Roberts Gorden UHA SERIES 350 user manual

User manual for the device Roberts Gorden UHA SERIES 350

Device: Roberts Gorden UHA SERIES 350
Category: Air Conditioner
Manufacturer: Roberts Gorden
Size: 2.87 MB
Added : 5/30/2014
Number of pages: 48
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Roberts Gorden UHA SERIES 350. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Roberts Gorden UHA SERIES 350.

For your convenience

If looking through the Roberts Gorden UHA SERIES 350 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Roberts Gorden UHA SERIES 350 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Roberts Gorden UHA SERIES 350 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Roberts Gorden UHA SERIES 350 User manual - Online PDF
Advertisement
« Page 1 of 48 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Roberts Gorden UHA SERIES 350 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Roberts Gorden UHA SERIES 350. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

 



 
 

®
 
 


 !
"
""#
$ 
 
%
##"
#!
& 
 
%
"
!

Combat
%
'% 
( )"*
!
'% 
+ ,,"
#"
%
#"
"
UHA-Series
%
"-
"*
!
'% 

!
"
%.
%#
Tubular Unit Heaters
/ -
%
#"
"#!
%
"
%0
#"
!

",
(Standard Range)

Installation, Operation
& Service Manual
Models UHA[S]
150,

Summary of the content on the page No. 2

Summary of the content on the page No. 3

TABLE OF CONTENTS SECTION 1: Heater Safety......................................................1 SECTION 11: User Instructions............................................22 1.1 Manpower Requirements .............................................1 11.1 User Instructions.......................................................22 SECTION 2: Installer Responsibility .....................................2 11.2 Heater Operation ......................................................22 2.1 Wall Tag ......

Summary of the content on the page No. 4

Summary of the content on the page No. 5

TABLE OF FIGURES Figure 1: Installation Clearances and Clearances to Combustibles.............................................................4 Figure 2: Suspension Methods .................................................6 Figure 3: Vent and Roof Detail ..................................................9 Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination ......................................9 Figure 5: Standard Vented Heater - Common Vertical Vent Termination....

Summary of the content on the page No. 6

Summary of the content on the page No. 7

SECTION 1: HEATER SAFETY SECTION 1: HEATER SAFETY Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections. Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operatio

Summary of the content on the page No. 8

® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL SECTION 2: INSTALLER RESPONSIBILITY The installer is responsible for the following: 2.2 Corrosive Chemicals • To install the heater, as well as the gas and electrical supplies, in accordance with applicable  specifications and codes. Roberts-Gordon              recommends the installer contact a Local  Building Inspector or Fire Marshal for guidance.       

Summary of the content on the page No. 9

SECTION 3: CRITICAL CONSIDERATIONS SECTION 3: CRITICAL CONSIDERATIONS 3.1 Basic Information 3.7 Electrical Supply UHA(S) heaters have automatic ignition burners for A permanent 120 V 60 Hz 1 Ø electrical supply is ON/OFF operation only. required for the main electrical power. The heater also requires suitable controls in accordance with Section 9. 3.2 Location and Suspension All models: 3.8 Vent • Must be installed indoors. Choose heater orientation to allow for the proper • Must be install

Summary of the content on the page No. 10

® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL $%& ! '( )  *  "        "      +   *  ,      ,      "#     !   "             *#    #  Figure 1: Installation Clearances and Clearances to Combustibles "" 8""# 8""#  8,'%' 4 $ )7     "$

Summary of the content on the page No. 11

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES 4.1 Gas Codes 4.3 Parking Structures and Repair Garages The type of gas appearing on the nameplate Installation in garages must be in accordance must be the type of gas used. Installation must with the following codes: comply with national and local codes and United States: Standard for Parking Structures requirements of the local gas company. NFPA 88A - latest revision or the Code for Motor

Summary of the content on the page No. 12

® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL SECTION 5: MAJOR COMPONENTS 5.1 General Heaters are designed for installation above 6' (1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points. 5.2 Suspension $%&  '(  -./0      !        

