Sierra Monitor Corporation 4501-XX user manual

User manual for the device Sierra Monitor Corporation 4501-XX

Device: Sierra Monitor Corporation 4501-XX
Category: Smoke Alarm
Manufacturer: Sierra Monitor Corporation
Size: 0.42 MB
Added : 8/29/2014
Number of pages: 25
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Sierra Monitor Corporation 4501-XX. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Sierra Monitor Corporation 4501-XX.

For your convenience

If looking through the Sierra Monitor Corporation 4501-XX user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Sierra Monitor Corporation 4501-XX on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Sierra Monitor Corporation 4501-XX to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Sierra Monitor Corporation 4501-XX User manual - Online PDF
Advertisement
« Page 1 of 25 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Sierra Monitor Corporation 4501-XX but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Sierra Monitor Corporation 4501-XX. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

MODEL 4501-XX
2-Wire Series
TOXIC GAS SENSOR MODULE

APPLICABILITY & EFFECTIVITY
Effective for all Model 4501-XX Modules manufactured after September 1, 2006.
4501-04 FM Pending
4501-05 FM Approved
4501-06 FM Pending

Instruction Manual Part Number T13022
Rev. A

Summary of the content on the page No. 2

Model 4501-XX Toxic Gas Sensor Module FM PERFORMANCE APPROVAL ONLY THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS ARE FM* APPROVED Model 4501-05 Hydrogen Sulfide Gas Sensor Module Sensor Module Model 4501-05 Sensor Module - Hydrogen Sulfide Calibration Equipment Model 1250-01 Gas Sensor Calibration Kit, Type A Model 1260-05 Hydrogen Sulfide in N2, 25 ppm Gas Cylinder Model 1260-45 Hydrogen Sulfide in N2, 10 ppm Gas Cylinder Model 5358-01 Calibration Adapter

Summary of the content on the page No. 3

Model 4501-XX Toxic Gas Sensor Module TABLE OF CONTENTS 1. PRODUCT DESCRIPTION .............................................................................................................................1 1.1 GENERAL........................................................................................................................................................1 1.2 MOUNTING CONFIGURATION...................................................................................................

Summary of the content on the page No. 4

Model 4501-XX Toxic Gas Sensor Module 7.4.2 CABLING INSTALLATION .....................................................................................................................16 7.4.3 SENSOR MODULE INSTALLATION .....................................................................................................16 7.4.4 MOISTURE TRAPS AND RAINSHIELDS..............................................................................................17 7.4.5 STANDARD VOLTAGES .................

Summary of the content on the page No. 5

Model 4501-XX Toxic Gas Sensor Module 1. PRODUCT DESCRIPTION 1.1 GENERAL The Model 4501-XX Toxic Gas Sensor Module is a 2-wire transmitter with 4-20 mA output and it offers a broad array of features including: • 2-wire loop powered • 180 day calibration interval • Selectable ranges • Non-intrusive one-person calibration • Integral LCD 2-line, 20-character display • Stainless steel enclosure and sensor housing • 4-20 mA output • Long sensor life • Rotatable faceplate enables multi-d

Summary of the content on the page No. 6

Model 4501-XX Toxic Gas Sensor Module 1.4 MECHANICAL The sensor module is comprised of the following three primary components: 1.4.1 ENCLOSURE Explosion proof, rain-tight stainless steel electrical housing with three ¾” FNPT conduit hubs. The enclosure cover has a viewing window. The 3 conduit hubs combined with the rotatable faceplate enable the user to mount the module in a variety of configurations. See Figure 1-2 for details. 1.4.2 TRANSMITTER ELECTRONICS Electronic Assembly consist

Summary of the content on the page No. 7

Model 4501-XX Toxic Gas Sensor Module Figure 1-1 Model 4501-05 Hydrogen Sulfide Gas Sensor Module– Dimensions Figure 1-2 Model 4501-05 Hydrogen Sulfide Gas Sensor Module– Orientation Options Page: 3

