APC INROOM SC ACPSC3500 user manual

User manual for the device APC INROOM SC ACPSC3500

Device: APC INROOM SC ACPSC3500
Category: Air Conditioner
Manufacturer: APC
Size: 1.36 MB
Added : 12/21/2013
Number of pages: 32
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for APC INROOM SC ACPSC3500. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with APC INROOM SC ACPSC3500.

For your convenience

If looking through the APC INROOM SC ACPSC3500 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual APC INROOM SC ACPSC3500 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual APC INROOM SC ACPSC3500 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
APC INROOM SC ACPSC3500 User manual - Online PDF
Advertisement
« Page 1 of 32 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual APC INROOM SC ACPSC3500 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to APC INROOM SC ACPSC3500. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

User Manual
InRoom SC
60 Hz
ACPSC2000
ACPSC3500
ON/OFF MODE FAN SLEEP
InRoom SC TEMP TIME

Summary of the content on the page No. 2

Summary of the content on the page No. 3

American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corpora- tion to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, American Power Conversion Corpo- ration assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based o

Summary of the content on the page No. 4

Summary of the content on the page No. 5

Contents General Information........................................................ 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 About the InRoom SC Portable Cooling Units . . . . . . . . . . . . . . . . . 1 Safety symbols that may be used in this manual . . . . . . . . . . . . . . 2 Cross-reference symbol used in this manual . . . . .

Summary of the content on the page No. 6

Display Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Display Screen Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Function Button and Indicator Light Operation . . . . . . . . . . . . . . . 16 Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Maintenance................................................................... 19 Clean the exterior . . . . . . . . . . .

Summary of the content on the page No. 7

General Information Overview Save these instructions This manual contains important instructions that must be followed during the installation of this equipment. About the InRoom SC Portable Cooling Units InRoom SC cooling units are portable, compact air conditioners designed for spot-cooling, emergency- cooling, and after-hours cooling of server closets, and data centers. InRoom SC ACPSC2000 provides 2.9 kW (9,900 BTU) of cooling capacity. InRoom SC ACPSC3500 provides 3.5 kW (12,000 BTU) of

Summary of the content on the page No. 8

Safety symbols that may be used in this manual Electrical Hazard: Indicates an electrical hazard which, if not avoided, could result in injury or death. Danger: Indicates a hazard which, if not avoided, could result in severe personal injury or substantial damage to product or other property. Warning: Indicates a hazard which, if not avoided, could result in personal injury or damage to product or other property. Caution: Indicates a potential hazard which, if not avoided, could result in per

Summary of the content on the page No. 9

Safety Electrical Hazard: Connect the equipment to a 3-wire AC outlet (two poles plus a ground). The receptacle must be connected to a dedicated, properly grounded 120 volt 60Hz branch circuit rated for 20 amp main protection (fuses/circuit breaker). Connection to any other power source may result in a shock hazard or damage to the cooling unit. Do not cut or remove the ground from the power cord plug. Use the cooling unit with the supplied power cord only. Do not use an extension cord with t

Summary of the content on the page No. 10

ON/OFF MODE FAN SLEEP InRoom SC TEMP TIME MODE TIMER SEND DRY Hr. + °F - °F Min ON/OFF S EEP L FAN Storing the Cooling Unit If the cooling unit will not be installed immediately, replace the packaging to protect from damage and dust. Store the cooling unit indoors in a climate controlled, dry place. Caution: Leaving the cooling unit uncovered and exposed to the elements can cause damage and voids the factory warranty. Cooling Unit Packaging Recycle the packaging material when possible. Do no

Summary of the content on the page No. 11

Inspecting the Cooling Unit Your cooling unit has been tested and inspected before shipment. To ensure that the cooling unit has not been damaged during transit, carefully inspect the cooling unit immediately upon receipt. Verify that all parts ordered were received as specified. See “Inventory” on page 6. Caution: Do not tip or place the unit on its side. Filing a claim If damage is identified on receipt of the cooling unit, note the damage on the bill of lading and file a damage claim with

Summary of the content on the page No. 12

MODE TIMER Tools Required Phillips head screwdriver Inventory The cooling unit includes the remote control storage bracket, hardware, batteries, the remote control, and the exhaust kit. See “Remote Control” on page 17 for more information. See “Exhaust kit” on page 10 for contents. Item Description Item Description Cooling unit Exhaust hose 1 4 Ceiling adapter Exhaust cap 2 5 Phillips head screw ST 4.2 x 9.5 (2) Remote control 3 6 6 InRoom SC 60 Hz User Manual SEND DRY Hr. + °F - °F Min ON/OF

Summary of the content on the page No. 13

O EE N/OFF MODE FAN SL P InRoom SC TEMP TIME MODE TIMER SEND DRY Hr. + °F Min - °F ON/OFF SL EEP FAN Component Identification ACPSC2000 and ACPSC3500 Item Description Control panel 1 Vertical air louver 2 Remote control / storage 3 Air filter / upper air intake (evaporator) 4 Air outlet (heat exchanger) 5 Power cord 6 Lower air intake (condenser) 7 Water outlet drain 8 Caster 9 Lower air intake (condenser) : Handle ; InRoom SC 60 Hz User Manual 7 ON/OFF MODE FAN SLEEP InRoom SC TEMP TIME na335

