Whirlpool GOLD W4GH6 user manual

User manual for the device Whirlpool GOLD W4GH6

Device: Whirlpool GOLD W4GH6
Category: Heat Pump
Manufacturer: Whirlpool
Size: 0.9 MB
Added : 7/1/2013
Number of pages: 20
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Whirlpool GOLD W4GH6. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Whirlpool GOLD W4GH6.

For your convenience

If looking through the Whirlpool GOLD W4GH6 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Whirlpool GOLD W4GH6 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Whirlpool GOLD W4GH6 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Whirlpool GOLD W4GH6 User manual - Online PDF
Advertisement
« Page 1 of 20 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Whirlpool GOLD W4GH6 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Whirlpool GOLD W4GH6. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

HEAT PUMP INSTALLATION INSTRUCTIONS
Table of Contents
HEAT PUMP SAFETY.....................................................................1 SEQUENCE OF OPERATION ......................................................12
Cooling Cycle .............................................................................12
INSTALLATION REQUIREMENTS ................................................1
Heating Cycle .............................................................................12
Tools and Parts

Summary of the content on the page No. 2

Indoor System Thermal Expansion Valve Tools and Parts Gather the required tools and parts before starting installation.  W4GH6 units are designed for use with thermal expansion Read and follow the instructions provided with any tools listed valve systems only. The thermal expansion valve must be here. ordered separately from the manufacturer. Tools Needed Thermal Expansion Valve Kits  Torch  Gauge set for R-410A Model Part Number refrigerant  ¹⁄₄" nut driver  Service wrench with hex-

Summary of the content on the page No. 3

Minimum Clearances Transition from Horizontal to Vertical This shows how to make a transition from horizontal to vertical. AB C D To Power Style 1 Style 2 Supply 48" Overhead To Clearance A G Indoor (Discharge Unit Air) To 12" Clearance Indoor (Inlet Air) Coil B B C C E F F D D E E 30" Service 12" Clearance Between 36" Clearance A. Style 1—anchored C. Liquid line E. Metal sleeve Access Clearance Unit and Building (Inlet Air) heavy nylon wire tie D. Vapor line— F. Wall stud B. Strap liqu

Summary of the content on the page No. 4

Electrical Requirements Inspect Shipment WARNING WARNING Excessive Weight Hazard Use two or more people to move and install condensing unit or heat pump. Failure to do so can result in back or other injury. Electrical Shock Hazard This heat pump is shipped in one package, completely assembled and wired. The thermostat is shipped in a separate Electrically ground condensing unit or heat pump. carton when ordered. Connect ground wire to ground lug. 1. Check the heat pump rating plate to confirm

Summary of the content on the page No. 5

1. Disconnect power. 8. Remove the valve cores. 2. Remove the refrigerant from the existing system per the manufacturer’s instructions provided with the recovery system being used. Connect the R-22 gauge set is connected to both sides of the refrigerant system (as shown), and verify that the entire system is void of refrigerant in A accordance with the manufacturer’s instructions provided with the recovery system being used. 3. Disconnect the liquid and vapor lines from the existing outdoo

Summary of the content on the page No. 6

17. Install the valve cores. 18. Install the R-410A thermal expansion valve specified for this system in the indoor coil. NOTE: R-410A systems use only thermal expansion valves. 19. Pressurize the lines and indoor coil with a pressure not to exceed 20 psig. A 20. Leak test the lines with a pressure not to exceed 20 psig. 21. Open the suction and liquid service valves fully. 22. Insulate the suction line with refrigerant line insulation material of ¹⁄₄" or more wall thickness. 23. Pack insulat

Summary of the content on the page No. 7

6. Tighten to 20 to 30 ft lbs. Use backup wrench on all wrench 6. Make sure indoor coil has been put in place according to the flats. Installation Instructions and is connected to the refrigerant ® lines. NOTE: Overtightening may crush the Teflon seal and cause a leak. 7. Replace valve cores. 8. Pressurize the lines and indoor coil with a pressure not to 7. Connect the external equalizer line to the equalizer port on exceed 20 psig. the suction line. 9. Leak test the lines with a pressure