Summary of the content on the page No. 8

Model 4501-XX Toxic Gas Sensor Module 2. CAUTIONS & WARNINGS 2.1 INTRODUCTION Although the 4501-XX Gas Sensor Module is designed and constructed for installation and operation in industrial applications including hostile environments, caution should be taken to insure that the installation is made in compliance with this instruction manual and that certain procedures and conditions are avoided. This chapter discusses the necessary cautions. Read the entire chapter prior to installation o

Summary of the content on the page No. 9

Model 4501-XX Toxic Gas Sensor Module 3. QUICK START 3.1 OVERVIEW The gas sensor module has been supplied factory calibrated and ready for immediate installation and operation. An installer familiar with installation and operation of gas detection products can use this section to begin immediate use of the module. 3.2 WIRING Provide two conductor shielded wiring from the power supply/control device to the sensor module location. Use wire that is 16 AWG or larger. 3.3 MODULE INSTALLA

Summary of the content on the page No. 10

Model 4501-XX Toxic Gas Sensor Module 4. INSTALLATION 4.1 SENSOR MODULE LOCATIONS The gas sensor module utilizes a diffusion type sensor which should be located close to either the expected source or destination of the gas hazard. If the gas is heavier than air, the sensor module should be installed within 24 inches of the ground or floor. If it is lighter than air, move it above 6’. After optimum locations are determined based on the above recommendations, consideration should be given

Summary of the content on the page No. 11

Model 4501-XX Toxic Gas Sensor Module 1. Remove the transmitter from the module housing by: • Unscrew the two captive panel screws on the faceplate. • Lift the transmitter out of the enclosure. • Unplug the sensor cable from transmitter connector J1. • Remove the sensor assembly from the enclosure hub. 2. Install the module enclosure onto the end of the supply conduit and/or bolt into position as required. NOTE When enclosure earth grounding is required for the installation a grounding

Summary of the content on the page No. 12

Model 4501-XX Toxic Gas Sensor Module 5. OPERATION 5.1 INTRODUCTION The 4501-XX Toxic Gas Sensor Module utilizes a visual menu system operated by means of a magnet. A magnet stick is supplied for this purpose. The menu system is used to calibrate the sensor module, and for maintenance and diagnostic procedures. The following adjustments can be made to the sensor module: Range adjustments (see section 5.4) 4mA and 20mA calibration adjustments (see section 5.4) Span adjustment (see

Summary of the content on the page No. 13

Model 4501-XX Toxic Gas Sensor Module 5.3 MAIN MENU Key Function Display Description Reference M E Mode Switch [M] M E Enter Switch [E] ME Up Switch [ ▲] Previous Menu ME Down Switch [ ▼] Next Menu 4501-XX First screen at power-up, Model and Version XX.XXaA Warm 148 Second screen at start-up, count down of Warm-up XX.XXaA H2S Default Display (example 4501-05) XXX.PPM M E H2S Mode Mode Function: Calibration (example 4501-05) Table 6-1 CALIB: M E H2S Down Mode Function: Maintenance (exampl

Summary of the content on the page No. 14

Model 4501-XX Toxic Gas Sensor Module 5.4 MAINTENANCE SUB-MENU Key Function Display Description Reference H2S Default Display (example 4501-05) XX PPM M E H2S Mode CALIB: ME H2S Down MAINT: M E Enter Calibration 4 mA Menu Enter Cal: 4mA Banner: Use [ ] or [ ] to change 4mA output, [E] when done A multi-meter should be inserted into the current loop to measure the loop current between the power and the sensor module No gas is required for this step M E 4mA Enter Acknowledges 4mA calibr

Summary of the content on the page No. 15

Model 4501-XX Toxic Gas Sensor Module 5.5 DIAGNOSTICS SUB-MENU Description Key Function Display Reference M E H2S Mode Default Display(example 4501-05) XXX PPM M E H2S Enter Go to previous maintenance menu item CALIB ME H2S Down MAINT: ME H2S Down DIAG: M E DIAG: Enter Enter diagnostics sub-menu RawSig M E D-RawSig Enter Voltage reading of the output of the sensor element XXXXmV M E DIAG: Mode Return to diagnostic menu RawSig ME DIAG: Down Ref M E D-Ref Enter Voltage reading of the out

