Crown Boiler 32-475ECS user manual

User manual for the device Crown Boiler 32-475ECS

Device: Crown Boiler 32-475ECS
Category: Boiler
Manufacturer: Crown Boiler
Size: 1.85 MB
Added : 11/3/2014
Number of pages: 16
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Crown Boiler 32-475ECS. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Crown Boiler 32-475ECS.

For your convenience

If looking through the Crown Boiler 32-475ECS user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Crown Boiler 32-475ECS on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Crown Boiler 32-475ECS to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Crown Boiler 32-475ECS User manual - Online PDF
Advertisement
« Page 1 of 16 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Crown Boiler 32-475ECS but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Crown Boiler 32-475ECS. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

D e s i g n e D t o L e a D
Series 32ECS

Gas-Fired Natural Draft Steam or Water Boilers
INStallatIoN SUPPlEMENt FoR:
32-380ECS
32-475ECS
EQUIPPED WItH 24 Volt CoNtRol SYStEMS
WaRNING: Improper installation,
adjustment, alteration, service or
maintenance can cause property
damage, injury, or loss of life. For
assistance or additional information,
consult a qualified installer, service
agency or the gas supplier. Read
these instructions care

Summary of the content on the page No. 2

Summary of the content on the page No. 3

I Product Description This supplement covers information not included in the standard Series 32 installation manual that is unique to the following models: 32-380WNLECS, 32-475WNLECS 32-380WNTECS, 32-475WNTECS 32-380SNLECS, 32-475SNLECS Follow the Series 32 installation instructions except where noted in this supplement. II Specifications 32-380ECS Dimensional Data (Refer to Figure 1 in Installation Manual): Jacket Overall

Summary of the content on the page No. 4

VII Venting Refer to installation manual. Vent sizing for the 32-380ECS should always be done in accordance with the National Fuel Gas Code. A vent damper can be installed on any 32-380ECS or 32-475ECS equipped with a 24 volt control system except for those with tankless heaters. If a vent damper is installed, the following components are required: • Effikal Model GVD-12 Vent Damper: Crown PN 96-038 • Damper Harness (Steam Boilers): Crown PN 9601300 • Damper Harness (Water Boilers): Cro

Summary of the content on the page No. 5

XI Control System Wiring WARNING All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such Wire the boiler in accordance with the following instructions rather than those in the installation manual. Provide the boiler with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit must be 15A. Wire the boiler using the appropriate wiring diagram shown in Figures A-C in this supplement. In addition, note th

Summary of the content on the page No. 6

VENTDAMPER(NOTE2) NOTE2 “BURNER” “BURNER” RD LESSVENT DAMPER RD ALARM ALARM ROBERTSHAW + TH 7000DERHC GASVALVE TR RD 2.ONBOILERSLESSVENTDAMPER,DAMPERHARNESSNOTUSED.REDANDBLUE LEADSAREJUMPEDTOGETHERUSINGREDJUMPERWIRE. Figure A: Steam Boiler Wiring (NOTE2) RD/YE RD 2 RD/YE MAINVALVE PILOTVALVE RD ALARM ALARM BL ROBERTSHAW + TH 7000DERHC GASVALVE TR RD RD/YE - REDwithYELLOWTRACE 2. WHENDAMPERISNOTUSED,DAMPERHARNESSISREPLACEDWITHJUMPERPLUG. Figure B: Water Boiler Wiring (Less Tankless Heater) 4

Summary of the content on the page No. 7

Sequence of Operation - Steam Boiler 1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damp- er. Assuming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close. On boilers equipped with Hydrolevel CG400A probe type low water cut-offs, voltage is also always applied to terminals “1” (blue) and “2” (yellow) on the low water cut-off to power the water level sensing circu

Summary of the content on the page No. 8

HONEYWELL L8124E RD RD/YE HIGHLIMIT 2 RD/YE RD MAINVALVE RD LOW LIMIT ALARM ALARM PILOTVALVE + ROBERTSHAW TH 7000DERHC GASVALVE TR Figure C: Water Boiler Wiring (With Tankless Heater) Figure D: Steam Boiler Control Installation 6

Summary of the content on the page No. 9

equipped with a reset button which must be pressed to restore normal burner operation. An open blocked vent switch is indicative of a problem with the vent system. If the blocked vent switch opens, the cause of the venting problem must be found and corrected by a qualified gas service technician before the blocked vent switch is reset. Sequence of Operation - Water Boiler, Less Tankless Heater 1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (ye

