Thomas & Betts 9395 user manual

User manual for the device Thomas & Betts 9395

Device: Thomas & Betts 9395
Category: Power Supply
Manufacturer: Thomas & Betts
Size: 0.86 MB
Added : 5/28/2013
Number of pages: 74
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Thomas & Betts 9395. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Thomas & Betts 9395.

For your convenience

If looking through the Thomas & Betts 9395 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Thomas & Betts 9395 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Thomas & Betts 9395 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Thomas & Betts 9395 User manual - Online PDF
Advertisement
« Page 1 of 74 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Thomas & Betts 9395 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Thomas & Betts 9395. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Powerware 9395 UPS
225–275 kVA
User’s and Installation Guide

Summary of the content on the page No. 2

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. WARNING This is a product for commercial and industrial application in the second environment . Installation restrictionsor additional measures may be needed to prevent disturbances. ©2007 Eaton Corporatio

Summary of the content on the page No. 3

Powerware 9395 UPS225–275 kVA User’s and Installation Guide 1027212 Revision B Contents 1 Introduction .................................................................................................................................................................................................5 1.1 UPS standard features ........................................................................................................................................................................

Summary of the content on the page No. 4

5.3 Operation .................................................................................................................................................................................................57 5.3.1 Starting the UPS in normal mode ................................................................................................................................................57 5.3.2 Starting the UPS in bypass mode .................................................................

Summary of the content on the page No. 5

1 Introduction The Eaton® Powerware® 9395 uninterruptible power supply (UPS) is a true online, continuous- duty, transformerless, double-conversion, solid-state, three-phase system, providing conditioned and uninterruptible AC power to protect the customer’s load from all nine power failures. The Powerware 9395 UPS is available as a single module system. The Powerware online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and mi

Summary of the content on the page No. 6

Figure 1-1. Powerware 9395 UPS (225–275 kVA) cabinet Figure 1-2. Powerware 9395 UPS (225–275 kVA) typical single module system  1027212 UPS 225 - 275 kVA Revision B User’s and Installation Guide

Summary of the content on the page No. 7

1.1.2 CustomerInt erface • Building Alarm Monitoring – Up to five inputs in the UPS are available to connect the facility’s alarm system contacts. Some system configurations may limit the number of inputs available. The UPS uses these inputs to monitor the building alarms in addition to the UPS status. See Chapter 7, “Communication,” for additional information. • Alarm Contact – One alarm contact is provided for connection to equipment at the facility, such as a light, an audible alarm, or

Summary of the content on the page No. 8

1.3Basic syst em configurations The following basic UPS system configurations are possible: • Single module UPS and one to four battery cabinets • Single module UPS and a standalone battery system The UPS system configuration can be enhanced by adding optional accessories such as a Remote Emergency Power-off (REPO) control, or X-Slot® communication cards. 1.4Using thismanual This manual describes how to install and operate the Powerware 9395 UPS (225–275 kVA) cabinet. Read and underst

Summary of the content on the page No. 9

1.6S ymbols, contr ols, andindicat ors The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions. This symbol indicates that you should not discard the UPS or the

Summary of the content on the page No. 10

2UPS installation plan andunpac king Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system (Chapter 2). 2. Prepare your site for the UPS system (Chapter 2). 3. Inspect and unpack the UPS cabinet (Chapter 2). 4. Unload and install the UPS cabinet, and wire the system (Chapter 3). 5. Complete the Installation Checklist (Chapter 3). 6. Have authorized service personnel perform preliminary operational checks and startup. NOTE

Summary of the content on the page No. 11

Dimensions are in millimeters. Weight kg Model Shipping Installed Powerware 9395-275/225 930 830 Powerware 9395-275/275 930 830 Table 2-1. UPS cabinet weights The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front of the cabinet and outlets are in the top. You must allow clearance in front of and above each cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in Table 2-2. From top of cabinet Mini

Summary of the content on the page No. 12

Figure 2-1. UPS cabinet dimensions (front view) Figure 2-2. UPS cabinet dimensions (right side view) 12 1027212 UPS 225 - 275 kVA Revision B User’s and Installation Guide