Summary of the content on the page No. 16

Model 4501-XX Toxic Gas Sensor Module 5.5.1 NOTES When selecting the output current requested, an acknowledge message will appear on the screen. Select [E] to accept this message. Whenever a message appears on the screen, select [E] to accept the message. No other action can be taken with messages. Except for the FactInit Menu, the sub-menus in the diagnostics section only provide information and do not cause action. Page: 12

Summary of the content on the page No. 17

Model 4501-XX Toxic Gas Sensor Module 6. CALIBRATION 6.1 CALIBRATION FREQUENCY The sensor module must be calibrated every 180 days. Periodic functional tests are advisable for critical applications and hostile environments. The sensor module microprocessor software includes high-level self checking algorithms which provide continuous sensor diagnostic and self adjustment. 6.2 CALIBRATION PREPARATION Calibration of the sensor is accomplished by simple menu based steps and application of

Summary of the content on the page No. 18

Model 4501-XX Toxic Gas Sensor Module 6.3 DIAGNOSTICS SUB-MENU Key Function Display Description Reference M E H2S Mode Default Display (example 4501-05) or Sub-Routine A CALIB: M E Enter CAL 0 PPM Banner: Apply zero gas, [E] when done Operation: Confirm area clear of gas, or apply zero air to sensor. M E Cal0PPM There is a minimum time to calibrate at 0PPM. If [E] is hit prior to this time Enter Wait.XXX has elapsed, a countdown screen will appear. Zero gas setting completed (Message wil

Summary of the content on the page No. 19

Model 4501-XX Toxic Gas Sensor Module 7. SERVICE 7.1 SENSOR MODULE CONFIGURATION The gas sensor module is comprised of the following sub-assemblies (Figure 7-1): 4501-XX Gas Sensor Module SPL27077 Enclosure SPM27071 Transmitter Assembly XXXXXXX Sensor Assembly (see Appendix B) XXXXXXX Sensor (see Appendix B) There are no field serviceable components below the sub assembly level. ENCLOSURE REPLACEMENT The enclosure should be replaced if the cover threads or conduit threads have bee

Summary of the content on the page No. 20

Model 4501-XX Toxic Gas Sensor Module TRANSMITTER REPLACEMENT The transmitter assembly should be replaced when it is determined that it is unreliable, noisy or cannot be adjusted for calibration. This may occur due to age, corrosion or failed components. To replace the transmitter assembly: a. Remove the cover of the main enclosure o b. Unscrew the two thumb screws in the top of the cover plate, lift the assembly and rotate 90 to relieve the wiring service loop c. Unplug the sensor co


Alternative user manuals
# User manual Category Download
1 Sierra Monitor Corporation Flame Detector 3100 User manual Smoke Alarm 1
2 Sierra Monitor Corporation 3140-01 User manual Smoke Alarm 0
3 Adobe CS3 User manual Smoke Alarm 1
4 ADT Security Services ADT-LCD40 User manual Smoke Alarm 6
5 ADT Security Services Safewatch Pro 2000 User manual Smoke Alarm 5
6 ADT Security Services SAVS20ADT-1 User manual Smoke Alarm 3
7 ADT Security Services Unimode 9600 User manual Smoke Alarm 7
8 ADT Security Services SAVS20ADTG User manual Smoke Alarm 4
9 Aico Ei166RC User manual Smoke Alarm 12
10 Aico Carbon Monoxide Alarm Ei 225EN User manual Smoke Alarm 40
11 Aico Ei161RC User manual Smoke Alarm 5
12 Aico Ei169RF User manual Smoke Alarm 1
13 Aico Ei168RC User manual Smoke Alarm 14
14 Aico Carbon Monoxide Alarms 260 Series User manual Smoke Alarm 0
15 Aico Carbon Monoxide Alarm Ei 220EN User manual Smoke Alarm 0