Summary of the content on the page No. 1 
                    
                        INSTALLATION, OPERATION 
West Warwick, Rhode Island 02893 & MAINTENANCE
 INSTRUCTIONS
®
BOILERMATE
INDIRECT-FIRED WATER HEATERS
MODELS CODES:
MODELS COVERED: 
™
P:  Packaged with circulator & Smart Control
• WH-7 &  9 Classic Series
™ ™
L:  Less Circulator, with Smart Control
• Top Down TD Series
Z:  Dial Aquastat
• RTR models
C:  High-output commercial exchanger
• WHS Premier Series 
DW:  Double-wall heat exchanger
RTR: Pre-piped and wired
INSTALLER: LEAVE THIS MANUAL WITH THE OWNER
IMPORTANT G
                    
                    Summary of the content on the page No. 2 
                    
                        1. TABLE OF CONTENTS 2. Pre-Installation Checklist .................................................2 10. Wiring All Ready-To-Run (RTR) Models ....................... 23 3. Required Components and Accessories Checklist .........3 11. Startup Procedure For All Models ................................ 25 4. WH-7 & 9 Classic Series Piping Installation ....................4 12. Setting the Smart Control™ .......................................... 26 5. Top Down™ TD-Series Piping Installation ........
                    
                    Summary of the content on the page No. 3 
                    
                        3. REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST     SHUTOFF VACUUM RELIEF THERMAL EXPANSION   MODEL CIRCULATOR ZONE VALVE* VALVE BREAKER VALVE TANK DRAIN   Residential = 5GPM *If Circulator not used    Required ®    WH SERIES Commercial = 10GPM 3/4” Full Port 4 1 Included (See Therm-X-Trol Included   Except “P” Models or 1” STD    Sizing Guide)   5GPM *If Circulator not used    Required ®    TD SERIES Except “P” Models 3/4” Full Port 4 1 Included (See Therm-X-Trol Included    or 1” STD    Sizin
                    
                    Summary of the content on the page No. 4 
                    
                        4. WH-7 & 9 CLASSIC SERIES PIPING INSTALLATION DOMESTIC WATER PIPING BOILER PIPING 3 1. Plumb the circulator or zone valve on the BOILER SUPPLY  1. Thread the included /4” brass tee onto the pipe marked  line.  If using a separate circulator, the pump flange  COLD WATER. can be mounted directly to the threaded pipe marked  BOILER SUPPLY.  Alternately, the circulator can be placed  3 2.  Screw the /4” drain valve into the opposite end of the brass  anywhere on the boiler supply line. tee. 2. Pipe
                    
                    Summary of the content on the page No. 5 
                    
                          PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR -5-                                                                                                                                                                                                                                                                                                                                                                                           
                    
                    Summary of the content on the page No. 6 
                    
                        5. TOP DOWN™ TD-SERIES PIPING INSTALLATION can be mounted directly to the threaded pipe marked  DOMESTIC WATER PIPING BOILER SUPPLY.  Alternately, the circulator can be placed  anywhere on the boiler supply line. 1. Connect the cold water supply to the pipe labeled COLD  WATER 2. Pipe the BOILER RETURN connection to the boiler return  line. 2. Connect the HOT WATER piping to the domestic hot water  system. Be sure the return line is NOT  plumbed to the suction side of any  3. Make an 8-inch “hea
                    
                    Summary of the content on the page No. 7 
                    
                          PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR -7-                                                                                                                                                                                                                                                                                                                                                                                           
                    
                    Summary of the content on the page No. 8 
                    
                        6. READY-TO-RUN RTR-SERIES PIPING INSTALLATION DOMESTIC WATER PIPING BOILER PIPING 1. Connect the cold water supply to the pipe labeled COLD 1. Plumb the BOILER SUPPLY line.  The circulator and flow  WATER. check are factory installed 2. Connect the HOT WATER piping to the domestic hot water 2. Pipe the BOILER RETURN connection to the boiler return  system. line. Be sure the return line is NOT  3. Make an 8-inch “heat trap” on the HOT WATER outlet as  plumbed to the suction side of any  shown in
                    
