALVE  are tightened. Use pipe hangers or other  INCREASER  supports at necessary intervals to provide  LEVEL  support. When expansion joints are used in  the piping system, they must be installed  CORRECT  CENTER LINE  beyond the piping supports closest to the  OF PIPE pump. Tie bolts should be used with  AIR POCKET  expansion joints to 
                    
                    Inhaltszusammenfassung zur Seite Nr. 13 
                    
                        Suction piping should be short in length, as spring type, sized to avoid excessive  direct as possible, and never smaller in friction in the suction line. (Under all other  diameter than the pump suction opening. A conditions, a check valve, if used, should  minimum of ten (10) pipe diameters between be installed in the discharge line.) (See  any elbow or tee and the pump should be “Valves in Discharge Piping”)  allowed. If a long suction pipe is required, it  b. When foot valves are used, or wh
                    
                    Inhaltszusammenfassung zur Seite Nr. 14 
                    
                        lubricate packing. Only when all of the  Pressure Gauges  following conditions prevail, can this be done:  Properly sized pressure gauges should be  1. Liquid is clean, free from sediment and  installed in both the suction and discharge  chemical precipitation and is compatible  nozzles in the gauge taps provided. The  with seal materials.  gauges will enable the operator to easily  observe the operation of the pump, and also  2. Temperature is above 32°F and below  determine if the pump is oper
                    
                    Inhaltszusammenfassung zur Seite Nr. 15 
                    
                        box. Excess pressure from an external  source can be very destructive to packing.  More pressure is required, however, for  abrasive slurries than for clear liquids.  Examination of the leakage will indicate  whether to increase or decrease external  pressure. If slurry is present in the leakage,  increase the pressure until only clear liquid  drips from the box. If the drippage is corrosive  or harmful to personnel, it should be collected  and piped away.  A common error is to open the external
                    
                    Inhaltszusammenfassung zur Seite Nr. 16 
                    
                        OPERATION    WARNING: Rotating Components  WARNING: Unexpected Startup Hazard  Hazard  Disconnect and lockout power before  Do not operate pump without all guards in place.  servicing. Failure to follow these instructions could  Failure to follow these instructions could result in  result in serious personal injury or death, or  serious personal injury or death and property  property damage.  damage.      WARNING: Electrical Shock Hazard  CAUTION: Seal Damage Hazard  Electrical connections to be
                    
                    Inhaltszusammenfassung zur Seite Nr. 17 
                    
                        b. Check and record pressure gauge  CAUTION: Bearing/Seal Damage Hazard  readings for future reference.  Do not let heated pump temperature rise  above 150°F. Failure to follow these instructions  c. Check and record voltage, amperage per  could result in property damage and/or moderate  phase, and kw if an indicating wattmeter is  personal injury.  available.    d. Check bearings for lubrication and  FIELD TESTING  temperature. Normal temperature is 180°  A typical performance curve for a speci
                    
                    Inhaltszusammenfassung zur Seite Nr. 18 
                    
                        Bearings are a primary concern on pumping greases are Texaco Multifak No. 2 and  units. First, dismantle the bearings; clean and Mobilux No. 2 grease.  inspect them for any rusted or badly worn  Greases made from animal or vegetable oils  surfaces. If bearings are free from rust and  are not recommended due to the danger of  wear, reassemble and relubricate them with  deterioration and forming of acid. Do not use  one of the recommended pump lubricants.  graphite. Use of an ISO VG 100 mineral ba
                    
                    Inhaltszusammenfassung zur Seite Nr. 19 
                    
                        MAINTENANCE TIME TABLE  EVERY MONTH Check bearing temperature with a thermometer, not by hand. If bearings are  running hot (over 180°F), it may be the result of too much lubricant. If changing the  lubricant does not correct the condition, disassembly and inspect the bearings. Lip  seals bearing on the shaft may also cause the housing to run hot. Lubricate lip  seals to correct.  EVERY 3 Check grease lubricated bearings for saponification. This condition is usually  caused by the infiltration o
                    
                    Inhaltszusammenfassung zur Seite Nr. 20 
                    
                        TROUBLE SHOOTING  Between regular maintenance inspections, be alert for signs of motor or pump trouble. Common  symptoms are listed below. Correct any trouble immediately and AVOID COSTLY REPAIR AND  SHUTDOWN.  CAUSES CURES  No Liquid Delivered  1. Lack of prime. Fill pump and suction pipe completely with liquid.  2. Loss of prime. Check for leaks in suction pipe joints and fittings; vent casing to remove  accumulated air. Check mechanical seal or packing.  3. Suction lift too high (a If there i