                        WSHP-DS-6
March 2000
Water Source
Heat Pump
Water-to-Water
Model WPWD
WSHP-DS-6                                                                                                                                                                                                                                                                                                                                                                                                                                     
                    
                    Краткое содержание страницы № 2 
                    
                        Introduction The WPWD product is a heating In the heating mode, the water-to- and cooling hydronic fluid water-to- water unit efficiently extracts heat  water heat pump capable of pro- from a water source (source side)  ducing water temperature up to such as a well, lake, boiler/tower  loop or closed ground loop heat-ex- 130 F or temperatures down to changer, then transfers the heat to  25 F. This extended operating  another flow of water (load side).  range offers great opportunities in  The am
                    
                    Краткое содержание страницы № 3 
                    
                        Table of Contents Introduction 2 Features and Benefits 4 Model Number Description 7 General Data 8 Application Considerations 9 Electrical Data 18 Performance Data 19 Dimensional Data 25 Wiring Diagram 28 Accessory Options 30 Mechanical Specifications 31 3                                                                                                                                                                                                                                                    
                    
                    Краткое содержание страницы № 4 
                    
                        Features General and Benefits WPWD cabinet includes full length  General channel stiffeners underneath the  unit. The water source heat pump model  WPWD (water-to-water) offers a  Heat Exchanger range of capacities from 2 tons to 6  The water to refrigerant heat ex- tons. All units are housed in one  changers are made of stainless  standard compact cabinet.  steel brazed plate. This design pro- Cabinet vides a larger amount of surface  area for heat exchange between  The cabinet, which allows ea
                    
                    Краткое содержание страницы № 5 
                    
                        Features Controls and Benefits 24 Volt Controls All electrical controls and safety de- 50 VA Transformer Lockout vices are factory wired, tested, and 24 VAC Contactor Relay mounted in the unit. The control package includes: Ground  Compressor contactor  24 Volt transformer  Lockout relay  Compressor run capacitor (1- Compressor phase units only) Run Capacitor  Reversing valve coil (For heat  Low Voltage pump only) High Voltage 2 Amp Fuse  Fuse (for desuperheater) 10 Pole Terminal (for use 
                    
                    Краткое содержание страницы № 6 
                    
                        Features Heat and Recovery Benefits The unit employs a circulating pump  Desuperheater Option to move water through a double wall  The desuperheater option is a heat  heat exchanger. It then returns the  recovery system packaged within  heated water to the water tank. This  the water-to-water unit. This option  water is heated by superheated re- captures heat energy from the heat  frigerant discharge gas from the  pump for considerable cost savings  compressor. This heat energy can  all year. Si
                    
                    Краткое содержание страницы № 7 
                    
                        Model Number Description 1 5 10 15 Digit 11: Freeze Protection Digits 1 & 2: Product Type (source side) WP = Trane Commercial Water 1 = Brazed Plate Heat Exchanger Source Heat Pump with 35 F (1.67 C) Freezestat 2 = Brazed Plate Heat Exchanger Digit 3: Product Configuration with 20 F (-6.67 C) Freezestat W = Water-to-Water Digit 4: Development Sequence D Digit 12: Freeze Protection (load side) 1 = Brazed Plate Heat Exchanger Digits 5-7: Unit Nominal Capacity with 35 F (1.67 C) Freezestat 024 = 24
                    
                    Краткое содержание страницы № 8 
                    
                        General Data Table G-1: Physical Data (English) Model: WPWD 024 036 042 048 060 072 Width of cabinet (in) 23 23 23 23 23 23 Width of cabinet and connections (in) 24.8 24.8 24.8 24.8 24.8 24.8 Unit Size Height (in) 24.3 24.3 24.3 24.3 24.3 24.3 Depth (in) 23.3 23.3 23.3 23.3 23.3 23.3 Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll R-22 Refrigerant (lbs) 3.25 3.375 3.50 4.00 4.25 4.25 Approximate Weight  With crate (lbs) 163 183 203 214 244 277 (lbs) Table G-2: Specifications (English) 
                    
                    Краткое содержание страницы № 9 
                    
                        Application Considerations Closed Loop System Closed loop systems (both ground source and surface water) provide heat rejection and heat addition to maintain proper water source temperatures. Operating and maintenace cost are low because an auxillary fossil fuel boiler and cooling tower are not required to maintain the loop temperature. The technology has advanced to the point where many electric utilities and rural electric cooperatives are offering incentives for the installation of geothermal
                    
