Pioneer MUH-GA20VB user manual

User manual for the device Pioneer MUH-GA20VB

Device: Pioneer MUH-GA20VB
Category: Air Conditioner
Manufacturer: Pioneer
Size: 0.81 MB
Added : 4/16/2014
Number of pages: 36
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Pioneer MUH-GA20VB. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Pioneer MUH-GA20VB.

For your convenience

If looking through the Pioneer MUH-GA20VB user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Pioneer MUH-GA20VB on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Pioneer MUH-GA20VB to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Pioneer MUH-GA20VB User manual - Online PDF
Advertisement
« Page 1 of 36 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Pioneer MUH-GA20VB but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Pioneer MUH-GA20VB. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

OB387-1.qxp 05.2.21 10:03 AM Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
No. OB387
HFC
utilized
R410A
SERVICE MANUAL
Wireless type
Models
E1
MUH-GA20VB -
E1
MUH-GA25VB -
E1
MUH-GA35VB -
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················6
3. SPECIFICATION·················································6
4. NOISE CRITERIA CURVES·······························7
Indication of
5. OUTLINES AND DIMENSIONS ······················

Summary of the content on the page No. 2

OB387-1.qxp 05.2.21 10:03 AM Page 2 1 TECHNICAL CHANGES E1 E1 MUH-A07YV- MUH-GA20VB- 1. Indication of capacity has been changed. (BTU base kw) 2. Dimension of outdoor unit has been changed. (780Wo540Ho255D 800Wo550Ho285D) 3. Stop valve cover has been added. 4. Outdoor fan motor has been changed. (RC6V20-AB RA6V21-AD) 5. Outdoor fan motor capacitor has been changed. 6. Compressor capacitor has been changed. 7. Outdoor heat exchanger has been changed. (L-BEND FLAT) E1 E1 MUH-A09YV- M

Summary of the content on the page No. 3

OB387-1.qxp 05.2.21 10:03 AM Page 3 INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT • This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer. • Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/ materials are required. Refer to the table below. 2 Take suf

Summary of the content on the page No. 4

OB387-1.qxp 05.2.21 10:03 AM Page 4 Conversion chart of refrigerant temperature and pressure (MPa [Gauge]) 4.0 3.5 R410A 3.0 R22 2.5 2.0 NOTE : The unit of pressure has been changed to MPa on the 1.5 international system of units(SI unit system). 1.0 The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f f [Gauge]) 0.5 0.0 -0.5 -30 -20 -10 0 10 20 30 40 50 60 (:) 1.Tools dedicated for the air conditioner with R410A refrigerant The following tools are required for R410A refrigerant. Some R22 too

Summary of the content on the page No. 5

OB387-1.qxp 05.2.21 10:03 AM Page 5 2 Flaring work and flare nut Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”. Dimension of flare nut Pipe diameter R410A mm R22 6.35 17 17 9.52 22 22 3.Refrigeration oil Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces. 4.Air purge • Do not discharge the refrigerant into the atmosphere. Take care not to disc

Summary of the content on the page No. 6

OB387-1.qxp 05.2.21 10:03 AM Page 6 2 PART NAMES AND FUNCTIONS OUTDOOR UNIT ACCESSORIES E1 E1 MUH-GA20VB - MUH-GA20VB- E1 E1 MUH-GA25VB- MUH-GA25VB - E1 E1 MUH-GA35VB - MUH-GA35VB- Air inlet back : MUH-GA20VB back and side : MUH-GA25VB ( ) 1 Drain socket 1 MUH-GA35VB Piping Drain hose Air outlet Drain outlet 3 SPECIFICATION E1 E1 E1 MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - Outdoor model Single phase

Summary of the content on the page No. 7

OB387-1.qxp 05.2.21 10:03 AM Page 7 4 NOISE CRITERIA CURVES SPL(dB(A)) LINE SPL(dB(A)) LINE FUNCTION FUNCTION MUH-GA25VB- E1 MUH-GA20VB- E1 COOLING COOLING 49 47 MUH-GA35VB- E1 HEATING HEATING Test conditions, Test conditions, Cooling :DB35: WB24: Cooling :DB35: WB24: Heating :DB 7: WB 6: Heating :DB 7: WB 6: 90 90 80 80 70 70 NC-70 NC-70 60 60 NC-60 NC-60 50 50 NC-50 NC-50 40 40 NC-40 NC-40 30 30 NC-30 NC-30 APPROXIMATE APPROXIMATE 20 20 TERESHOLD OF TERESHOLD OF HEARING FOR HEARING

Summary of the content on the page No. 8

100mm or more 350mm or more OB387-1.qxp 05.2.21 10:03 AM Page 8 5 OUTLINES AND DIMENSIONS E1 E1 E1 Unit: mm MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - OUTDOOR UNIT REQUIRED SPACE Basically open 100mm or more without any obstruction in front and on both sides of the unit. 400 Drain hole [42 Air in Air in (MUH-GA25 /GA35VB) Open two sides of left, 40 2 holes 10X21 right, or rear side. Service panel Air out 23 22.3 Liquid refrigerant pipe joint Handle Refrigerant pipe (flared) [6.35 Gas refrigera