Summary of the content on the page No. 13

SECTION 6: VENTING SECTION 6: VENTING 6.1 Venting mechanical air supply inlet to any building. This heater must be vented in accordance with the The vent shall not terminate within 3' (.9 m) of a rules contained in this manual and with the following window or door that can be opened in any building, national codes and any state, provincial or local any non-mechanical air supply inlet to any building, codes which may apply: United States: Refer to or of the combustion air inlet of any other ap

Summary of the content on the page No. 14

® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 6.2.2 Separated Combustion Heaters 6.5 Vertical Venting (Models UHAS 150 - 400) Vertically vented heaters can be common vented The heaters are designed to be installed as (up to 4 heaters). separated combustion heaters. The vent and air For vent lengths greater than 5' (1.5 m), intake are run as separate pipes to the wall or roof condensation will form. Insulation is recommended terminals. See Page 12, Figure 8.

Summary of the content on the page No. 15

SECTION 6: VENTING 6.7 Vent Material Figure 3: Vent and Roof Detail Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to Page 7, Section 6.2. >  If penetrating a combustible wall or roof, a listed 4 $ thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type B-1 vent material may be used at the roof or wall penetration instead of a thimble. Ensure vent ?

Summary of the content on the page No. 16

® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL Figure 5: Standard Vented Heater - Common Vertical Vent Termination 4# 'A'  " )' <',$# %  )4      $  ,  9 4# 'A'>  8 *<')/&"$,  5 ?   4   "          %    4$  $# 4# 'A'    )D"  ,     $    %$%      9 38   

Summary of the content on the page No. 17

SECTION 6: VENTING Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent Termination *')-*"$, 5$%$ $     $ )$#  E    ""  " , >   D ! ( 9#" *')-*"$,  5$%$ $     12"  $ )$#  E  .C   ""  " , A   D !  D ! 4 $  >  4 $  >  *')-*"$,    5$%$ $  4  @  Model Vent Diameter Terminal P/N

Summary of the content on the page No. 18

>  ® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL Figure 8: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater >  4 $ /'4# A*  A 8 >  :6*++B 9  $ )A#7  , &'@9 3 ) "  -  $  " , :6-/B <'@9 3 $ %   4 $ ?  )A#7  , "  " >  A1 &')*&"$, 5$%$  D ! ( *')-*"$, 9#" 51$%$ >      4  *2)-

Summary of the content on the page No. 19

SECTION 7: AIR SUPPLY SECTION 7: AIR SUPPLY 7.1 Separated Combustion Installation When installed as a separated combustion heater, the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate space around heater to provide air for the axial air distribution fan. 7.2 Unvented Installation It is important to ensure that there is adequate fresh air supply at all times for both combustion and heating requirements in accordance with local and n

Summary of the content on the page No. 20

® COMBAT UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL SECTION 8: GAS PIPING • Meter and service must be large enough to handle all the burners being installed plus any $%& other connected load. The gas pipe which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2" w.c. When gas piping is not included in the layout drawing, contact the local gas supplier. • An isolating valve and union connection should Fire Hazard ! '(


Alternative user manuals
# User manual Category Download
1 Roberts Gorden UHA SERIES 150 User manual Air Conditioner 0
2 Roberts Gorden UHA SERIES 175 User manual Air Conditioner 0
3 Roberts Gorden UHA SERIES 250 User manual Air Conditioner 0
4 Roberts Gorden UHA SERIES 225 User manual Air Conditioner 0
5 Roberts Gorden UHA SERIES 400 User manual Air Conditioner 0
6 Roberts Gorden UHA SERIES 300 User manual Air Conditioner 0
7 Roberts Gorden UHA SERIES 200 User manual Air Conditioner 0
8 Roberts Gorden UHA SERIES 350 User manual Gas Heater 0
9 Sony SU-PW2 User manual Air Conditioner 12
10 Sony CV-P12PX User manual Air Conditioner 3
11 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
12 Sony VGN-BX500 User manual Air Conditioner 1
13 Philips 190S5 User manual Air Conditioner 21
14 Philips Comfort-Cire AMC 45 User manual Air Conditioner 7
15 Philips Comfort-Cire AMC 30 User manual Air Conditioner 2