Summary of the content on the page No. 14

Power plug Electrical Hazard: This equipment requires an LCDI plug. Use only the power cord supplied with the equipment. IN THE EVENT THIS DEVICE TRIPS, THE CAUSE OF THE MALFUNCTION IS TO BE CORRECTED BEFORE 1 FURTHER USE OF THE DEVICE. SEE 4 OWNERS MANUAL FOR ADDITIONAL INFORMATION. 2 TESTING: 3 1. PRESS TEST BUTTON. LINE SHOULD TRIP. 2. PRESS RESET BUTTON FOR USE. DO NOT USE IF ABOVE TEST FAILS. Item Description 1 15 amp plug 2 Green (Power ON) LED 3 Reset button 4 Test button Importan

Summary of the content on the page No. 15

> 500 (20) Installation Location Requirements When deciding where to locate the cooling unit, consider cooling needs, air flow, and the location of the electrical outlet. The cooling unit can be no more than 2.4 m (8 ft) from the electrical outlet, condenser intake and exhaust access. Cooling needs. Position the cooling unit as close as possible to the main heat source that requires cooling. Air flow. Position the rear of the cooling unit at least 500 mm (20 in) away from a wall or othe

Summary of the content on the page No. 16

E P ON/OFF MODE FAN SL EP InRoom SC TEM TIME MODE TIMER SEND Y DR Hr. + °F - °F Min ON/OFF SLEEP FAN Exhaust Duct Assembly Dry Mode. Exhaust air must be allowed to return to the room in order for dehumidification to take place. Do not connect the exhaust hose to vent it outside the room. Continuous drainage for the condensate drain pan must be provided or it will fill up and the unit will automatically shut down until it is emptied. Cool Mode. Exhaust air must vent outside the room when usin

Summary of the content on the page No. 17

Installation. Exhaust air can be vented to the outside through the ceiling. The cooling unit should be positioned a minimum of 500 mm (20 in) from any wall; either at the back or on the sides. In a dropped ceiling, the ceiling adapter can be installed in place of one of the ceiling tiles. 1. Position the end of the exhaust hose so the small tabs line up with the holes in the ceiling adapter. 1 Insert the exhaust hose into the ceiling adapter and 2 turn the exhaust hose counterclockwise slightl

Summary of the content on the page No. 18

ON/OFF MODE FAN SLEEP InRoom SC TEMP TIME MODE TIMER SEND DRY Hr. + °F Min - °F N/OF O F SLEEP FAN Condensate Drain The InRoom SC utilizes evaporative technology, which eliminates the need for a condensate tank. To manage any excess condensation, a drain pan is located in the bottom of the unit. When the drain pan is full, a light will flash on the display and an alarm will sound to alert you. The cooling unit will automatically shut down. Caution: The cooling unit must be turned off and unp

Summary of the content on the page No. 19

Continuous draining Note: Continuous drainage is recommended when the unit is used in DRY mode. Caution: Condensate draining is done by gravity. Do not run a drain hose to a drain that is located above the drain port of the cooling unit. InRoom SC 60 Hz User Manual 13 na3393a

Summary of the content on the page No. 20

Operation Control Panel ON/OFF MODE FAN SLEEP TEMP TIME InRoom SC Function Button Locations Item Function Description Power control Turn the cooling unit On and Off 1 Mode selection Three mode control settings: Cool, Dehumidify, and Fan. 2 The settings are adjusted by pressing the Mode Control Button. Remote control infrared Receives commands sent from the remote control. 3 receiver Fan speed control Press the Fan Speed Control button to move through the three settings: 4 Low, Medium and High


Alternative user manuals
# User manual Category Download
1 APC INROOM ACPCW40-150 User manual Air Conditioner 23
2 APC AP7004 User manual Air Conditioner 5
3 APC INROOM ACPDX21-86 User manual Air Conditioner 9
4 APC INROOM ACPSC3000 User manual Air Conditioner 11
5 APC INROOM SC ACPSC2000 User manual Air Conditioner 9
6 APC NETWORKAIR ACPA4000 User manual Air Conditioner 7
7 APC AP7003 User manual Air Conditioner 2
8 Sony SU-PW2 User manual Air Conditioner 12
9 Sony CV-P12PX User manual Air Conditioner 3
10 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
11 Sony VGN-BX500 User manual Air Conditioner 1
12 Philips 190S5 User manual Air Conditioner 21
13 Philips Comfort-Cire AMC 45 User manual Air Conditioner 7
14 Philips Comfort-Cire AMC 30 User manual Air Conditioner 2
15 Philips CS-E15DB4EW User manual Air Conditioner 4