                    Summary of the content on the page No. 9 
                    
                          PIPING MODELS WITH PRE-INSTALLED CIRCULATOR W/INTEGRAL FLOW CHECK -9-                                                                                                                                                                                                                                                                                                                                                                                                                                             
                    
                    Summary of the content on the page No. 10 
                    
                        7. WHS PREMIER SERIES PIPING INSTALLATION DOMESTIC WATER PIPING BOILER PIPING 1. Thread the included brass tee onto the pipe marked COLD 1. Plumb the circulator or zone valve on the BOILER SUPPLY  WATER. line.  If using a separate circulator, the pump flange  can be mounted directly to the threaded pipe marked  2. Screw the drain valve into the opposite end of the brass BOILER SUPPLY.  Alternately, the circulator can be placed  tee anywhere on the boiler supply line. 3. Connect the cold water su
                    
                    Summary of the content on the page No. 11 
                    
                          PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR -11-                                                                                                                                                                                                                                                                                                                                                                                          
                    
                    Summary of the content on the page No. 12 
                    
                        ™ 8. WIRING ALL SMART CONTROL MODELS The Smart Control™ incorporates all the switching and temperature control functions necessary to control the BoilerMate™.   The diagram below shows internal wiring and the associated functions. After wiring is complete, insert the white thermistor (sensor) plug into the receptacle at the base of the Smart Control™. Select  the plug marked CIRCULATOR or ZONE VALVE based on the application. Zone valves can be slow actuating. Therefore, the  zone valve sensor co
                    
                    Summary of the content on the page No. 13 
                    
                        ® BOILERMATE L1 L2  JUNCTION BOX ORANGE  ORANGE  BLUE  L8124 A & C  BLUE  VIOLET  1 2  T T  VIOLET  WHITE  BLACK  (PLACE A WIRE NUT OVER EACH WIRE NOT USED)  ® BOILERMATE B2 B1 CIRCULATOR ZR  C2 C1  ZC  HONEYWELL L8124 A & C  L8124 B & D  ® T BOILERMATE T  JUNCTION BOX ORANGE  HIGH LOW LIMIT/  CIRCULATOR  LIMIT  ORANGE  W  BLUE  B R  BLUE  B VIOLET  R  VIOLET  B2 C1  B1 WHITE  BLACK  C2  1 2  (PLACE A WIRE NUT OVER EACH WIRE NOT USED)  ® BOILERMATE CIRCULATOR HONEYWELL L8124 B & D  L1 L2  L1 L2 
                    
                    Summary of the content on the page No. 14 
                    
                        ® BOILERMATE JUNCTION BOX L8148J  ORANGE  T W TV  ORANGE  TP Z  BLUE  BLUE  HI  B  LIMIT  VIOLET  R  VIOLET  WHITE  BLACK  C1 C2  (PLACE A WIRE NUT OVER B2 B3  B1 L1 L2  EACH WIRE NOT USED)  ® BOILERMATE CIRCULATOR L1 L2  HONEYWELL L8148 J  WITH MILLIVOLT GAS VALVE  ® BOILERMATE JUNCTION BOX L8148J  ORANGE  W TV  T  ORANGE  Z  TP  BLUE  BLUE  HI  B  LIMIT  VIOLET  R  VIOLET  WHITE  BLACK  C1 C2  (PLACE A WIRE NUT OVER  B1 B2 B3 L1 L2  EACH WIRE NOT USED)  ® BOILERMATE CIRCULATOR L1 L2  HONEYWELL
                    
                    Summary of the content on the page No. 15 
                    
                        ® BOILERMATE JUNCTION BOX 8J48A  ORANGE  TV W T  ORANGE  Z B  TP BLUE  BLUE  C1 C2  VIOLET   L1  B1 B2 B3 L2  VIOLET  WHITE  BLACK  (PLACE A WIRE NUT OVER EACH WIRE NOT USED)  WHITE - RODGERS 8J48A  WITH SELF-GENERATING GAS VALVE   ® L1 L2  BOILERMATE JUNCTION BOX ORANGE  ORANGE  BLUE  L8124 A & C  BLUE  VIOLET  1 2 T T  VIOLET  WHITE  BLACK  B2 B1  ZR  ZC C2 C1  ® BOILERMATE CIRCULATOR PRIORITY WIRING  HEATING   CIRCULATOR  HONEYWELL L8124 A & C  L8124 B & D  ® T  T BOILERMATE JUNCTION BOX HIGH
                    