                    Краткое содержание страницы № 10 
                    
                        Application Considerations Open Loop System Where an existing or proposed well can provide an ample supply of suitable quality water, ground water systems may be very efficient. (See Figure 7) Operation and benefits are similar to those for closed loop systems. There are however several considerations that should be addressed prior to installation.  An acceptable way to discharge the  significant volume of used water from  the heat pump should be defined. It may  be necessary to install a recha
                    
                    Краткое содержание страницы № 11 
                    
                        Application Source Side Considerations vs. Load Side source side heat exchanger to the  Source vs. Load load side heat exchanger. The model WPWD water-to-water  The “load side” heat exchanger  system contains two water to refrig- takes the place of a DX (direct ex- erant heat exchangers. The two  pansion) air coil. It provides treated  heat exchangers enable the system  fluid (hot or cold) to a mechanical  to be divided into a source and load  device. These mechanical devices  separation. includ
                    
                    Краткое содержание страницы № 12 
                    
                        Application Closed Loop Considerations Geothermal Hydronic Ice Melting Via a Water-to-Water Unit Geothermal Space Temperature Heating / Cooling Refrigeration Equipment (Closed) Ground Loop Heat Exchanger Cold climates may take an even Geothermal Typical Benefits greater advantage of the heat Integrated System  Annual energy savings means  rejected by the stores refrigeration The Trane ground source heat lower operational costs equipment and space conditioning pump is highly efficient in service
                    
                    Краткое содержание страницы № 13 
                    
                        Application Fresh Air Considerations Ventilation Water-Out Fresh Air Ventilation (source) with Water-to-Water Units Water-Out Water-In (load) (source) Water-In Exhaust (load) Air Fresh Air Geothermal Space Heating and Cooling (Closed) Ground Loop Heat Exchanger Water-to-Water and Fresh Air Ventilation Geothermal energy systems take  the makeup air unit hydronic coil to  advantage of the fact that  heat the makeup air to maintain  subsurface earth temperatures are  building requirements. This  co
                    
                    Краткое содержание страницы № 14 
                    
                        Application Fresh Air Considerations Ventilation Mechanical EXHAUST OUTSIDE AIR AIR HOT WATER COIL AIR HANDLER AIR HANDLER EXP TANK AUTOMATIC AIR VENT HAND PUMP WPWD DRAIN VA PRESSURE WPWD RELIEF VA WPWD WPWD BALL VA SUPPLY RETURN 14 EXHAUST AIR FROM TOILET RMS EXHAUST AIR TO HEAT PUMPS                                                                                                                                                                                                                     
                    
                    Краткое содержание страницы № 15 
                    
                        Application Central  Considerations Pumping System 6 7 1 5 2 4 3 Figure 10: Central pumping system installation minal devices with 45 F or General Central Pump 120 F fluid. Application A central pumping system involves  The sound attenuation pad  should be slightly oversized for  a single pump design usually locat-  Ball valves should be installed  unit. This field supplied product  ed within a basement or mechanical in the supply and return lines  is recommended for sound  for unit isolatio
                    
                    Краткое содержание страницы № 16 
                    
                        Application Well Water Considerations Systems 7 6 5 9 8 1 3 2 4 Figure 11: Well water installation  The sound attenuation pad  Well Water General should be slightly oversized for  Application the unit. This field supplied  A well water application involves an  product is recommended for   Ball valves should be installed  open loop water supply. The water  sound absorption of unit. in the supply and return lines  is drawn from an open well or pond   The low voltage control con- for unit iso
                    
                    Краткое содержание страницы № 17 
                    
                        Application Distributed Considerations Pumping System 8 7 6 1 5 2 4 3 Figure 12: Distibuted pumping installation  The sound attenuation pad  General Earth Coupled should be slightly oversized for  Application the unit. This field supplied  A distributed pumping system con- product is recommended for  tains either a single or dual pump  Ball valves should be installed  sound absorption of unit. module connected directly to the in the supply and return lines   The low voltage control con- fo
                    
                    Краткое содержание страницы № 18 
                    
                        Electrical Data Table E-1: Electrical Data  024 036 042 048 060 072 Model: WPWD Voltage 208-230/60hz/1phase Compressor RLA 11.4 15 18.4 20.4 28 32.1 Compressor LRA 56 73 95 109 169 169 Minimum Circuit Ampacity 16 21 25.8 28.6 39 45 Max Fuse Size 25 30 40 45 60 70 Aux Pump Amps 2.5 2.5 2.5 2.5 2.5 2.5 Desuperheater Min Cir Ampacity 14.3 18.8 23 25.5 35 40.1 Desuperheater Pump RLA 0.4 0.4 0.4 0.4 0.4 0.4 Voltage 208-230/60hz/3phase Compressor RLA - 10.7 11.4 13.9 20 19.3 Compressor LRA - 63 77 88