Lenox Elite Series X16Units user manual

User manual for the device Lenox Elite Series X16Units

Device: Lenox Elite Series X16Units
Category: Air Conditioner
Manufacturer: Lenox
Size: 0.89 MB
Added : 11/9/2013
Number of pages: 28
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Lenox Elite Series X16Units. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Lenox Elite Series X16Units.

For your convenience

If looking through the Lenox Elite Series X16Units user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Lenox Elite Series X16Units on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Lenox Elite Series X16Units to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Lenox Elite Series X16Units User manual - Online PDF
Advertisement
« Page 1 of 28 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Lenox Elite Series X16Units but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Lenox Elite Series X16Units. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

INSTALLATION
INSTRUCTIONS
2010 Lennox Industries Inc.
Dallas, Texas, USA
®
Elite Series XC16 Units
AIR CONDITIONER
506637−01
Litho U.S.A.
11/10
Supersedes 506101−01
TABLE OF CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . 1
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Model Number Identification . . . . . . . . . . . . . . . . . . . . 2
Unit Pa

Summary of the content on the page No. 2

Unit Dimensions − Inches (mm) LIQUID LINE CONNECTION C ELECTRICAL INLETS A SUCTION LINE CONNECTION 4−3/4" 4−1/2" (121) (108) B TOP VIEW SIDE VIEW UNIT SUPPORT FEET D K E J F G H XC14−024 TO −060 BASE WITH ELONGATED LEGS Model Number A B C D E F G H J K XC16−024−230 39 (991) XC16−036−230 45 (1143) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524) XC16−048−230 39 (991) XC16−060−230 39 (991) 35−1/2 (902) 39−3/8 (1001) 16−7/8 (429) 8−3/4 (222

Summary of the content on the page No. 3

Typical Unit Parts Arrangement CONTROL PANEL SINGLE POLE CONTACTOR (K1) GROUND LUG DUAL RUN CAPACITOR (C12) COMPRESSOR COMPRESSOR HARNESS CRANKCASE THERMOSTAT (S40) −048 AND HIGH PRESSURE −060 UNITS ONLY SWITCH (MANUAL RESET) (S4) LIQUID LINE FILTER LOW PRESSURE DRIER (SINGLE FLOW) SWITCH (S87) SUCTION LINE LIQUID LINE SERVICE SERVICE VALVE VALVE FIELD CONNECTION FOR SUCTION LINE FIELD CONNECTION FOR LIQUID LINE SET PLUMBING AND SWITCHES COMPONENTS Figure 1. Typical Parts Arrangements Page 3 XC1

Summary of the content on the page No. 4

IMPORTANT WARNING Electric Shock Hazard. Can cause injury To prevent stripping of the various caps used, the or death. Unit must be grounded in appropriately sized wrench should be used and fitted accordance with national and local snugly over the cap before tightening. codes. Table 1. Torque Requirements Line voltage is present at all components Parts Recommended Torque when unit is not in operation on units with single-pole contactors. Disconnect all Service valve cap 8 ft.− lb. 11 NM remote e

Summary of the content on the page No. 5

Operating Angle Type Service Valve: 1. Remove stem cap with an appropriately sized wrench. 2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go. SERVICE PORT CAP SERVICE PORT CORE (VALVE STEM SHOWN TO INDOOR CLOSED) INSERT HEX (VALVE STEM SHOWN OPEN) UNIT WRENCH HERE INSERT HEX WRENCH HERE SERVICE PORT STEM CAP CORE TO OUTDOOR UNIT ANGLE−TYPE SERVICE VALVE ANGLE−TYPE S

Summary of the content on the page No. 6

Recovering Refrigerant from Existing System RECOVERING REFRIGERANT FROM SYSTEM DISCONNECT POWER CONNECT MANIFOLD GAUGE SET Disconnect all power to the existing outdoor unit at the disconnect Connect a gauge set, clean recovery cylinder and a recovery 1 2 switch or main fuse box/breaker panel. machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections. MAIN FUSE BOX/BREAKER PANEL MAIN FUSE MANIFOLD GAUGES BOX/BREAKER PANEL RE

Summary of the content on the page No. 7

CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS) 6 (152) ACCESS PANEL MINIMUM CLEARANCE NOTES: CONTROL PANEL ABOVE UNIT ACCESS  Clearance to one of the other three LOCATION sides must be 36 inches (914mm). 30 (762) 12 (305)  Clearance to one of the remaining two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm). 48 (1219) LINE SET 36 (914) CONNECTIONS MINIMUM CLEARANCE BETWEEN TWO UNITS 24 (610) Figure 3. Installation Clearances PLACING UNIT ON SLAB New Outdoor Unit Placem

Summary of the content on the page No. 8

 Outside Unit Placement DETAIL A  Slab Mounting at Ground Level DETAIL B Install unit away from windows. Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure. BUILDING STRUCTURE MOUNTING SLAB GROUND LEVEL TWO 90° ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION. STABILIZING UNIT ON UNEVEN SURFACES  Elevated Slab Mounting DETAIL C using Feet Extenders  Slab Side Mounting DETAIL

Summary of the content on the page No. 9

ROOF MOUNTING Removing and Installing Panels Install the unit a minimum of 6 inches (152 mm) above the IMPORTANT roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that Do not allow panels to hang on unit by top tab. Tab is for can adequately support the unit. Consult local codes for alignment and not designed to support weight of panel. rooftop applications. WARNING To prevent personal injury, or damage to panels, unit or NOTICE str