                    Summary of the content on the page No. 16 
                    
                        L1 L2  ® BOILERMATE JUNCTION BOX L8148A  ORANGE  L1 L2 T T  ORANGE  BLUE  HIGH  3  LIMIT  BLUE  VIOLET  B  VIOLET  WHITE  R  BLACK  C1 C2 B1  B2  ® PRIORITY WIRING  BOILERMATE CIRCULATOR HONEYWELL L8148A  L1 L2  ® BOILERMATE JUNCTION BOX ORANGE  ORANGE  L8148B  BLUE  BLUE  L1 L2 T T  VIOLET  HIGH VIOLET  LIMIT  WHITE  B BLACK  R  ® BOILERMATE C1  C2 B1  B2  CIRCULATOR PRIORITY WIRING  HONEYWELL L8148B  ® BOILERMATE JUNCTION BOX L8148J  ORANGE  T W TV  ORANGE  Z  TP  BLUE  BLUE  HI B  LIMIT VIOLE
                    
                    Summary of the content on the page No. 17 
                    
                        ® BOILERMATE JUNCTION BOX L8148J  ORANGE  T W TV  ORANGE  Z  TP  BLUE  BLUE  HI B  VIOLET  LIMIT  R  VIOLET  WHITE  BLACK  C1 C2  B1 B2 B3   L1 L2  PRIORITY WIRING  ® BOILERMATE HONEYWELL L8148 J  CIRCULATOR WITH MILLIVOLT GAS VALVE   L1 L2  ® BOILERMATE JUNCTION BOX 8J48A  ORANGE  TV W T  ORANGE  HEATING  TP Z B  BLUE  CIRCULATOR  C1 BLUE  C2  VIOLET  L1  B3  B1 B2 L2  VIOLET  WHITE  BLACK  (PLACE A WIRE NUT OVER EACH WIRE NOT USED)  PRIORITY WIRING  WHITE-RODGERS 8J48A  ® BOILERMATE WITH 24VOL
                    
                    Summary of the content on the page No. 18 
                    
                        Typical Multi-Zone Relay  ORANGE  Utilizing Post-Purge Feature  ORANGE  BLUE  BLUE  Thermostat  Inputs  VIOLET  VIOLET  Priority or  DHW Zone  BLACK  WHITE  Zone Outputs  Smart Control™  X    X  L1 L2 (PLACE A WIRE NUT OVER  EACH WIRE NOT USED)  120V  Supply  T    T  ® BoilerMate Boiler Aquastat Circulator Typical Multi-Zone Relay  ORANGE  24V without Post-Purge Feature  ORANGE  BLUE  BLUE  Thermostat  VIOLET  Inputs  VIOLET  Priority or  DHW Zone  BLACK  24V  Supply  WHITE  Zone Outputs  Smart 
                    
                    Summary of the content on the page No. 19 
                    
                        WATER SENSOR INSTALLATION (IF EQUIPPED) The Smart Control™ features an error code designed to alert the user to the presence of water on the floor.  This is useful to  warn of a leaking boiler, water heater, etc., or to alert the owner to a leak in the basement.  If equipped with the optional water  sensor, follow the installation instructions below: Water Sensor Plug 1. If the sensor will be used to detect a water heater leak, the proper placement is in a drip pan as required in the warning  se
                    
                    Summary of the content on the page No. 20 
                    
                        9. WIRING ALL DIAL CONTROL MODELS (EXCEPT RTR MODELS) Dial Control models utilize a standard dry-contact aquastat with capillary temperature sensor.  The dial control contains a  make-and-break switch and is suitable for 24V or 120V, 25A Max.   CAPILLARY TUBE SENSOR BULB SHAFT WIRE LEADS To wire Dial Control models, select the appropriate diagram from the following pages.  If a suitable diagram is not available for  your application, please contact AMTROL Tech Support at (401)535-1216.  Always d