Summary of the content on the page No. 8

Normal Operating Pressures NOTE: Values provided in chart are typical pressures. Indoor unit matchup, indoor air quality and indoor load will cause pressures to vary. Model -24 -36 -48 -60 Temperature of the Air Entering the Outdoor Coil Liquid Suction Liquid Suction Liquid Suction Liquid Suction Cooling—1st Stage (Low Capacity) 65ºF 232 146 225 144 235 144 225 138 75ºF 264 148 261 147 268 145 264 141 85ºF 307 149 302 149 310 147 305 142 95ºF 353 151 349 151 356 148 352 146 105ºF 403 153 397

Summary of the content on the page No. 9

Suction Line Sizes Liquid Line Sizes Installations exceeding 100 ft are not recommended. Installations exceeding 100 ft are not recommended. Btu/h Line Set Size (in. OD) Btu/h Line Set Size (in. OD) 24,000 ³⁄₄ ³⁄₄ ³⁄₄ 24,000 ³⁄₈ ³⁄₈ ³⁄₈ 36,000 ⁷⁄₈ ⁷⁄₈ ⁷⁄₈ 36,000 ³⁄₈ ³⁄₈ ³⁄₈ 48,000 ⁷⁄₈ ⁷⁄₈ ⁷⁄₈ 48,000 ³⁄₈ ³⁄₈ ³⁄₈ 60,000 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 60,000 ³⁄₈ ³⁄₈ ³⁄₈ Line Set Length Less than 25 ft Over 25 ft and Line Set Length Less than 25 ft Over 25 ft and 25 ft up to 50 ft 25 ft up to 50 ft Make Electrica

Summary of the content on the page No. 10

4. Connect ground wire to ground lug. 5. Connect low voltage circuit. Typical Wiring Connection (low voltage circuit) T2 T1 NOTE: Some connections may not apply. Refer to specific thermostat and indoor unit. Without Auxiliary Heat Thermostat Indoor Unit Outdoor Unit Power Power A B R R R L2 L1 Common C C C 1st Stage 1st Stage W1 W1 W1 Aux. Heat Aux. Heat W2 W3 Indoor Blower If Applicable G G A Reversing Valve L2 L1 O O B Y1 Y1 Y1 Compressor Y2 Y2 Y2 C A. Ground lug With Auxiliary Heat B. Field s

Summary of the content on the page No. 11

Outdoor Unit Typical Wiring Diagram LT BU R Outdoor Fan Dual Capacitor PR FC H Thermostat W1 Y1 Y2 BK C R O Fan BK OR O-OUT W1 W1 L Y C C LO-PS BU 24V L L DF R R BK Common O O R C S Y1 OUT Y1 Y1 HI-PS Compressor Diagnostic Module Crankcase Heater Defrost Control Y L2 208-230/60/1 Ground L1 Lug Ground Crankcase Thermostat Thermostat Defrost Control Reversing Valve C R W1 O Y1 Y2 Defrost Fan Thermostat L1 O-OUT W1 Low Pressure L C Compressor LO-PS Switch L 24V R Defrost Switch DF BK L1 C SR O Comm

Summary of the content on the page No. 12

SEQUENCE OF OPERATION Defrost Control Cooling Cycle Upon cooling demand, the thermostat closes circuit R to O and Y. The defrost control board includes the combined functions of the Closing R to O and Y energizes the reversing valve for cooling time/temperature defrost control, defrost relay, diagnostic LEDs operation and closes the heat pump contactor, starting the and terminal strip for field wiring connections. See “Defrost compressor and outdoor fan. The thermostat automatically Cont