Summary of the content on the page No. 10

Field refrigerant piping consists of liquid and vapor lines New or Replacement Line Set from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series REFRIGERANT LINE SET line set, or field−fabricated refrigerant line sizes as listed in table 2. This section provides information on installation or replacement of existing line set. If new or replacement line NOTE  When installing refrigerant lines longer than 50 set is not being installed then procee

Summary of the content on the page No. 11

Line Set Isolation  The following illustrations are examples of proper refrigerant line set isolation: REFRIGERANT LINE SET  TRANSITION REFRIGERANT LINE SET  INSTALLING VERTICAL RUNS (NEW CONSTRUCTION SHOWN) FROM VERTICAL TO HORIZONTAL NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the ANCHORED HEAVY NYLON temperature of the liquid line or when pressure drop is equal to or greater WIRE TIE OR AUTOMOTIVE AUTOMOTIVE

Summary of the content on the page No. 12

Brazing Connections IMPORTANT Use the procedures outline in figures 7 and 8 for brazing line set connections to service valves. Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port WARNING valve. Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed IMPORTANT as much as possible. DO NOT remove line set c

Summary of the content on the page No. 13

CAP AND CORE REMOVAL CUT AND DEBUR Cut ends of the refrigerant lines square (free from nicks or dents) Remove service cap and core from 2 1 and debur the ends. The pipe must remain round. Do not crimp end both the suction / vapor and liquid line of the line. service ports. CUT AND DEBUR SERVICE PORT SERVICE PORT CAP CORE LINE SET SIZE MATCHES SERVICE VALVE CONNECTION SERVICE SERVICE VALVE PORT CONNECTION CORE SERVICE COPPER TUBE PORT CAP STUB LIQUID LINE SERVICE SUCTION / VAPOR LINE VALVE SERV

Summary of the content on the page No. 14

WRAP SERVICE VALVES To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use 4 additional water saturated cloths underneath the valve body to protect the base paint. FLOW NITROGEN Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and 5 out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set conne

Summary of the content on the page No. 15

VAPOR LIQUID Flushing Line Set and Indoor Coil TYPICAL EXISTING FIXED ORIFICE TYPICAL EXISTING EXPANSION VALVE REMOVAL REMOVAL PROCEDURE (UNCASED OR PROCEDURE (UNCASED COIL SHOWN) 1B 1A COIL SHOWN) STUB END TWO PIECE PATCH PLATE LIQUID LINE CHECK DISTRIBUTOR TUBES (UNCASED COIL ONLY) ORIFICE EXPANSION LIQUID LINE ORIFICE HOUSING HOUSING VALVE DISTRIBUTOR TUBES ® TEFLON ® TEFLON RING RING FIXED ORIFICE BRASS NUT ® TEFLON SENSING RING LINE DISTRIBUTOR ASSEMBLY DISTRIBUTOR EQUALIZER ASSEMBLY LINE R

Summary of the content on the page No. 16

Installing Indoor Metering Device This outdoor unit is designed for use in systems that use coil. In applications where an uncased coil is being expansion valve metering devices at the indoor coil. installed in a field−provided plenum, install the expansion valve in a manner that will provide access for field servicing See the Lennox XC16 Engineering Handbook for of the expansion valve. Refer to below illustration for approved expansion valve kit match−ups. The expansion reference during instal

Summary of the content on the page No. 17

Leak Test Line Set and Indoor Coil IMPORTANT The Environmental Protection Agency (EPA) prohibits WARNING the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. When using a high pressure gas such as Approved methods of recovery, recycling or reclaiming dry nitrogen to pressurize a refrigeration must be followed. or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa). IMPORTANT If this un

Summary of the content on the page No. 18

Evacuating Line Set and Indoor Coil CONNECT GAUGE SET LOW HIGH NOTE  Remove cores from service valves (if not already done). 1 A Connect low side of manifold gauge set with 1/4 SAE in−line tee to vapor line service valve B Connect high side of manifold gauge OUTDOOR set to liquid line service valve MANIFOLD A34000 1/4 SAE TEE WITH UNIT GAUGE SET C Connect micron gauge available SWIVEL COUPLER connector on the 1/4 SAE in−line tee. A D Connect the vacuum pump (with 500 vacuum gauge) to the cente

Summary of the content on the page No. 19

temperatures and pressures present during operation of IMPORTANT an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances Use a thermocouple or thermistor electronic vacuum that corrode copper piping and compressor parts. gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns. Electrical In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). I

Summary of the content on the page No. 20

ƒ ⁄ Figure 13. Typical Unit Wiring Diagram Page 20 506637−01 11/10


Alternative user manuals
# User manual Category Download
1 Lenox 506637-01 User manual Air Conditioner 17
2 Lenox Elite Series User manual Air Conditioner 6
3 Lenox wb2-17 User manual Air Conditioner 3
4 Lenox wb2-17a User manual Air Conditioner 2
5 Lenox XC14 User manual Air Conditioner 12
6 Lenox P506640-01 User manual Air Conditioner 8
7 Lenox Elite Series XP16 Units Heat Pumps User manual Air Conditioner 7
8 Sony SU-PW2 User manual Air Conditioner 12
9 Sony CV-P12PX User manual Air Conditioner 3
10 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
11 Sony VGN-BX500 User manual Air Conditioner 1
12 Philips 190S5 User manual Air Conditioner 21
13 Philips Comfort-Cire AMC 45 User manual Air Conditioner 7
14 Philips Comfort-Cire AMC 30 User manual Air Conditioner 2
15 Philips CS-E15DB4EW User manual Air Conditioner 4