ページ18に含まれる内容の要旨
036-21570-002 Rev. D (0605) HEATING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA03011 INDOOR COIL MODEL NO. G2FD030S17 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 800 1000 1200 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 37.8 2.9 3.8 37.2 2.9 3.8 36.6 2.8 3.9 60 70 36.1 3.1 3.5 35.9 3.0 3.5 35.8 2.9 3.6 80 34.5 3.2 3.2 34.7 3.1 3.3 34.9 3.0 3.4 60 33.5 2.7 3.7 33.1 2.6 3.7 32.7 2.5 3.8 47 70 28.6 2.7 3.1 30.0 2.7 3.3 31.4 2.6 3.5 80 23.6 2.8 2.5 26.9 2.7 2.9
ページ19に含まれる内容の要旨
036-21570-002 Rev. D (0605) HEATING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA03611 INDOOR COIL MODEL NO. G2FD036S17 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 1000 1200 1400 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 41.2 3.0 4.0 42.8 2.9 4.3 44.4 2.9 4.6 60 70 38.4 3.2 3.5 39.8 3.1 3.8 41.3 3.0 4.0 80 35.6 3.3 3.1 36.9 3.3 3.3 38.1 3.2 3.5 60 37.0 2.8 3.8 38.1 2.8 4.0 39.1 2.7 4.3 47 70 34.0 3.0 3.3 35.2 2.9 3.5 36.4 2.8 3.7 80 31.0 3.1 2.9 32.3 3.1 3.
ページ20に含まれる内容の要旨
036-21570-002 Rev. D (0605) HEATING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA04211 INDOOR COIL MODEL NO. G2FD048S21 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 1200 1400 1600 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 49.8 3.6 4.1 50.8 3.4 4.4 51.9 3.3 4.6 60 70 47.2 3.9 3.6 48.2 3.7 3.8 49.2 3.6 4.0 80 44.7 4.2 3.1 45.7 4.1 3.3 46.6 3.9 3.5 60 43.7 3.3 3.9 44.5 3.2 4.1 45.3 3.1 4.3 47 70 41.3 3.6 3.3 42.0 3.5 3.5 42.7 3.4 3.7 80 38.9 4.0 2.9 39.5 3.8 3.
ページ1に含まれる内容の要旨
P
G
M
U
Y
P
L
T
P
A
CE
OM
H
E
S C
R
T
I
F
I A
E
R
I
R
Q
A
I
CA
A
S T
T
U
A
I
O
I
N
O
036-21570-002 Rev. D (0605)
DESCRIPTION
The YMA Series unit is the outdoor part of a versatile heat pump
system. It is designed to be custom matched with one of our
complete line of evaporator sections, each designed to serve a
specific function. Matching air handlers are available for upflow,
downflow, and horizontal left or right application to provide a
complete system. Electric heaters are available if requi
ページ2に含まれる内容の要旨
036-21570-002 Rev. D (0605) Physical and Electrical Data MODEL YMA02411 YMA03011 YMA03611 YMA04211 YMA04811 YMA06011 Unit Supply Voltage 208-230V, 1 φ, 60Hz 1 187 to 252 Normal Voltage Range Minimum Circuit Ampacity 14.3 18.1 21.9 32.6 34.7 39.0 2 25 30 35 50 60 60 Max. Overcurrent Device Amps Compressor Type Recip Recip Recip Scroll Scroll Scroll Rated Load 11.1 13.3 16.4 24.9 26.6 30 Compressor Amps Locked Rotor 60 68 78 115 150 150 Crankcase Heater Yes Yes Yes No No No Fan Motor Amps Rated
ページ3に含まれる内容の要旨
036-21570-002 Rev. D (0605) Additional R-22 Charge / TXV Size for Various Matched Systems Outdoor Unit YMA02411 YMA03011 YMA03611 YMA04211 YMA04811 YMA06011 Unit Orifice (s) 63 69 78 87 - 96 1,2 1TV0701 1TV0701 1TV0702 1TV0702 1TV0703 - Approved System Thermal Expansion Valve Factory R-22 Charge, lbs-oz 7 - 2 7 - 12 8 - 6 8 - 12 9 - 1 14 - 2 3 4 Orifice - Additional Charge, Oz Indoor Coil Coil Orifice G2FD030(S,H)17 65 63/(701) + 2 69/(701) + 0 - - - G2FD035(S,H)14 65 63/(701) + 2 69/(701) + 0
ページ4に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING CAPACITY - With Air Handler Coils AIR HANDLER COOLING 1 UNIT COIL 2 RATED TOTAL SENSIBLE SEER SEER ELECTRIC MODEL MODEL MODEL W EER HEAT KW CFM CAPACITY CAPACITY W/O TXV W/ TXV 1 PH 12 SEER HP WITH N1AH / G2FD N1AHB08 2,5,8,10 17 G2FD030(S,H)17(T) 800 24.0 18.8 12.00 12.0010.90 YMA02411 N1AHB12 2,5,8,10 17 G2FD030(S,H)17(T) 800 24.0 18.8 12.00 12.0010.90 N1AHB08 2,5,8,10 17 G2FD030(S,H)17(T) 1000 30.0 23.0 12.00 12.0011.10 YMA03011 N1AHB12 2,5,8,10 17 G2FD03
