Streszczenie treści zawartej na stronie nr. 1 
                    
                         
 
GNB
           A division of
            Exide Technologies            
 
 
 
 
 
 
 
 
 
 
 
             Industrial Battery Charger 
 
                   Installation and Operation Manual 
 
 
 
                            S47-0079 REV0410
1                                                                                                                                                                                                                                                             
                    
                    Streszczenie treści zawartej na stronie nr. 2 
                    
                        INDEX                Page Section Description      3 - Safety Instructions      4 1.0 Installation      4 1.1 Receiving      4 1.2 Location      4 1.3 Line Voltage Adjustments      6 1.4 AC Service Requirements      6 1.5 Connecting AC Service to Charger      7 1.6 Grounding the Charger      7 1.7 Battery Connector and Charger Cable      7 1.8 Charging Rate Adjustment      8 2.0 Operation      8 2.1 046-0371 Control      13 3.0 Optional Features      13 4.0 Troubleshooting & Maintenance      15 
                    
                    Streszczenie treści zawartej na stronie nr. 3 
                    
                            WARNING  THIS EQUIPMENT CONTAINS LETHAL VOLTAGE LEVELS.  INSTALLATION AND  SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL      IMPORTANT:  SAVE THESE INSTRUCTIONS!  READ AND FOLLOW ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING, OR  SERVICING CHARGER.  ANY DEVIATION CAN CAUSE SERIOUS AND PERMANENT  DAMAGE.  FAILURE TO FOLLOW THE INSTRUCTIONS VOIDS THE WARRANTY.      1. Install and ground the charger in accordance with the National Electric Code and your local  electric code.  Failure to p
                    
                    Streszczenie treści zawartej na stronie nr. 4 
                    
                          SECTION 1 - INSTALLATION    1.1. Receiving    Immediately upon receipt of the charger, check it against the shipping invoice to ensure the shipment is  complete and undamaged.    Examine the outside of the packing for signs of rough handling before accepting the charger from the  carrier.    If there is evidence of damage, the receipt should be signed, and both copies (carrier's and receiving  copies) marked "Shipment Received Damaged". The carrier's representative should be called  immediatel
                    
                    Streszczenie treści zawartej na stronie nr. 5 
                    
                          NOTE:   When a 120/208/240 AC input unit is set for 120VAC a fuse neutral (brass tube) is required in  the Line 2 (neutral) fuse position.    Fig. 1.3.1.  A.C. Voltage Adjustments  1 Ø 60Hz. (120/208/240)  “A” Voltage Code                                    Fig. 1.3.2.    A.C. Voltage Adjustments    1Ø & 3Ø  60Hz. (208/240/480)    “B” Voltage Code                                      Fig.1.3.3.    A.C. Voltage Adjustments    3 Ø 60Hz. (480/575)    “K” Voltage Code            POWER TRANSFORMER 
                    
                    Streszczenie treści zawartej na stronie nr. 6 
                    
                            1.4.  AC Service Requirements    Follow local code requirements if they are different than the instructions in this manual.  After checking  the transformer connections as described in Paragraph 1.3, refer to Table 1-1, to determine the correct  ratings for the AC cable, AC fuses, and AC service disconnect switch for the line amperes as listed on  the nameplate of the charger for the available AC voltage      TABLE 1-1             Line Amperes Disconnect Switch Fuse Size Amps             000
                    
                    Streszczenie treści zawartej na stronie nr. 7 
                    
                          1.6 Grounding the Charger    The charger must be grounded to the AC system ground for personnel safety.    The green ground wire in the AC input wiring must be connected to the charger ground stud   (Identified by a green dot and ground symbol).      1.7 Battery Connector and Charging Cable    Verify that the connectors on both the battery and the charger are attached so that the positive  output terminal of the charger is connected to the positive battery terminal.    CAUTION: If the polarity
                    
                    Streszczenie treści zawartej na stronie nr. 8 
                    
                          SECTION 2 - OPERATION   The charger utilizes a standard ferro-resonant transformer, which provides isolation from the AC service  line and regulates the charging current. The transformer output is connected to a full-wave bridge of  silicon diodes, which provides DC charging current to the battery.  The starting charge amps and length of time required for a charge vary depending on the charger model.  See the data plate on the charger for information.    2.1.1 046-0371 Control Feature Summary 
                    
                    Streszczenie treści zawartej na stronie nr. 9 
                    
                        observe any defective segments or indicators. When the self-diagnostic is complete, the charge starts if  no delay is set, and the yellow ‘Charging’ indicator lights. The display shows the charging amps and  battery volts per cell along with a message to indicate the charger is in phase 1 of the charge cycle.  If  auto start is disabled, the display shows ‘CHARGER OFF’.  Press STOP to manually start the charge.  When the battery is 80% charged, the charger starts phase 2 of the charge cycle.   W
                    
                    Streszczenie treści zawartej na stronie nr. 10 
                    
                        The 046-0371 control can provide an auto-refresh charge as long as the battery remains  connected to the charger if enabled.  If AC power is lost during the wait period, the control resumes from  where it left off after power is restored.  During the auto-refresh charge, the amp-hours and charge time  are added to the original charge.  The refresh charge consists of 30 minutes at the equalize current.  To  change the auto-refresh settings, refer to the programming section.    2.1.8 Viewing Charg
                    
