Honeywell MS-9200UDLSE user manual

User manual for the device Honeywell MS-9200UDLSE

Device: Honeywell MS-9200UDLSE
Category: Smoke Alarm
Manufacturer: Honeywell
Size: 2.53 MB
Added : 5/24/2014
Number of pages: 188
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Honeywell MS-9200UDLSE. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Honeywell MS-9200UDLSE.

For your convenience

If looking through the Honeywell MS-9200UDLSE user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Honeywell MS-9200UDLSE on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Honeywell MS-9200UDLSE to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Honeywell MS-9200UDLSE User manual - Online PDF
Advertisement
« Page 1 of 188 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Honeywell MS-9200UDLSE but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Honeywell MS-9200UDLSE. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1



PN: 52750:A ECN 05-680
Fire Alarm Control Panel
MS-9200UDLS
MS-9200UDLSE
IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #52750
A
11/04/05 Revision:

Summary of the content on the page No. 2

While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede- ing devices, and a fire alarm control panel with remote notifi- termined rate or reaches a predetermined level. Rate-of-rise cation capa

Summary of the content on the page No. 3

Adherence to the following will aid in problem-free Installation Precautions installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to of power before servicing. Control unit and associated equip- lightning-induced transients. Although no system is com- ment may be damaged by remo

Summary of the content on the page No. 4

Notes 4 MS-9200UDLS PN 52750:A 11/04/05

Summary of the content on the page No. 5

Table of Contents SECTION 1: Product Description ........................................................................................................................12 1.1: Features and Options...................................................................................................................................12 1.2: Specifications ..............................................................................................................................................13 1.2.

Summary of the content on the page No. 6

Table of Contents 3.4: Programming Screens Description..............................................................................................................44 3.5: Programming and Passwords ......................................................................................................................44 3.6: Master Programming Level.........................................................................................................................46 3.6.1: Autoprogram .........

Summary of the content on the page No. 7

Table of Contents 3.6.9: Option Modules................................................................................................................................96 3.6.9.1 Annunciators/UDACT ............................................................................................................96 3.6.9.2 Onboard DACT .......................................................................................................................97 3.6.9.2.1 Onboard DACT Enable ..................

Summary of the content on the page No. 8

Table of Contents 4.22.2: Zones ...............................................................................................................................................142 4.22.3: Power...............................................................................................................................................143 4.22.4: Trouble Reminder............................................................................................................................144 4.22.5: T

Summary of the content on the page No. 9

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • Underwriters Laboratories Standards • NFPA 72 National Fire Alarm Code • CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents. NFPA Standards NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code Und

Summary of the content on the page No. 10

CAUTION! HIGH VOLTAGE TRANSFORMER 2 TRANSFORMER 1 10 MS-9200UDLS PN 52750:A 11/04/05 Notification Appliance Circuits EIA-232 NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited) to printer or (Special Application) 2.5 amps max. per circuit. JP6 configured personal computer for Class B using NACKEY card. Basic System Connections (See Style Z illustrated near right edge of board). (nonsupervised) 5 4 3 2 1 For EDP-listed equipment or NAC #1 NAC #3 NAC #4 NAC #2 9 8

Summary of the content on the page No. 11

Peripheral Devices and Their Documents: ACM-8RF AFM-16ATF & ACS Series Doc. #50362 AFM-32AF 51480 Doc. #15970 ACS (EIA-485) Annunciators LDM-32F AFM-16AF Doc. #50055 Doc. #15210 TERM (EIA-485) LCD-80F Annunciators Doc. #51338 SLC Loop Addressable Devices and SLC Wiring Doc. #51309 Battery Connector CHG-75 Charger CHG-120F Charger Doc. # 51315 Doc. #50888 MS-9200UDLS PN 52750:A 11/04/05 11 92udperi.cdr

Summary of the content on the page No. 12

Product Description Features and Options SECTION 1 Product Description The Fire-LiteMS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features. The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection technol

Summary of the content on the page No. 13

Specifications Product Description • Telephone Line Active LEDs • Communication Confirmation (Kissoff) LED • Touchtone/Rotary dialing • Programmable Make/Break Ratio • EIA-232 Printer/PC interface (variable baud rate) • 80-character LCD display (backlit) • Real-time clock/calendar with daylight savings time control • History file with 1,000 event capacity • Advanced fire technology features: Automatic drift compensation Maintenance alert Detector sensitivity test capability (NFPA 72 complian

Summary of the content on the page No. 14

Product Description Specifications Battery (Lead Acid Only) - J9 Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp Maximum Battery Charger Capacity: 18 Amp Hour (MS-9200UDLS cabinet holds maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box. Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the FACP battery charger when using an externa

Summary of the content on the page No. 15

Specifications Product Description EIA-485 (TERM) or EIA-232 (ACS) - TB8 EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +), 3 (Out -), 4 (In -) EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (Ground) EIA-485 (ACS) - TB9 ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead 1.2.1 Current Availability The following figure illustrates the maximum current that is possible for each panel circuit and the to

Summary of the content on the page No. 16

Product Description Controls and Indicators 1.3 Controls and Indicators LCD Display The FACP uses an 80-character HONEYWELL LIFE SAFETY (4 lines X 20 characters) high viewing angle LCD display. The SYSTEM ALL NORMAL display includes a long life LED 10:00A 012102 backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries. LED Indicators LED indicators are provided to annunciate the following conditions:

Summary of the content on the page No. 17

Circuits Product Description 1.4 Circuits SLC Communication Loop One SLC loop is provided standard on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring manual for information on wiring devices. Reference Output Circuits Manual The following output circuits are available on the FACP: • Special Application Power 24 VDC Res

Summary of the content on the page No. 18

Product Description Components 1.6 Components Main Circuit Board The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board. Cabinet See Page The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of th

Summary of the content on the page No. 19

Components Product Description 1.6.2 Intelligent Addressable Modules: Newer Series The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99. Note that a blinking LED on an addressable module indicates communication between the module and the control panel. These dev

Summary of the content on the page No. 20

Product Description Optional Modules 1.7 Optional Modules The MS-9200UDLS main circuit board includes option module connectors for the following module: 4XTMF Transmitter Module The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no ala


Alternative user manuals
# User manual Category Download
1 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7625B User manual Smoke Alarm 11
2 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7635B User manual Smoke Alarm 3
3 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7655B User manual Smoke Alarm 3
4 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7635C User manual Smoke Alarm 6
5 Honeywell 25/50ZS User manual Smoke Alarm 12
6 Honeywell 25/50ZST User manual Smoke Alarm 1
7 Honeywell EXCEL ADT-HRSI User manual Smoke Alarm 7
8 Honeywell ANN-RLY User manual Smoke Alarm 2
9 Honeywell 50ZST User manual Smoke Alarm 0
10 Honeywell C User manual Smoke Alarm 1
11 Honeywell C7015A User manual Smoke Alarm 14
12 Honeywell C7021F User manual Smoke Alarm 0
13 Honeywell C7021B User manual Smoke Alarm 1
14 Honeywell C7021D User manual Smoke Alarm 1
15 Honeywell C7021K User manual Smoke Alarm 0
16 Adobe CS3 User manual Smoke Alarm 1
17 ADT Security Services ADT-LCD40 User manual Smoke Alarm 6
18 ADT Security Services Safewatch Pro 2000 User manual Smoke Alarm 5
19 ADT Security Services SAVS20ADT-1 User manual Smoke Alarm 3
20 ADT Security Services Unimode 9600 User manual Smoke Alarm 7