ページ5に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils FURNACE** COOLING COIL UNIT MODEL CFM RANGE TOTAL SENSIBLE SEER W/O TXV SEER W/TXV MODEL WRATED CFM EER 1,2 (MIN.-MAX.) CAPACITY CAPACITY + TDR + TDR 14 G1FA036S14 800 24.2 19.1 12.00 12.00 11.00 17,21 G1FA036S17,21 800 24.0 18.8 12.00 12.00 10.90 17 G2FD030(S,H)17(T) 800 24.0 18.8 12.00 12.00 10.90 14 G2FD035(S,H)14(T) 800 24.0 18.8 12.00 12.00 10.90 600 YMA02411 17 G1NA036S17J 800 24.2 18.8 12.00
ページ6に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING CAPACITY - With Variable Speed Furnaces COOLING UNIT VARIABLE SPEED COIL W 1 RATED TOTAL SENSIBLE SEER SEER/ MODEL FURNACE MODEL MODEL EER 2 CFM CAPACITY CAPACITY W/O TXV +TDR W/TXV +TDR 3 1 PH 12 SEER HP / P1DU / P1XD / P1XU - VARIABLE SPEED P*DUA12V G1FA036S14 14 750 24.4 18.5 13.00 13.00 11.95 P*DUA12V G2FD035(S,H)14(T) 14 750 24.2 18.5 13.00 13.00 11.90 P*DUB16V G1FA036S17 17 795 24.4 19.0 13.00 13.00 11.95 P*DUB16V G2FD030(S,H)17(T) 17 795 24.4 19.0 13
ページ7に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING CAPACITY - With Variable Speed Furnaces (Continued) COOLING UNIT VARIABLE SPEED COIL W RATED TOTAL SENSIBLE SEER SEER/ 4 MODEL FURNACE MODEL MODEL EER 5 CFM CAPACITY CAPACITY W/O TXV +TDR W/TXV +TDR 6 1 PH 12 SEER HP / P1DU / P1XD / P1XU - VARIABLE SPEED P*DUC20V G1FA060S21(T) 21 1610 46.0 35.8 - 12.10 10.40 P*DUC20V G2FD060(S,H)24(T) 24 1610 46.0 35.8 - 12.10 10.40 P*DUC20V G2FD061H24 24 1500 46.0 36.2 - 12.50 10.65 P1XUC16V G1FA060S21(T) 21 1600 46.0 3
ページ8に含まれる内容の要旨
036-21570-002 Rev. D (0605) HEATING PERFORMANCE - With Air Handler 2 3 ARI HEATING OUTDOOR TEMP 1 UNIT AIR COIL 47 17.00 HSPF -3 7 27 37 57 MODEL* HANDLER MODEL MBH COP KW MBH COP KW STD MBH KW MBH KW MBH KW MBH KW MBH KW 1 PH 12 SEER HP WITH N1AH/G2FD N1AHB08 G2FD030(S,H)17(T)24.03.462.0313.82.441.668.007.01.4110.41.5315.91.7317.91.7927.42.16 YMA02411 N1AHB12 G2FD030(S,H)17(T)24.03.462.0313.82.441.668.007.01.4110.41.5315.91.7317.91.7927.42.16 N1AHB08 G2FD030(S,H)17(T)30.03.282.6817.82.442.14
ページ9に含まれる内容の要旨
036-21570-002 Rev. D (0605) HEATING PERFORMANCE - Furnace Coils 2 3 ARI HEATING OUTDOOR TEMP 1 UNIT COIL 47°F17°FHSPF -3°F 7°F27°F37°F57°F MODEL* MODEL MBH COP KW MBH COP KW STD MBH KW MBH KW MBH KW MBH KW MBH KW G1FA036S14 24.0 3.50 2.01 13.8 2.46 1.64 8.00 7.1 1.41 10.5 1.53 16.0 1.72 18.0 1.79 27.5 2.15 G1FA036S17,21 24.0 3.46 2.03 13.8 2.44 1.66 8.00 7.0 1.41 10.4 1.53 15.9 1.73 17.9 1.79 27.4 2.16 G2FD030(S,H)17(T) 24.0 3.46 2.03 13.8 2.44 1.66 8.00 7.0 1.41 10.4 1.53 15.9 1.73 17.9 1.79
ページ10に含まれる内容の要旨
036-21570-002 Rev. D (0605) ACCESSORIES* SOUND POWER RATINGS* Hard Start Kit (024-31994-000, 024-31995-000) - Provides UNIT MODEL (dBA) increased starting torque for areas with low voltage. 024 71 TXV Kits - 1TV07 series thermal expansion valves precisely 030 75 meter refrigerant for optimum performance. 036 74 Dehumidistat (2HU16700124) - Provides increased dehu- 042 74 midification when matched with variable speed furnace or air 048 75 handler. 060 75 Heat Pump Risers - (526-35389-000, 526-353