Summary of the content on the page No. 9

OB387-1.qxp 05.2.21 10:03 AM Page 9 6 WIRING DIAGRAM E1 E1 E1 MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - MODELS WIRING DIAGRAM OUTDOOR UNIT 21S4 RT61 TB2 RED CN661 CN721 3 CN711 BLK WHT N BLK CIRCUIT MF BREAKER RED SR61 TB1 L T61 BLU N TAB20 52C BRN WHT PE 4 3 C BLU RED S MC R C1 BLK NAME SYMBOL SYMBOL NAME SYMBOL NAME TRANS FORMER C1 COMPRESSOR CAPACITOR OUTDOOR FAN MOTOR T61 MF (INNER FUSE) C65 OUTDOOR FAN CAPACITOR TB1,TB2 TERMINAL BLOCK DSAR SURGE ABSORBER NR61 VARISTOR 21S4 R.V. COIL F61 FUSE

Summary of the content on the page No. 10

OB387-1.qxp 05.2.21 10:03 AM Page 10 7 REFRIGERANT SYSTEM DIAGRAM Unit:mm E1 E1 E1 MUH-GA20VB - MUH-GA25VB - MUH-GA35VB - OUTDOOR UNIT Refrigerant pipe [ 9.52 4-way valve (with heat insulator) Stop valve Outdoor (with service heat port) Defrost Flared connection Muffler exchanger thermistor RT61 Compressor Capillary tube [3.0x[1.4x700 (MUH-GA20VB) [3.0x[1.4x1000(MUH-GA25VB) Flared connection [3.0x[1.4x500 (MUH-GA35VB) Check valve R.V. coil Strainer heating ON #100 cooling OFF Capillary tube

Summary of the content on the page No. 11

OB387-1.qxp 05.2.21 10:03 AM Page 11 MAX. REFRIGERANT PIPING LENGTH Refrigerant piping Piping size O.D : mm Length of connecting pipe : m Max. length : m Model Gas Liquid Indoor unit Outdoor unit A MUH-GA20VB - E1 Gas 0.43 Gas 0 20 MUH-GA25VB - E1 9.52 6.35 Liquid 0 Liquid 0.5 MUH-GA35VB - E1 25 MAX. HEIGHT DIFFERENCE Indoor unit Height difference should be within Refrigerant Piping 10m regardless of which unit, Max.length w Max. Height indoor or o

Summary of the content on the page No. 12

OB387-1.qxp 05.2.21 10:03 AM Page 12 How to measure the indoor air wet-bulb/dry-bulb temperature difference 1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high. 2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent di

Summary of the content on the page No. 13

OB387-1.qxp 05.2.21 10:03 AM Page 13 8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation ‹ Both indoor and outdoor unit are under the same temperature/humidity condition. Relative humidity(%) Dry-bulb temperature 20 50 25 60 30 70 ` Air flow should be set at MAX. fi The unit of pressure has been changed to MPa on the international system of units(SI unit system). The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/f f[Gauge] ) E1 E1 (kgf/F[Gauge])(MPa[Gauge]) MUH-GA20VB - MUH-GA20VB

Summary of the content on the page No. 14

OB387-1.qxp 05.2.21 10:03 AM Page 14 HEAT operation Condition indoor:Dry bulb temperature 20.0°C Outdoor:Dry bulb temperature 7,15,20°C Wet bulb temperature 14.5°C Wet bulb temperature 6,12,14.5°C E1 E1 MUH-GA25VB - MUH-GA20VB - 5 5 230V 4 4 230V 3 3 2 2 5 7 10 15 20 21 25(:) 21 (:) 5 7 10 15 20 25 Ambient temperature(˚C) Ambient temperature(˚C) E1 MUH-GA35VB - 6 230V 5 4 3 5 10 15 20 21 25(:) 7 Ambient temperature(˚C) 14 Outdoor unit current (A) Outdoor unit current (A) Outdoor unit current (

Summary of the content on the page No. 15

OB387-1.qxp 05.2.21 10:03 AM Page 15 PERFORMANCE DATA COOL operation (230V) E1 E1 MSC-GA20VB - : MUH-GA20VB - CAPACITY : 2.3(kW) SHF : 0.74 INPUT : 715(W) OUTDOOR DB(:) 21 25 27 30 INDOOR INDOOR Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT DB(:) WB(:) 21 18 2.70 1.51 0.56 572 2.59 1.45 0.56 601 2.48 1.39 0.56 629 2.39 1.34 0.56 658 21 20 2.82 1.24 0.44 601 2.70 1.19 0.44 636 2.62 1.15 0.44 651 2.53 1.11 0.44 679 22 18 2.70 1.62 0.60 572 2.59 1.55 0.60 601 2.48 1.4

Summary of the content on the page No. 16

OB387-1.qxp 05.2.21 10:03 AM Page 16 PERFORMANCE DATA COOL operation (230V) E1 E1 MSC-GA20VB - : MUH-GA20VB - CAPACITY : 2.3(kW) SHF : 0.74 INPUT : 715(W) OUTDOOR DB(:) INDOOR INDOOR 35 40 43 DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.25 1.26 0.56 701 2.07 1.16 0.56 744 1.99 1.11 0.56 758 21 20 2.37 1.04 0.44 729 2.21 0.97 0.44 765 2.13 0.94 0.44 787 22 18 2.25 1.35 0.60 701 2.07 1.24 0.60 744 1.99 1.19 0.60 758 22 20 2.37 1.14 0.48 729 2.21 1.06 0.48 765 2.

