Mitsubishi Electric Air Conditioner Network System
AI controller
PAC-YG63MCA
Installation/Instruction Manual
Table of Contents
Page
1. Safety Precautions ..............................................1
2. Usage ..................................................................2
3. Parts List..............................................................2
4. Specifications ......................................................2
4-1. Device Specifications .........................2
4-2. External
Streszczenie treści zawartej na stronie nr. 2
1 Safety Precautions • Thoroughly read the following safety precautions before use. • Hazards that can occur from incorrect handling are classified by the symbols below: Warning Incorrect handling can result in death, serious injury, etc. Caution Incorrect handling can result in bodily injury and/or structure damage. • After reading this manual, keep this manual for future reference. When the device is reinstalled or repaired, give this manual to those who provide these services. When the user
Streszczenie treści zawartej na stronie nr. 3
2 Usage The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints. Historical measurement data can be displayed via only the G(B)-50A Web browser and TG-2000A. Temperature and humidity cannot be displayed on the G-50A LCD. Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit. The AI controller also features a function that interlocks M-NET devices for indoor units, etc. set in
Streszczenie treści zawartej na stronie nr. 4
4-2. External Dimensions ( 13 ) 46 1 /16 ( 25 ) 45 1 /32 ( 7 ) 200 7 /8 3 29 9 ( /8) 150 (5 /32) 4.5 (3 ) /16 Al controller PAC-YG63MCA [ OUTPUT ] Non-voltage Contact Output Ch1 Ch2 Alarm Alarm [ Output LEDs ] Ch1 Ch2 Alarm Alarm N623 Al controller MODEL PAC-YG63MCA SERVICE REF. PAC-YG60MCA-J INPUT VOLTAGE DC24V;0.2A This device complies with Part15 of the FCC Rules.Operation is WEIGHT 0.6 kg / 1 / 3 8 lb subject to the following two conditions: (1)this device may not cause SERIAL No. harmful
Streszczenie treści zawartej na stronie nr. 5
6 Installation 6-1. Parts Purchased Separately Prepare the following parts to install this device. Required Part Specification Unit fixing screws M4 screw × 4 (* M4: ISO metric screw thread) Commercially available power source: 24 VDC±10% 0.2 A (Minimum loading), SELV circuit, power line with grounding terminal Ripple noise: Lower than 200 mVp-p Power supply for this Compatible specification device Authorized or CE marked products. Subject to regulations: - IEC60950 (or EN60950) - CISPR22/24 (o
Streszczenie treści zawartej na stronie nr. 6
6-2. Installation Instructions The AI controller PAC-YG63MCA does not have a waterproof structure. Be sure to install the AI controller inside a control panel that is located indoors. Prepare a control panel capable of storing this device such as the one shown in the figure. (Install the device in a control 3 panel strong enough to withstand a weight of 0.6 kg [1 /8 lb].) This device can be installed horizontally, or as shown below, vertically. The following diagram also provides a rough esti
Streszczenie treści zawartej na stronie nr. 7
(3) Refer to "7. Wiring Instructions" and connect the wires for the power line, M-NET transmission line, output signal lines, and sensor input signal lines. Output M-NET Sensor input signal lines Power line signal lines Note: • Do not install the sensor input signal lines parallel to or near the M-NET transmission line or power line. Also avoid loop wiring. • Be sure to ground this device, PAC- SC50KUA and 24 VDC Power source. Measurement accuracy AI may be affected if devices are not c
Streszczenie treści zawartej na stronie nr. 8
7-2. Connecting the Power and M-NET Transmission Lines Tightening torque for terminal screws: 1 N·m Connect the M-NET transmission line of this device to a power supply unit (PAC-SC50KUA) for the M-NET transmission line or an outdoor unit (either a centralized control line or indoor CN02 control line can be connected). A/B/S * Only the M-NET circuitry of this device receives the power from the V+/V-/FG M-NET transmission line. The power consumption factor is "1/4" (equivalent to one ME R