ページ11に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA02411 INDOOR COIL MODEL NO. G2FD030S17 ID CFM 600 800 1000 CONDENSER ENTERING AIR ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 TEMPERATURE ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57 T.C. 22.5 25.1 25.1 28.2 30.0 25.0 26.4 26.4 29.2 30.1 27.5 27.6 27.8 30.1 30.3 65 S.C. 24.5 21.7 18.2 18.3 14.5 27.1 25.5 20.8 19.9 14.8 29.6 29.3 23.3 21.5 15.1 K.W. 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
ページ12に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA03011 INDOOR COIL MODEL NO. G2FD030S17 ID CFM 800 1000 1200 CONDENSER ENTERING AIR ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 TEMPERATURE ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57 T.C. 29.1 32.6 32.6 35.6 35.2 31.4 33.1 35.3 35.0 34.4 33.7 33.7 38.0 34.4 33.7 65 S.C. 29.2 26.8 22.6 22.4 17.0 31.5 28.7 26.4 21.8 17.4 33.8 30.6 30.2 21.2 17.8 K.W. 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
ページ13に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA03611 INDOOR COIL MODEL NO. G2FD036S17 ID CFM 1000 1200 1400 CONDENSER ENTERING AIR ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 TEMPERATURE ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57 T.C. 34.8 38.3 37.7 41.6 40.7 37.8 39.6 39.0 42.0 40.2 40.8 40.9 40.4 42.5 39.8 65 S.C. 36.0 33.5 28.1 27.7 20.1 38.5 36.5 30.3 29.5 20.6 40.9 39.5 32.6 31.4 21.2 K.W. 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.
ページ14に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA04211 INDOOR COIL MODEL NO. G1FA048S21 ID CFM 1200 1400 1600 CONDENSER ENTERING AIR ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 TEMPERATURE ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57 T.C. 40.0 43.8 42.6 47.1 46.4 42.0 45.2 43.7 47.9 46.0 44.0 46.6 44.8 48.7 45.5 65 S.C. 42.3 38.6 32.9 32.6 23.9 44.2 42.0 35.4 34.5 24.4 46.2 45.4 37.9 36.4 24.9 K.W. 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.
ページ15に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA04811 INDOOR COIL MODEL NO. G2FA060S24 ID CFM 1400 1600 1800 CONDENSER ENTERING AIR ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 TEMPERATURE ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57 T.C. 42.8 45.7 45.8 50.3 57.2 44.6 47.0 47.0 51.5 57.3 46.3 48.3 48.1 52.8 57.5 65 S.C. 43.7 41.4 35.6 35.2 27.3 45.4 44.0 37.9 37.8 28.8 47.1 46.5 40.3 40.3 30.4 K.W. 3.1 3.1 3.1 3.2 3.2 3.1 3.1 3.1 3.2 3.2 3.
ページ16に含まれる内容の要旨
036-21570-002 Rev. D (0605) COOLING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA06011 INDOOR COIL MODEL NO. G2FA060S24 ID CFM 1600 1800 2000 CONDENSER ENTERING AIR ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 TEMPERATURE ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57 T.C. 57.6 59.5 57.0 62.3 58.7 59.1 61.0 58.3 63.3 60.1 60.6 62.5 59.5 64.2 61.5 65 S.C. 56.2 53.7 44.2 44.1 30.5 57.7 56.6 46.8 46.4 31.9 59.3 59.5 49.4 48.8 33.3 K.W. 3.5 3.6 3.6 3.6 3.6 3.5 3.6 3.6 3.6 3.6 3.
ページ17に含まれる内容の要旨
036-21570-002 Rev. D (0605) HEATING PERFORMANCE DATA OUTDOOR UNIT MODEL NO. YMA02411 INDOOR COIL MODEL NO. G2FD030S17 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 600 800 1000 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 27.2 2.2 3.5 27.3 2.1 3.7 27.4 2.0 3.9 60 70 26.8 2.3 3.4 27.1 2.2 3.5 27.4 2.1 3.7 80 26.4 2.4 3.2 26.9 2.3 3.4 27.3 2.3 3.5 60 24.9 2.0 3.6 24.6 2.0 3.7 24.4 1.9 3.8 47 70 23.7 2.1 3.3 24.0 2.0 3.5 24.3 2.0 3.6 80 22.4 2.2 3.0 23.4 2.1 3.2