Summary of the content on the page No. 17

OB387-1.qxp 05.2.21 10:03 AM Page 17 PERFORMANCE DATA COOL operation (230V) E1 E1 MSC-GA25VB - : MUH-GA25VB - CAPACITY : 2.65(kW) SHF : 0.70 INPUT : 820(W) OUTDOOR DB(:) INDOOR INDOOR 21 25 27 30 DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 3.11 1.62 0.52 656 2.98 1.55 0.52 689 2.86 1.49 0.52 722 2.76 1.43 0.52 754 21 20 3.25 1.30 0.40 689 3.11 1.25 0.40 730 3.02 1.21 0.40 746 2.92 1.17 0.40 779 22 18 3.11 1.74 0.56 656 2.98 1.67 0.56 689 2.86 1.

Summary of the content on the page No. 18

OB387-1.qxp 05.2.21 10:03 AM Page 18 PERFORMANCE DATA COOL operation (230V) E1 E1 MSC-GA25VB - : MUH-GA25VB - CAPACITY : 2.65(kW) SHF : 0.70 INPUT : 820(W) OUTDOOR DB(:) INDOOR INDOOR 35 40 43 DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.60 1.35 0.52 804 2.39 1.24 0.52 853 2.29 1.19 0.52 869 21 20 2.73 1.09 0.40 836 2.54 1.02 0.40 877 2.45 0.98 0.40 902 22 18 2.60 1.45 0.56 804 2.39 1.34 0.56 853 2.29 1.28 0.56 869 22 20 2.73 1.20 0.44 836 2.54 1.12 0.44 877 2

Summary of the content on the page No. 19

OB387-1.qxp 05.2.21 10:03 AM Page 19 PERFORMANCE DATA COOL operation (230V) E1 E1 MSC-GA35VB - : MUH-GA35VB - CAPACITY : 3.5(kW) SHF : 0.66 INPUT : 1090(W) OUTDOOR DB(:) 21 25 27 30 INDOOR INDOOR Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT DB(:) WB(:) 21 18 4.11 1.97 0.48 872 3.94 1.89 0.48 916 3.78 1.81 0.48 959 3.64 1.75 0.48 1003 21 20 4.29 1.54 0.36 916 4.11 1.48 0.36 970 3.99 1.44 0.36 992 3.85 1.39 0.36 1036 22 18 4.11 2.14 0.52 872 3.94 2.05 0.52 916 3.78

Summary of the content on the page No. 20

OB387-1.qxp 05.2.21 10:03 AM Page 20 PERFORMANCE DATA COOL operation (230V) E1 E1 MSC-GA35VB - : MUH-GA35VB - CAPACITY : 3.5(kW) SHF : 0.66 INPUT : 1090(W) OUTDOOR DB(:) INDOOR INDOOR 35 40 43 DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 3.43 1.65 0.48 1068 3.15 1.51 0.48 1134 3.03 1.45 0.48 1155 21 20 3.61 1.30 0.36 1112 3.36 1.21 0.36 1166 3.24 1.17 0.36 1199 22 18 3.43 1.78 0.52 1068 3.15 1.64 0.52 1134 3.03 1.57 0.52 1155 22 20 3.61 1.44 0.40 1112 3.36 1.34


Alternative user manuals
# User manual Category Download
1 Pioneer MUH-GA25VB User manual Air Conditioner 197
2 Pioneer MUH-GA35VB User manual Air Conditioner 54
3 Sony SU-PW2 User manual Air Conditioner 12
4 Sony CV-P12PX User manual Air Conditioner 3
5 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
6 Sony VGN-BX500 User manual Air Conditioner 1
7 Philips 190S5 User manual Air Conditioner 21
8 Philips Comfort-Cire AMC 45 User manual Air Conditioner 7
9 Philips Comfort-Cire AMC 30 User manual Air Conditioner 2
10 Philips CS-E15DB4EW User manual Air Conditioner 4
11 Philips GOGEAR SA3425 User manual Air Conditioner 1
12 Philips 3160 User manual Air Conditioner 7
13 Philips Comfort-Cire AMW User manual Air Conditioner 3
14 Philips Comfort-Cire AMC 25 User manual Air Conditioner 2
15 Philips GoGear SA3446 User manual Air Conditioner 0