Summary of the content on the page No. 13

Time Delay Adjust Defrost System The time delay is 5 minutes long. The delay helps to protect the Defrost Control Board compressor from short cycling in case the power to the heat pump is interrupted or a pressure switch opens. The delay is Optional high pressure switch connections bypassed by placing the timer select jumper across the TEST NOTE: To add the pressure switch, remove the factory-installed pins for 0.5 seconds. jumper. Pressure Switch Circuit P1 FAN 30 The defrost control inclu

Summary of the content on the page No. 14

2. Remove the heater compartment access panel. 3. Connect the test pins on the defrost control using a test jumper wire. 3. Adjust the time period between defrost cycles by placing the defrost time plug in the proper position. See “Defrost Control NOTE: If the outdoor temperature is above 32°F, connect the Board.” defrost sensor terminals using a test jumper wire. See “Defrost Control Board” in the “Adjust Defrost System”  For 30-minute intervals between defrost cycles, connect section. t

Summary of the content on the page No. 15

TROUBLESHOOTING Heat Pump Fails to Operate Properly LED Description Review “Sequence of Operation” and visually inspect the heat Power LED (Green) indicates voltage is present at the power pump before troubleshooting: connection of the module. Alert LED (Yellow) communicates an abnormal system condition through a unique flash code. The Alert LED will flash a number of WARNING times consecutively, pause, and then repeat the process. The number of consecutive flashes correlates to a particular

Summary of the content on the page No. 16

Flash Codes LED Status Fault Description Troubleshooting Information  Thermostat demand signal is intermittent. Alert (Yellow) Flash Code 3 Short Cycling: Compressor is running only briefly.  Time delay relay or control board is defective.  If high pressure switch is present, go to Flash Code 2 information.  If low pressure switch is present, go to Flash Code 1 information.  Run capacitor has failed. Alert (Yellow) Flash Code 4 Locked Rotor  Low line voltage (contact utility if voltage

Summary of the content on the page No. 17

Incorrectly Wired Module Codes Depending on the system configuration, some Alert flash codes Incorrectly wiring the diagnostic module will cause false LED may not be active. The presence of safety switches affects how codes. The Incorrectly Wired Module Troubleshooting chart the system alerts are displayed by the module. describes LED operation when the module is incorrectly wired and what troubleshooting action is required to correct the problem. Incorrectly Wired Module Troubleshooting Inc

Summary of the content on the page No. 18

18

Summary of the content on the page No. 19

Keep this book and your sales slip together for future reference. You must provide proof of purchase or installation Dealer name____________________________________________________ date for in-warranty service. Address ________________________________________________________ Write down the following information about your Split System Heat Pump—Outdoor Section to better help you obtain Phone number__________________________________________________ assistance or service if you ever need it. M

Summary of the content on the page No. 20

48488A006 ®Registered Trademark/TM Trademark of Whirlpool, U.S.A., 6/06 © 2006. All rights reserved. Manufactured under license by Tradewinds Distributing Company, LLC., Coconut Grove, Florida Printed in U.S.A.


Alternative user manuals
# User manual Category Download
1 Edelbrock 15005 User manual Heat Pump 0
2 A.O. Smith AH User manual Heat Pump 2
3 ACS 882.00217.00 User manual Heat Pump 1
4 A.O. Smith AHD 290 User manual Heat Pump 3
5 AC International SELF-PRIMING CENTRIFUGAL PUMPS User manual Heat Pump 5
6 Acnodes Q5RF SERIES User manual Heat Pump 2
7 Amana 10730418 User manual Heat Pump 1
8 Allied Air Enterprises (2 User manual Heat Pump 0
9 Allied Air Enterprises 15) User manual Heat Pump 0
10 Allied Air Enterprises 4HP16LT User manual Heat Pump 2
11 AC International 8200 Series User manual Heat Pump 1
12 American Standard TWE060B***E User manual Heat Pump 2
13 Allied Air Enterprises 4)PHP(13 User manual Heat Pump 1
14 American Standard TWE120A***F User manual Heat Pump 0
15 American Standard TWE090B***E User manual Heat Pump 0