Summary of the content on the page No. 13

Figure 2-3. UPS cabinet dimensions (top view) Figure 2-4. UPS cabinet dimensions (bottom view) Figure 2-5. UPS Cabinet dimensions (bottom view with mounting brackets) 1027212 13 UPS 225 - 275 kVA Revision B User’s and Installation Guide

Summary of the content on the page No. 14

Figure 2-6. UPS cabinet center of gravity Figure 2-7. Remote EPO switch dimensions 2.2.2UPS syst em power wiring preparation NOTE If installing, aspar tof the UPS system, a maintenanceb ypass without a rectifier input breaker,a minimum of tw osepar ate feeds withupstr eam feeder breakers, or one feed with two upstream feeder breakers, must be provided: one for theUPS and one f orthe maintenanceb ypassinput. DO NOTuse one feedor a si

Summary of the content on the page No. 15

For external wiring requirements, including the minimum size of external wiring, see Table 2-4. The power wiring connections for this equipment are rated at 70°C. If wire is run in an ambient temperature greater than 30°C, higher temperature wire and/or larger size wire may be necessary. Units Rating 50/60 Hz Basic unit rating at 0.9 lagging pF load kVA 225 275 kW 202 247 Input and output voltage Volts 400/400 400/400 AC input to UPS rectifier (0.98 Min. pF) Full load current plus battery r

Summary of the content on the page No. 16

Terminals E1 through E12 are 2-hole bus bar mountings for standard NEMA 2-hole barrel lugs. See Table 2-5 for power cable terminations and Table 2-6 for recommended installation parts and tools not supplied by Eaton Corporation. Figure 3-4 and Figure 3-5 show the location of the power cable terminals inside the UPS. Tightening torgue Terminal function Terminal Function Bus landing Bolt size Nm E1 Phase L1 4-2 bolt mounting 76 M12 AC input to UPS rectifier E2 Phase L2 4-2 bolt mounting 76 M12

Summary of the content on the page No. 17

The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values for AC output to critical load shown in Table 2-4. The recommended line-to- line load unbalance is 50% or less. Source protection for the AC input to bypass should be treated as if supplying a 275 kVA three- phase transformer, to allow for inrush current. Bypass input wiring and bypass input breaker rating should be treated as if supplying a 275 kVA load, regardless of the rating

Summary of the content on the page No. 18

Read and understand the following notes while planning and performing the installation: • Install the interface wiring (for example, building alarm, relay output, battery breaker trip, and X-Slot) separate from the power wiring. The wiring should have double insulation and rated at Uo/U = 300/500 Volts. • All interface wiring is to be provided by the customer. • When installing internal interface wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communica

Summary of the content on the page No. 19

2.3Inspecting and unpac king the UPScabinet The UPS cabinet is palleted separately for shipping. The cabinet is shipped bolted to a wooden pallet and protected with outer protective packaging material (see Figure 3-8). CAUTION TheUPS cabinetis hea vy(see Table2-1 onpag e 11). If unpac kinginstr uctionsar e not closely followed, the cabinet maytip and cause ser iousinjury . 1. Carefully inspect the outer packaging for evidence of damage during transit

Summary of the content on the page No. 20

6. After removing the protective covering, inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact your service representative immediately to determine the extent of the damage and its impact upon further installation. NOTE While waiting for installation, protect the unpacked cabinet from moisture, dust, and other harmful contaminants. Failure to store and protect th


Alternative user manuals
# User manual Category Download
1 Thomas & Betts Limitorque MX Device Net Field Unit User manual Power Supply 10
2 Sony AC U50A User manual Power Supply 5
3 Sony AC LS1 User manual Power Supply 2
4 Sony NP-FM30 User manual Power Supply 35
5 Sony NP FX101 User manual Power Supply 1
6 Sony NH-AAA-DA User manual Power Supply 2
7 3Com 3645A User manual Power Supply 0
8 3Com 3CNJPSE24 User manual Power Supply 2
9 3Com COREBUILDER 5000 User manual Power Supply 0
10 3Com 3646A User manual Power Supply 0
11 3Com External PoE Power System PSE2500-A3 User manual Power Supply 1
12 Sony AC E45HG User manual Power Supply 10
13 3Com Powerware Uninterruptible Power System Prestige Series User manual Power Supply 7
14 AB Soft ATX 12V User manual Power Supply 0
15 AC International Lenze SV01B User manual Power Supply 8