                    Streszczenie treści zawartej na stronie nr. 11 
                    
                          2.1.9 Charge Indications   The following indications are not necessarily a result of a charger problem.  They are typically caused by  external problems such as AC line, poor battery conditions, connections, etc.  If abnormal charge conditions are  detected, the charge is terminated, the red fault LED lights and the display shows:  DISPLAY DESCRIPTION POSSIBLE CAUSE  Battery voltage did not reach 2.00 V/C within 30 - Shorted Cell  F0  SHORTED minutes. #.##VC is the volts per cell at end of cha
                    
                    Streszczenie treści zawartej na stronie nr. 12 
                    
                          Note: F3 and F4 clear automatically if the battery voltage falls within acceptable limits.  All indications  except F8, F9 and F10 can be cleared by disconnecting the battery. For F8, F9 and F10, correct the  condition that caused the indication and disconnect the battery to clear the indication.  CAUTION: If F8 is showing, and the charger is providing current to the battery, remove AC power  from the charger before disconnecting the battery.    2.1.10 F3 (Low Battery) Override  If battery vol
                    
                    Streszczenie treści zawartej na stronie nr. 13 
                    
                        2.1.12 Programming  To enter programming mode, press and hold the EDIT button and while holding it, press the INFO button.  The  display shows a message describing the current parameter followed by the parameter‘s value.  While in  programming mode, the buttons have the following functions:    STOP: Exit programming mode and save all parameters  =: Shift position of parameter being edited  EDIT: Change value of current position of parameter being edited  INFO: Change parameter to edit    Some of
                    
                    Streszczenie treści zawartej na stronie nr. 14 
                    
                          SECTION 3 - OPTIONAL FEATURES  3.1 Fusible Door-Interlock Switch (JIC Switch)  The door interlock switch assembly connects the AC service to the charger’s input fuses for each AC line.  The switch is mechanically latched by the door so that it must be in the OFF position before the door can  be opened. Operation of the charger is identical to that of the standard model, except the charger cannot  be energized if the door is open.  3.2 Remote Control  The remote control option makes it possible
                    
                    Streszczenie treści zawartej na stronie nr. 15 
                    
                        4.3. AC fuse blows.    POSSIBLE CAUSE    A. Incorrect fuse rating.  B. Incorrect AC voltage.  C. Fuse Block holding clips loose.  D. Shorted transformer winding.    4.4. DC fuse blows.    POSSIBLE CAUSE    A. Reversed battery connector.  B. Incorrect fuse rating.  C. Shorted diode.    4.5. Excessive water loss in battery.    POSSIBLE CAUSE    A. Charging rate is too high. See Section 1.8.  B. Charger amp-hour rating exceeds the battery amp-hour rating.  C. Battery has defective cells.    4.6. Lo
                    
                    Streszczenie treści zawartej na stronie nr. 16 
                    
                          SECTION 5 – REPLACEABLE PARTS    5.1 Ordering Information    The following information must be supplied when ordering a replacement part from your service agent in  order to ensure that the correct part is supplied:    A. Model or Spec. number of charger (Located on charger data plate)  B. Serial number of charger (Located on charger data plate)  C. Schematic reference symbol or part  D. Description of part    5.2  Recommended Spares    The quantity of spares stocked should be increased as the
                    
                    Streszczenie treści zawartej na stronie nr. 17 
                    
                          5.3  Spare Parts List      Part Number          Description   Condensers       008-0002        2 MFD 440 Volt  008-0004        4 MFD 440 Volt  008-0006        6 MFD 440 Volt  008-0008        8 MFD 440 Volt  008-0010       10 MFD 440 Volt  008-0012       12.5 MFD 440 Volt  008-0015       15 MFD 440 Volt  008-0017       17.5 MFD 440 Volt  008-0020       20 MFD 440 Volt  008-0030       30 MFD 440 Volt  008-0040       40 MFD 440 Volt    Resistors  037-0017      1.25 Ohm 100 Watt  037-0018      1.2
                    
                    Streszczenie treści zawartej na stronie nr. 18 
                    
                                                                                                Three Phase Charger Schematic # 02-400  18                                                                                                                                                                                                                                                                                                                                                                                                  
                    
                    Streszczenie treści zawartej na stronie nr. 19 
                    
                                                                                              Single Phase Charger Schematic # 02-416    19                                                                                                                                                                                                                                                                                                                                                                                                 
                    
                    Streszczenie treści zawartej na stronie nr. 20 
                    
                        02-490 (C1,C2,C3 AND C4) TYPICAL CIRCUIT 2 12 11 10 98 765 43 21 NOTES: 1 RESISTOR OPTIONAL 2 DISCONNECT OPTIONAL 3 WATER VALVE OPTIONAL 4 FAN AND FILTER OPTIONAL 5 SHOWN IN HIGH VOLTAGE SETTING 6 OUTPUT TAP ADJUSTMENT MODELS WITH DUAL VOLTAGE PRIMARY'S 7 WILL ONLY HAVE 1,5 AND 6 TAPS 8 MODELS THAT HAVE A SET VOLTAGE WILL ONLY HAVE 1 AND 6 TAPS 3 PHASE, 4 TRANS, DWG. NO. WIRING DIAGRAM: 9 MODELS THAT HAVE DUAL VOLTAGE OR 4 GANG, STANDARD CONFIGURATION. SET VOLTAGE MAY HAVE A SET VOLTAGE DATE: CH