Summary of the content on the page No. 10

Figure E: Blocked Vent Switch Installation Figure F: Water Boiler Control Installation (Less Tankless Heater Version Shown) 8

Summary of the content on the page No. 11

6) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve (terminals “MV” and “MV/PV”), opening the valve and establishing main flame. 7) The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot depends upon the exact ignition module supplied with the boiler. For more information on module operation, consult the ignition module instructions supplied with the boiler or the local Cro

Summary of the content on the page No. 12

SERIES 32 MASTER PARTS LIST FOR 32-380ECS & 32-475ECS SECTIONS DESCRIPTION 380 475 380 475 I A PART # (STANDARD) 310000 310001 310002 3110053 3110063 310405 310406 311026 311020 311010 310400 311027 311028 311031 1 EA. 1 EA. QUANTITY PART # BOILER MODEL 32-380ECS 1 1 3 1 1 1 1 1 1 1 1 311035 311037 32-475ECS 1 1 4 1 1 1 1 1 1 1 1 311035 311037 ECS BASE CARTON DESCRIPTION PART # 380 475 380 ECS BASE ASSEMBLY 3131053 1 475 ECS BASE ASSEMBLY 3131063 1 REAR TIE ROD CHANNEL BRACKET 310311 1 1 5/8 X 4

Summary of the content on the page No. 13

BASE SIDE CARTON - See Installation Manual JACKET SIDE PANEL CARTON- See Installation Manual WATER AND STEAM BOILER CARTONS - As shown in Installation Manual except that Rating Plate is factory applied to RH Side Jacket Panel. BASE PARTS - Base parts are identical to those shown in Installation Manual with the following exceptions: 1) 24 Volt transformer (KEY #34) is not provided 2) 285 base is not used 3) CSD-1 gas train is not available. ECS WATER TRIM CARTON (LESS TANKLESS HEATER) DESCRIP

Summary of the content on the page No. 14

ECS STEAM TRIM CARTON DESCRIPTION PART # QTY STEAM PROBE CONTROL SUB ASSY 3513210 1 LWCO, CG400 WITH "P" PROBE 400824 1 BLOCKED VENT SWITCH ASSY 960128 1 GLASS SET (20-104-10, 8" CTR TO CTR) 950080 1 L404F PRESSURE LIMIT 3503805 1 STRAIGHT BRASS PIGTAIL 95-060 1 1/2 X 4 BRASS NIPPLE 950004 1 1/2 BRASS TEE 951441 1 1/2 BRASS PLUG 95-091 1 PRESSURE GAUGE 95-070 1 1/2 X 1/4 BRASS BUSHING 95-146 2 1/2 X 3 BR NIPPLES 95-116 2 1/2" BR. UNION 95-150 2 1/2 X CL BRASS NIPPLES 95-147 2 BLANK COIL PLATE 27

Summary of the content on the page No. 15

Summary of the content on the page No. 16

Manufacturer of Hydronic Heating Products P.O. Box 14818 3633 I. Street Philadelphia, PA 19134 Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com PN 980895 05/10


Alternative user manuals
# User manual Category Download
1 Crown Boiler 24-03 User manual Boiler 0
2 Crown Boiler 24-08 User manual Boiler 0
3 Crown Boiler 24-06 User manual Boiler 0
4 Crown Boiler 24-09 User manual Boiler 0
5 Crown Boiler 24-07 User manual Boiler 0
6 Crown Boiler 24-11 User manual Boiler 0
7 Crown Boiler 24-05 User manual Boiler 0
8 Crown Boiler 24-10 User manual Boiler 0
9 Crown Boiler 32 User manual Boiler 0
10 Crown Boiler 24-12 User manual Boiler 0
11 Crown Boiler 32-380ECS User manual Boiler 0
12 Crown Boiler 50-003 User manual Boiler 0
13 Crown Boiler 24-04 User manual Boiler 0
14 Crown Boiler ABF-EID User manual Boiler 0
15 Crown Boiler AWI037 User manual Boiler 0
16 Sony HDV 1080I HVR-M15N/M15P User manual Boiler 67
17 Sony HDV 1080I HVR-M25N/M25P User manual Boiler 50
18 A.O. Smith 200 User manual Boiler 2
19 A.O. Smith 201 User manual Boiler 7
20 A.O. Smith 750 & 1000 User manual Boiler 6