Streszczenie treści zawartej na stronie nr. 9
7-3. Connecting the Sensors • For channel 1, select one of the following four types: Pt100 detection, 4 to 20 mADC, 1 to 5 VDC, or 0 to 10 VDC analog input. • For channel 2, select one of the following three types: 4 to 20 mADC, 1 to 5 VDC, or 0 to 10 VDC analog input. • The wire length depends on the specifications of the sensor. However, since the use of long wires makes the device susceptible to noise, using wires shorter than 12 m (39.4 ft) is recommended. Use a shielded line for the senso
Streszczenie treści zawartej na stronie nr. 10
7-4. Connecting Alarm Setpoint Outputs (Non-valtage Contacts) The maximum wire length is 100 m. However, since the use of long wires makes the device susceptible to noise, using wires no more than 10 m long is recommended. To use these, various settings need to be configured. Refer to "8. Initial Settings". Load Caution: Power supply • To use X1 relay, obtain one that satisfies the following V1 (DC) specifications. Operating coil Power supply X1 Field [Applied load] V2 (DC) Connections MAX:
Streszczenie treści zawartej na stronie nr. 11
8 Initial Settings After completing the procedures described in "6. Installation" and "7. Wiring Instructions", set the initial settings in accordance with the procedure described below. (1) M-NET address settings 1s 10s Note: • An address from 01 to 50 can be set. • Set an address that is not the same as that of another unit. The address is set to "01" at factory default. SW06 SW07 In the case of address "41" (2) Use the dip switches to select functions. Select the function required fo
Streszczenie treści zawartej na stronie nr. 12
(3) Turn on the power of this device. Verify that the LED16 (CPU power on) and LED17 (M-NET power on) are lit. (4) Set the time. Set the current time from a system controller (G(B)-50A, TG-2000A) or a Maintenance Tool. (5) Configure the settings of the system controller (G(B)-50A or TG-2000A). Configure settings for the system controller (G(B)-50A or TG-2000A) such as the type of sensor to use and the measurement range. The main items that should be set are shown below. (a) When using Pt100
Streszczenie treści zawartej na stronie nr. 13
9 Dip Switch Functions Supported SW Function OFF ON Remark Channel SW01 1 Selection of the input to use No Yes Specify whether to use the channel 1 input terminal. 4 to 20 mADC/ 0 to 10 VDC Set the type of analog input for channel 1 (1). 2 1 to 5 VDC detection Selection of the analog input * This should also be set in accordance with the selection detection type (1) of analog input type (2) (SW11-1 and 2). Pt100 * The setting of SW01-2 is disabled when SW01-3 is ON. 3– detection Channel 1 4
Streszczenie treści zawartej na stronie nr. 14
10 LED Display Designations The LEDs of this device indicate the upper/lower limit alarm interlock output status and error status of this device. 10-1.Alarm Setpoint Output and Error Displays Display Item Display LED Content Note :On, :Off, :Flashing Power supply status (1) Power supply to CPU LED16 : Lights when the CPU is energized. (CPU power on) : Flashes during M-NET communication. (2) Power supply to M-NET LED17 : Lights when the M-NET is energized. circuit (M-NET power on) Output Ch1, 2 (
Streszczenie treści zawartej na stronie nr. 15
11 System Operation Test Use the following procedure to confirm operation of the system. (1) Configure the settings of this device and the system controller while referring to "8. Initial Settings". (2) Confirm whether the measurement values of channel 1 and channel 2 are displayed on the system controller properly. * Depending on the conditions, compare the measurement values with those of, for example, a commercially available portable thermohygrometer. If the measurement accuracy of the se
Streszczenie treści zawartej na stronie nr. 16
This product is designed and intended for use in the residential, commercial and light-industrial environment. This product at hand is • Low Voltage Directive 2006/95/EC based on the following • Electromagnetic Compatibility Directive EU regulations: 2004/108/EC NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a